600/1000V multi-core mica tape and XLPE insulated
LSZH sheathed armoured fire resistant cable
is designed for critical low voltage circuits.
It is suitable for emergency power systems,
fire safety systems, public buildings,
transport systems and industrial projects.
The mica tape layer helps maintain
circuit integrity during fire conditions.
The XLPE insulation provides reliable
electrical performance and thermal stability.
The LSZH sheath helps reduce smoke emission
and corrosive gas release in the event of fire.
The armoured construction provides improved
mechanical protection.
It is suitable for cable trays, cable ducts,
underground cable routes, tunnels
and protected outdoor installation.
Typical applications include emergency lighting,
fire alarm systems, smoke control systems,
sprinkler pumps and essential power circuits.
The cable should be selected according to
voltage rating, number of cores,
conductor size, armour type,
fire performance requirement
and project specification.
Basic design adapted from IEC 60502-1
| Circuit Integrity | IEC 60331-21; EN 6387; BS 8491 |
| Flame Retardance (single vertical wire or cable test) | IEC 60332-1-2; EN 60332-1-2 |
| Reduced fire Propagation (Vertically-mounted bundled wires & cables test) | IEC 60332-3-24; EN 60332-3-24 |
| Halogen Free | IEC 60754-1; EN 50267-2-1 |
| No Corrosive Gas emission | IEC 60754-2; EN 50267-2-2 |
| Minimum smoke emission | IEC 61034-2; EN 61034-2 |
600/1000V
Conductor : The conductors shall be class 2 plain or metal-coated annealed copper in accordance with IEC 60228. Class 1 and class 5 conductor can be offered as option.
Fire Barrier : Mica glass tape.
Insulation : Thermosetting XLPE material as per IEC 60502-1.
Inner Covering : Thermoplastic halogen free compound ST8 as per IEC 60502-1.
Armouring : Steel wire armour.
Outer Sheath : Thermoplastic halogen free compound ST8 as per IEC 60502-1.
Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.
2-core : Brown and blue.
3-core : Brown, black and grey.
4-core : Blue, brown, black and grey.
5-core : Green-and-yellow, blue, brown, black, grey.
Other colours can be offered upon request.
Maximum temperature range during operation : 90°C
Maximum short circuit temperature (5 Seconds) : 250°C
Minimum bending radius
circular copper conductors : 6 × Overall Diameter
shaped copper conductors : 8 × Overall Diameter
| Conductor | FRP600-mRZ1MZ1-R | |||||||
|---|---|---|---|---|---|---|---|---|
| No. of Cores × Cross-sectional Area | Conductor Class | Nominal Insulation Thickness | Nominal Inner Covering Thickness | Nominal Armour Wire Diameter | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight | |
| No.×mm² | mm | mm | mm | mm | mm | kg/km | ||
| 2 cores | ||||||||
| 2×1.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 15.2 | 393 | |
| 2×2.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 16 | 440 | |
| 2×4 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 17.1 | 507 | |
| 2×6 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 19.1 | 732 | |
| 2×10 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 21.0 | 894 | |
| 2×16 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 23.1 | 1103 | |
