This product is a low-voltage power cable rated at 0.6/1kV, featuring a 3-core plus earth conductor configuration. The conductors are made of bare soft copper, insulated with XLPE (cross-linked polyethylene), and sheathed with a PVC (polyvinyl chloride) outer jacket. It is also equipped with a galvanized steel wire armored layer. The product complies with the GB/T 12706.1-2020 national standard and CCC mandatory certification, while also meeting international standards such as AS/NZS 5000.1, AS/NZS 3008, and AS/NZS 1125.
Designed specifically for fixed installation applications such as building electrical systems and industrial plants, this cable offers excellent electrical performance, mechanical strength, and environmental resistance. It is suitable for various complex and demanding installation environments, including direct burial, conduit, and overhead applications. The armored layer provides reliable tensile and compressive protection, while the orange PVC sheath (other colors customizable) ensures good weather resistance and visibility.
Available in a range of cross-sectional areas from 16mm² to 240mm², this cable delivers high current-carrying capacity, low voltage drop, and stable impedance characteristics. It serves as a core cable solution for power transmission and distribution networks, equipment power supply, and main or branch power lines. We provide comprehensive technical parameters and selection support. Inquiries are welcome.
AS/NZS 5000.1
AS/NZS 3008
AS/NZS 1125
| Conductor | Plain annealed copper. |
| Insulation | XLPE X-90. |
| Insulation colour: | 3C + E – Red, White, Blue, Green/yellow |
| Bedding: | Polyvinylchloride compound PVC 5V-90 |
| Bedding colour: | Black |
| Armour: | Galvanised Steel Wire |
| Sheath: | Polyvinylchloride compound PVC 5V-90 |
| Sheath colour: | Orange, other colors are available upon request |
| Conductor | Current Ratings | Electrical Characteristics | |||||
|---|---|---|---|---|---|---|---|
| Nominal Area mm^2 | Unenclosed In Air A | Buried Direct A | Buried In Ducts A | Maximum DC Resistance @20°C Ohm/km | Maximum AC Resistance @90°C Ohm/km | Reactance Ohm/km | Three Phase Voltage Drop @90°C mV/Am |
| 16 | 83 | 110 | 83 | 1.15 | 1.47 | 0.0805 | 2.55 |
| 25 | 110 | 145 | 110 | 0.727 | 0.927 | 0.0808 | 1.61 |
| 35 | 135 | 170 | 135 | 0.524 | 0.669 | 0.0786 | 1.17 |
| 50 | 170 | 205 | 160 | 0.387 | 0.494 | 0.0751 | 0.868 |
| 70 | 215 | 250 | 200 | 0.268 | 0.343 | 0.0741 | 0.609 |
| 95 | 265 | 300 | 240 | 0.193 | 0.248 | 0.0725 | 0.450 |
| 120 | 305 | 345 | 275 | 0.153 | 0.197 | 0.0713 | 0.366 |
| 150 | 350 | 385 | 310 | 0.124 | 0.160 | 0.0718 | 0.307 |
| 185 | 405 | 435 | 355 | 0.0991 | 0.129 | 0.0720 | 0.259 |
| 240 | 480 | 500 | 420 | 0.0754 | 0.0998 | 0.0709 | 0.216 |
| Nom. conductor area mm^2 | Conductor No./ OD | Nom. insulation thickness mm | Nom. earth conductor area mm^2 | Nom. earth conductor insulation thickness mm | Nom. diameter over bedding mm | Armour diameter mm | Nom. overall diameter mm | Approx. mass kg/km |
|---|---|---|---|---|---|---|---|---|
| 16 | 7/1.70 | 0.7 | 6 | 0.7 | 17.5 | 1.25 | 22.8 | 1285 |
| 25 | 7/2.14 | 0.9 | 6 | 0.7 | 22.2 | 1.6 | 26.7 | 1845 |
| 35 | 7/2.65 | 0.9 | 10 | 0.7 | 23.5 | 1.6 | 28.7 | 2315 |
| 50 | 19/1.89 | 1.0 | 16 | 0.7 | 26.7 | 1.6 | 32.0 | 2935 |
| 70 | 19/2.24 | 1.1 | 25 | 0.9 | 31.7 | 2.0 | 38.3 | 3880 |
| 95 | 19/2.65 | 1.1 | 25 | 0.9 | 25.6 | 2.0 | 43.1 | 5250 |
| 120 | 19/2.94 | 1.2 | 35 | 0.9 | 39.9 | 2.0 | 45.4 | 5765 |
| 150 | 19/3.28 | 1.4 | 50 | 1.0 | 41.1 | 2.5 | 51.4 | 7560 |
| 185 | 37/2.65 | 1.6 | 70 | 1.1 | 46.1 | 2.5 | 56.6 | 9220 |
| 240 | 37/2.94 | 1.7 | 95 | 1.1 | 52.4 | 2.5 | 63.3 | 11740 |