FLP300-V2-U/R/K Series Cable is an internationally standard-compliant PVC-insulated flame-retardant cable specifically designed for 300/500V low-voltage electrical systems. With excellent safety performance, diverse structural configurations, and stable electrical transmission capacity, it is widely applicable to building wiring, industrial equipment, home decoration, internal wiring of electrical installations, and other scenarios, providing reliable power connection guarantee for various electrical environments.
Basic design to BS EN 50525-2-31(formerly BS 6004:2000)
| Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2 |
300/500V
| Conductor | H05V-U | Class 1 solid copper conductor to BS EN 60228. |
| H05V-R | Class 2 stranded copper conductor to BS EN 60228. | |
| H05V-K | Class 5 stranded copper conductor to BS EN 60228. | |
| Insulation | PVC Type TI 3 according to BS EN 50363-3 | |
Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow. Bicolours of any combination of the above mono-colours are permitted.
| Maximum temperature range during operation (PVC) | 90°C | |
| Maximum short circuit temperature (5 Seconds) | 160°C | |
| Minimum bending radius | Up to 8mm² | 4 x overall diameter |
| 8mm² to 12mm² | 5 x overall diameter | |
| Above 12mm² | 6 x overall diameter | |
| Conductor | FLP300-V2-U/R/K | |||
|---|---|---|---|---|
| No. of Cores x Cross Section | Class of Conductor | Nominal Insulation Thickness | Maximum Overall Diameter | Approx. Weight |
| No.xmm² | mm | mm | kg/km | |
| 1x0.50 | 1 | 0.6 | 2.3 | 8 |
| 1x0.75 | 1 | 0.6 | 2.5 | 11 |
| 1x1.0 | 1 | 0.6 | 2.7 | 14 |
| 1x0.50 | 2 | 0.6 | 2.4 | 9 |
| 1x0.75 | 2 | 0.6 | 2.6 | 12 |
| 1x1.0 | 2 | 0.6 | 2.8 | 14 |
| 1x0.50 | 5 | 0.6 | 2.5 | 8 |
| 1x0.75 | 5 | 0.6 | 2.7 | 11 |
| 1x1.0 | 5 | 0.6 | 2.8 | 13 |
| Conductor cross-sectional area | PVC insulated types (HD 21) | |
|---|---|---|
| single-phase a.c. | three-phase a.c. | |
| mm² | A | A |
| 0.50 | 3 | 3 |
| 0.75 | 6 | 6 |
| 1.0 | 10 | 10 |
Note: These values apply to the majority of cases. Further information should be sought in unusual cases eg.: (i) When high ambient temperatures are involved, ie. above 30°C (ii) Where long lengths are used (iii) Where ventilation is restricted (iv) Where the cords are used for other purposes, ego internal wiring of apparatus. | ||
| Nominal Cross Section Area | 2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||
|---|---|---|---|---|---|---|---|---|
| Ref. Methods A and B (enclosed in conduit or trunking) | Ref. Methods C, F & G (clipped direct, on trays or in free air) | Ref. Methods A & B (enclosed in conduit or trunking | Ref. Methods C, F & G (clipped direct, on trays or in free air) | |||||
| Cables touching | Cables spaced* | Cables touching, Trefoil | Cables touching, Flat | Cables spaced*, Flat | ||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
| mm² | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m |
| 0.50 | 93 | 93 | 93 | 93 | 80 | 80 | 80 | 80 |
| 0.75 | 62 | 62 | 62 | 62 | 54 | 54 | 54 | 54 |
| 1.0 | 46 | 46 | 46 | 46 | 40 | 40 | 40 | 40 |