| 2×25 | 2 | 0.9 | 1.0 | 1.6 | 1.8 | 27.2 | 1622 | |
| 2×35 | 2 | 0.9 | 1.0 | 1.6 | 1.8 | 29.5 | 1936 | |
| 2×50 | 2 | 1.0 | 1.0 | 1.6 | 1.9 | 32.8 | 2368 | |
| 2×70 | 2 | 1.1 | 1.0 | 2.0 | 2.0 | 37.8 | 3311 | |
| 2×95 | 2 | 1.1 | 1.2 | 2.0 | 2.1 | 42.2 | 4157 | |
| 2×120 | 2 | 1.2 | 1.2 | 2.0 | 2.3 | 46.2 | 4950 | |
| 2×150 | 2 | 1.4 | 1.2 | 2.5 | 2.4 | 51.3 | 6286 | |
| 2×185 | 2 | 1.6 | 1.4 | 2.5 | 2.6 | 56.7 | 7551 | |
| 2×240 | 2 | 1.7 | 1.4 | 2.5 | 2.7 | 62.5 | 9218 | |
| 2×300 | 2 | 1.8 | 1.6 | 2.5 | 2.9 | 68.6 | 11064 | |
| 2×400 | 2 | 2.0 | 1.6 | 2.5 | 3.1 | 75.7 | 13459 | |
| 3 cores | ||||||||
| 3×1.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 15.8 | 436 | |
| 3×2.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 16.7 | 495 | |
| 3×4 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 17.9 | 581 | |
| 3×6 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 20.0 | 838 | |
| 3×10 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 22.0 | 1050 | |
| 3×16 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 24.3 | 1328 | |
| 3×25 | 2 | 0.9 | 1.0 | 1.6 | 1.8 | 28.7 | 1973 | |
| 3×35 | 2 | 0.9 | 1.0 | 1.6 | 1.8 | 31.2 | 2398 | |
| 3×50 | 2 | 1.0 | 1.0 | 1.6 | 1.9 | 34.7 | 2976 | |
| 3×70 | 2 | 1.1 | 1.0 | 2.0 | 2.1 | 40.2 | 4200 | |
| 3×95 | 2 | 1.1 | 1.2 | 2.0 | 2.2 | 44.9 | 5346 | |
| 3×120 | 2 | 1.2 | 1.2 | 2.0 | 2.3 | 49.0 | 6402 | |
| 3×150 | 2 | 1.4 | 1.4 | 2.5 | 2.5 | 55.0 | 8187 | |
| 3×185 | 2 | 1.6 | 1.4 | 2.5 | 2.7 | 60.3 | 9822 | |
| 3×240 | 2 | 1.7 | 1.4 | 2.5 | 2.8 | 66.5 | 12141 | |
| 3×300 | 2 | 1.8 | 1.6 | 2.5 | 3.0 | 73.0 | 14682 | |
| 3×400 | 2 | 2.0 | 1.6 | 3.15 | 3.3 | 82.2 | 19088 | |
| 3 cores + 1 core earth conductor | ||||||||
| 3 cores | 1 core | |||||||
| 3×16/10 | 2 | 0.7 | 0.7 | 1.0 | 1.6 | 1.8 | 25.6 | 1442 |
| 3×25/16 | 2 | 0.9 | 0.7 | 1.0 | 1.6 | 1.8 | 29.5 | 2148 |
| 3×35/16 | 2 | 0.9 | 0.7 | 1.0 | 1.6 | 1.9 | 32.3 | 2573 |
| 3×50/25 | 2 | 1.0 | 0.9 | 1.0 | 1.6 | 2.1 | 36.1 | 3254 |
| 3×70/35 | 2 | 1.1 | 0.9 | 1.2 | 2 | 2.2 | 42.0 | 4578 |
| 3×95/50 | 2 | 1.1 | 1.0 | 1.2 | 2 | 2.3 | 46.6 | 5857 |
| 3×120/70 | 2 | 1.2 | 1.1 | 1.2 | 2 | 2.5 | 51.0 | 7135 |
| 3×150/70 | 2 | 1.4 | 1.1 | 1.4 | 2.5 | 2.7 | 57.2 | 8920 |
| 3×185/95 | 2 | 1.6 | 1.1 | 1.4 | 2.5 | 2.8 | 62.5 | 10826 |
| 3×240/120 | 2 | 1.7 | 1.2 | 1.6 | 2.5 | 3.1 | 69.9 | 13407 |
| 3×300/150 | 2 | 1.8 | 1.4 | 1.6 | 2.5 | 3.2 | 76..0 | 16243 |
| 3×400/185 | 2 | 2.0 | 1.6 | 1.6 | 3.15 | 3.6 | 85.7 | 21047 |
| 4 cores | ||||||||
| 4×1.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 16.8 | 491 | |
| 4×2.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 17.8 | 565 | |
| 4×4 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 19.1 | 702 | |
| 4×6 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 21.4 | 968 | |
| 4×10 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 23.7 | 1233 | |
| 4×16 | 2 | 0.7 | 1.0 | 1.6 | 1.8 | 26.9 | 1755 | |
| 4×25 | 2 | 0.9 | 1.0 | 1.6 | 1.8 | 31.0 | 2369 | |
| 4×35 | 2 | 0.9 | 1.0 | 1.6 | 1.9 | 34.0 | 2928 | |
| 4×50 | 2 | 1.0 | 1.0 | 2.0 | 2.1 | 38.9 | 3972 | |
| 4×70 | 2 | 1.1 | 1.2 | 2.0 | 2.2 | 44.3 | 5233 | |
| 4×95 | 2 | 1.1 | 1.2 | 2.0 | 2.3 | 49.1 | 6636 | |
