whatsapp
backtop
6491B LSZH Single Core Cable to BS7211 / BS EN 50525-3-41
6491B LSZH single core cable to BS7211 and BS EN 50525-3-41 is designed for fixed wiring, conduit wiring, trunking systems and protected building wiring applications.
6491B to BS 7211 (New BS EN 50525-3-41).pdf Contact us

Application and Description

6491B LSZH single core cable to BS7211

and BS EN 50525-3-41 is designed for

fixed wiring and building wiring

applications.


It is suitable for residential,

commercial, industrial and public

building installations.


Typical applications include conduit

wiring, trunking systems, switchgear,

distribution boards, control panels

and electrical cabinets.


The cable is commonly used where

low smoke zero halogen performance

is required to reduce smoke emission

and corrosive gas release in the event

of fire.


The LSOH thermosetting insulation provides

reliable electrical performance,

thermal stability and safer fire behaviour

for indoor wiring systems.


6491B cable is normally used as a

single core insulated wire.


It should be installed in conduit,

trunking, panels or other protected

wiring systems where mechanical protection

is required.


Solid conductor, stranded conductor

and flexible conductor options may be

available according to project requirement.


The cable should be selected according to

voltage rating, conductor class,

conductor size, insulation colour,

installation method and project specification.


Cable Construction

  • - Bare copper made of solid/strands conductor

  • - Solid to BS 6360 CL-1 or IEC 60228 CL-1(H07Z-U)

  • - Stranding to BS 6360 CL-2 or IEC 60228 CL-2(H07Z-R)

  • - Stranding to BS 6360 CL-5 or IEC 60228 CL-5(H07Z-K)

  • - LSOH thermosetting core insulation type EI5

Core Identification

Black, Blue, Green/Yellow, Red, Yellow, White, Violet, Brown, Grey, Orange, Pink

Technical Characteristics

  • - Working voltage: 450/750v

  • - Test voltage: 2500 volts

  • - Minimum bending radius: up to 10 mm^2 - 3xoverall diameter; above 25 mm^2 - 6xoverall diameter

  • - Operating temperature: +0o C to +90o C

  • - Short circuit temperature: +250o C

  • - Insulation resistance: 10 MΩxkm

  • - Halogen free acc. to EN 50267-2-1 / IEC 60754-1

  • - Smoke density acc. to EN 50268-2 / IEC 61034-2

  • - Corrosivity of gases acc. to EN 50267-2-2, IEC 60754-2

  • - Flame retardancy acc. to EN 50265-2-1, IEC 60332-1

Cable Parameter

AWG
(No of Strands/
Strand Diameter)
No. of Cores x
Nominal Cross
Sectional Area
#xmm^2
Nominal
Thickness of
Insulation
mm
Nominal
Overall
Diameter
mm
Nominal
Copper
Weight
kg/km
Nominal
Weight
kg/km
16(solid)1x1.572.814.420
14(solid)1x2.583.32430
12(solid)1x483.83845
10(solid)1x684.35865
8(solid)1x10105.596105
16(7/24)1x1.50.73.014.421
14(7/22)1x2.50.83.62433
12(7/20)1x40.84.13949
10(7/18)1x60.84.75871
8(7/16)1x101696114
6(7/14)1x1616.8154172
4(7/12)1x251.28.4240265
2(7/10)1x351.29.3336360
1(19/13)1x501.410.9480487
2/0(19/11)1x701.412.6672683
3/0(19/10)1x951.614.7912946
4/0(37/12)1x1201.61611521174
300MCM(37/11)1x1501.817.914401448
350MCM(37/10)1x1852.020.017761820
500MCM(61/11)1x2402.222.723042371
-(61/10)1x3002.425.429803050
-(61/9)1x4002.628.837653842
-(61/8)1x5002.832.847254900
-(127/10)1x6302.836.562056334
16(30/30)1 x 1.573.514.424
14(50/30)1 x 2.5842435
12(56/28)1 x 484.83851
10(84/28)1 x 6865871
8(80/26)1 x 10106.796118
6(128/26)1 x 16108.2154180
4(200/26)1 x 251210.2240278
2(280/26)1 x 351211.5336375
1(400/26)1 x 501413.6480560
2/0(356/24)1 x 701416672780
3/0(485/24)1 x 951618.4912952
4/0(614/24)1 x 1201620.311521200
300 MCM (765/24)1 x 1501822.714401505
350 MCM (944/24)1 x 1852025.317761845
500MCM(1225/24)1 x 2402228.323042400

KEY FEATURES


- Designed according to BS7211 requirements

- Also related to BS EN 50525-3-41

- 6491B single core cable type

- LSOH / LSZH thermosetting insulation

- Low smoke zero halogen performance

- Suitable for fixed wiring installation

- Suitable for conduit and trunking systems

- Suitable for switchgear and distribution boards

- Suitable for control panels and electrical cabinets

- Available with different conductor classes



SELECTION NOTES


Before quotation, please confirm:


- Voltage rating

- Conductor size

- Conductor class

- Insulation colour

- Cable length

- Installation method

- Required standard or project specification

- Packing requirement

- Destination port or delivery address


6491B cable is commonly selected for

fixed wiring and building wiring

applications where low smoke zero

halogen performance is required.


It is suitable for conduit wiring,

trunking systems, distribution boards,

switchgear, control panels and protected

building wiring systems.


As a single core insulated cable, it

should be installed in conduit, trunking,

panels or other protected wiring routes

according to project specification.



RELATED CABLE TYPES


- 6491B cable

- BS7211 cable

- BS EN 50525-3-41 cable

- 2491B cable

- 6181B cable

- 6182B cable

- 6183B cable

- 6241B cable

- 6242B cable

- 6243B cable

- LSZH building wire

- Fixed wiring cable



FAQ


What is 6491B cable used for?


6491B cable is used for fixed wiring,

conduit wiring, trunking systems,

distribution boards, switchgear,

control panels and electrical cabinets.



What standard does 6491B cable follow?


6491B cable is designed according to

BS7211 requirements and is also related

to BS EN 50525-3-41.



Is 6491B cable LSZH?


Yes. 6491B cable uses LSOH / LSZH

thermosetting insulation to help reduce

smoke emission and corrosive gas release

in the event of fire.



Is 6491B cable sheathed?


No. 6491B is generally a single core

insulated cable.


It is not normally described as a

sheathed power cable.



Is 6491B cable armoured?


No. 6491B is not an armoured cable.


It should be installed in conduit,

trunking, panels or other protected

wiring systems where mechanical protection

is required.



What is the difference between 6491B and 2491B?


6491B is commonly used for fixed wiring

and building wiring applications.


2491B is commonly used where greater

flexibility is required for panel wiring

and equipment wiring.



Where is 6491B cable commonly installed?


It is commonly installed in buildings,

public facilities, schools, hospitals,

airports, offices, control panels,

switchgear and distribution boards.



What information is required for quotation?


Please confirm voltage rating,

conductor size, conductor class,

insulation colour, cable length,

installation method and required standard.


Destination port or delivery address

is also required.



Can BURYCABLE supply 6491B cable?


Yes. BURYCABLE can supply 6491B LSZH

single core cables according to project

voltage, conductor size, conductor class,

colour, length and packing requirements.