| 4×120 | 2 | 1.2 | 1.4 | 2.5 | 2.5 | 55.3 | 8608 | |
| 4×150 | 2 | 1.4 | 1.4 | 2.5 | 2.7 | 60.4 | 10203 | |
| 4×185 | 2 | 1.6 | 1.4 | 2.5 | 2.8 | 66.1 | 12264 | |
| 4×240 | 2 | 1.7 | 1.6 | 2.5 | 3.1 | 73.9 | 15427 | |
| 4×300 | 2 | 1.8 | 1.6 | 2.5 | 3.2 | 80.4 | 18565 | |
| 4×400 | 2 | 2.0 | 1.8 | 3.15 | 3.6 | 91.1 | 24233 | |
| 5 cores | ||||||||
| 5x1.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 17.9 | 578 | |
| 5×2.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 19.0 | 668 | |
| 5×4 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 20.5 | 799 | |
| 5×6 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 22.9 | 1140 | |
| 5×10 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 25.4 | 1465 | |
| 5×16 | 2 | 0.7 | 1.0 | 1.6 | 1.8 | 29.0 | 2083 | |
| 5×25 | 2 | 0.9 | 1.0 | 1.6 | 1.9 | 33.8 | 2853 | |
| 5×35 | 2 | 0.9 | 1.0 | 1.6 | 2.0 | 37.1 | 3544 | |
Conductor operating temperature : 90°C
Air ambient temperature : 30°C
Ground ambient temperature : 20°C
| Conductor cross-sectional area | Ref. Method C (clipped direct) | Ref. Method E (in free air or on a perforated cable tray etc. horizontal or vertical) | Ref. Method D (direct in in groud or in ducting in groud. in or around buildings) | |||
|---|---|---|---|---|---|---|
| 1 two-core cable, single-phase a.c. or d.c. | 1 three- or four-core cable, three-phase a.c. | 1 two-core cable, single-phase a.c. or d.c. | 1 three- or four-core cable, three-phase a.c. | 1 two-core cable, single-phase a.c. or d.c. | 1 three- or four-core cable, three-phase a.c. | |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 |
| mm² | A | A | A | A | A | A |
| 1.5 | 27 | 23 | 29 | 25 | 25 | 21 |
| 2.5 | 36 | 31 | 39 | 33 | 33 | 28 |
| 4 | 49 | 42 | 52 | 44 | 43 | 36 |
| 6 | 62 | 53 | 66 | 56 | 53 | 44 |
| 10 | 85 | 73 | 90 | 78 | 71 | 58 |
| 16 | 110 | 94 | 115 | 99 | 91 | 75 |
| 25 | 146 | 124 | 152 | 131 | 116 | 96 |
| 35 | 180 | 154 | 188 | 162 | 139 | 115 |
| 50 | 219 | 187 | 228 | 197 | 164 | 135 |
| 70 | 279 | 238 | 291 | 251 | 203 | 167 |
| 95 | 338 | 289 | 354 | 304 | 239 | 197 |
| 120 | 392 | 335 | 410 | 353 | 271 | 223 |
| 150 | 451 | 386 | 472 | 406 | 306 | 251 |
| 185 | 515 | 441 | 539 | 463 | 343 | 281 |
| 240 | 607 | 520 | 636 | 546 | 395 | 324 |
| 300 | 698 | 599 | 732 | 628 | 446 | 365 |
| 400 | 787 | 673 | 847 | 728 | - | - |
| Conductor cross-sectional area | Two-core cables, d.c. | Two-core cable, single-phase a.c. | Three- or four-core cable, three-phase a.c. | ||||
|---|---|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | ||||
| mm² | mV/A/m | mV/A/m | mV/A/m | ||||
| 1.5 | 31 | 31 | 27 | ||||
| 2.5 | 19 | 19 | 16 | ||||
| 4 | 12 | 12 | 10 | ||||
| 6 | 7.9 | 7.9 | 6.8 | ||||
| 10 | 4.7 | 4.7 | 4.0 | ||||
| 16 | 2.9 | 2.9 | 2.5 | ||||
| r | x | z | r | x | z | ||
| 25 | 1.85 | 1.85 | 0.160 | 1.90 | 1.60 | 0.140 | 1.65 |
| 35 | 1.35 | 1.35 | 0.155 | 1.35 | 1.15 | 0.135 | 1.15 |
| 50 | 0.98 | 0.99 | 0.155 | 1.00 | 0.86 | 0.135 | 0.87 |
| 70 | 0.67 | 0.67 | 0.150 | 0.69 | 0.59 | 0.130 | 0.60 |
| 95 | 0.49 | 0.50 | 0.150 | 0.52 | 0.43 | 0.130 | 0.45 |
| 120 | 0.39 | 0.40 | 0.145 | 0.42 | 0.34 | 0.130 | 0.37 |
| 150 | 0.31 | 0.32 | 0.145 | 0.35 | 0.38 | 0.125 | 0.30 |
| 185 | 0.25 | 0.26 | 0.145 | 0.29 | 0.22 | 0.125 | 0.26 |
| 240 | 0.195 | 0.200 | 0.140 | 0.24 | 0.175 | 0.125 | 0.21 |
| 300 | 0.155 | 0.160 | 0.140 | 0.21 | 0.140 | 0.120 | 0.185 |
| 400 | 0.120 | 0.130 | 0.140 | 0.190 | 0.115 | 0.120 | 0.165 |
r = conductor resistance at operating temperature
x = reactance
z = impedance
KEY FEATURES
- Manufactured according to IEC 60502-1 requirements
- Fire resistant cable construction
- Mica tape fire barrier
- XLPE insulated conductors
- LSZH / LSOH outer sheath
- Armoured cable design
- Multi-core power cable construction
- Suitable for emergency power circuits
- Suitable for public buildings and transport systems
- Designed to support circuit integrity during fire
SELECTION NOTES
Before quotation, please confirm:
- Voltage rating
- Number of cores
- Conductor size
- Conductor material
- Armour type
- Cable length
- Sheath colour
- Fire resistance requirement
- Circuit integrity requirement
- Installation method
- Installation environment
- Required standard or project specification
- Packing requirement
- Destination port or delivery address
600/1000V mica XLPE LSZH armoured cable
is commonly selected for projects requiring
fire resistance, LSZH performance
and mechanical protection.
It is suitable for emergency circuits,
public buildings, tunnels, transport systems
and critical infrastructure projects.
RELATED CABLE TYPES
- BS 6387 fire resistant cable
- IEC 60331 fire resistant cable
- IEC 60502 low voltage cable
- Mica tape fire resistant cable
- XLPE LSZH armoured cable
- XLPE LSZH unarmoured cable
- BS6724 LSZH armoured cable
- BS5467 armoured power cable
- Emergency power cable
- Low voltage power cable
FAQ
What is this cable used for?
It is used for critical low voltage
power circuits.
It is suitable for emergency lighting,
fire alarm systems, smoke control systems
and essential power supply routes.
What standard does this cable follow?
The cable is designed according to
IEC 60502-1 requirements.
Fire performance can be tested according to
IEC 60331, BS 6387 or project requirements.
What does the mica tape layer do?
The mica tape layer helps maintain
circuit integrity during fire conditions.
It supports continued operation
of essential circuits during emergencies.
Is this cable armoured?
Yes. This is an armoured cable.
The armour provides improved
mechanical protection.
What does LSZH mean?
LSZH means Low Smoke Zero Halogen.
The sheath helps reduce smoke emission
and corrosive gas release during fire.
Can this cable be used underground?
Yes. It can be used for underground
cable routes and cable trenches.
The final installation should follow
project specifications and local
installation requirements.
What information is required for quotation?
Please confirm voltage rating,
number of cores, conductor size,
armour type and cable length.
Fire resistance requirement,
circuit integrity requirement
and destination port are also required.
Can BURYCABLE supply fire resistant
mica XLPE LSZH armoured cable?
Yes. BURYCABLE can supply 600/1000V
mica tape XLPE insulated LSZH sheathed
armoured fire resistant cables.
We can support different core numbers,
conductor sizes, armour types,
fire performance requirements and packing.