300/500V PVC insulated and PVC sheathed multi-core cable is used for fixed wiring installations.
It is suitable for building wiring, lighting circuits, power circuits and general low voltage electrical installations.
The cable can be used in domestic, commercial and industrial buildings.
It is designed for protected installations where PVC insulation and PVC outer sheath are required.
Typical applications include conduit, trunking, cable trays, panels and protected wiring systems.
The cable should be selected according to voltage rating, number of cores, conductor size, installation method and project specification.
Basic design to BS EN 50525-2-11(formerly BS 6500)
| Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2 |
300/500V
| Conductor | Flexible copper wire according to EN 60228 class 5. |
| Insulation | PVC Type TI 2 according to EN 50363-3. |
| Filling | For circular cable having two cores, the space between the cores shall be filled either by separate fillers or by the sheath filling the interstices. For circular cables with three, four or five cores, a centre filler may be used. |
| Outer Sheath | PVC Type TM 2 according to EN 50363-4-1. A tape may be applied around the core assembly before application of the sheath. |
| Outer Sheath Option | UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request. |
Insulation Colour :
| No. of cores | Colour of coresb | ||||
| Protective | Live | ||||
| 3 Cores | Yellow/Green | Blue | Brown | ||
| 4 Cores | Yellow/Green | - | Brown | Black | Grey |
| 4 Coresa | Yellow/Green | Blue | Brown | Black | |
| 5 Cores | Yellow/Green | Blue | Brown | Black | Grey |
a : For certain applications only. b : In this table an uninsulated concentric conductor, such as a metallic sheath, armour or screen wire, is not regarded as a core. A concentric conductor is identified by its position and, therefore, need not be identified by colour. | |||||
| No. of cores | Colour of coresb | ||||
| 2 Cores | Blue | Brown | |||
| 3 Cores | - | Brown | Black | Grey | |
| 3 Coresa | Blue | Brown | Black | ||
| 4 Cores | Blue | Brown | Black | Grey | |
| 5 Cores | Blue | Brown | Black | Grey | Black |
a : For certain applications only. b : In this table an uninsulated concentric conductor, such as a metallic sheath, armour or screen wire, is not regarded as a core. A concentric conductor is identified by its position and, therefore, need not be identified by colour. | |||||
Sheath Colour : Black, other colours can be offered upon request.
| Maximum temperature range during operation (PVC) | 70°C |
| Maximum short circuit temperature (5 Seconds) | 160°C |
| Minimum bending radius | Up to 12mm² : 3 x overall diameter |
| Above 12mm² : 4 x overall diameter |
| Conductor | FLP300 VV-F | ||||
|---|---|---|---|---|---|
| No. of Cores x Cross Section | Class of Conductor | Nominal Insulation Thickness | Nominal Sheath Thickness | Maximum Overall Diameter | Approx. Weight |
| No.xmm² | mm | mm | mm | kg/km | |
| 2x0.75 | 5 | 0.6 | 0.8 | 7.2 | 57 |
| 2x1.0 | 5 | 0.6 | 0.8 | 7.5 | 65 |
| 2x1.5 | 5 | 0.7 | 0.8 | 8.6 | 87 |
| 2x2.5 | 5 | 0.8 | 1.0 | 10.6 | 134 |
| 2x4.0 | 5 | 0.8 | 1.1 | 12.1 | 174 |
| 3x0.75 | 5 | 0.6 | 0.8 | 7.6 | 68 |
| 3x1.0 | 5 | 0.6 | 0.8 | 8.0 | 79 |
| 3x1.5 | 5 | 0.7 | 0.9 | 9.4 | 111 |
| 3x2.5 | 5 | 0.8 | 1.1 | 11.4 | 169 |
| 3x4.0 | 5 | 0.8 | 1.2 | 13.1 | 233 |
| 4x0.75 | 5 | 0.6 | 0.8 | 8.3 | 84 |
| 4x1.0 | 5 | 0.6 | 0.9 | 9.0 | 101 |
| 4x1.5 | 5 | 0.7 | 1.0 | 10.5 | 142 |
| 4x2.5 | 5 | 0.8 | 1.1 | 12.5 | 211 |
| 4x4.0 | 5 | 0.8 | 1.2 | 14.3 | 292 |
| 5x0.75 | 5 | 0.6 | 0.9 | 9.3 | 106 |
| 5x1.0 | 5 | 0.6 | 0.9 | 9.8 | 123 |
| 5x1.5 | 5 | 0.7 | 1.1 | 11.6 | 176 |
| 5x2.5 | 5 | 0.8 | 1.2 | 13.9 | 262 |
| 5x4.0 | 5 | 0.8 | 1.4 | 16.1 | 369 |
| Conductor cross-sectional area | Single-phase a.c. | Three-phase a.c. |
|---|---|---|
| mm² | A | A |
| 0.75 | 6 | 6 |
| 1.0 | 10 | 10 |
| 1.5 | 16 | 16 |
| 2.5 | 25 | 20 |
| 4.0 | 32 | 25 |
| Conductor cross-sectional area | d.c. or single-phase a.c. | Three-phase a.c. |
|---|---|---|
| mm² | mV/A/m | mV/A/m |
| 0.75 | 62 | 54 |
| 1.0 | 46 | 40 |
| 1.5 | 32 | 27 |
| 2.5 | 19 | 16 |
| 4.0 | 12 | 10 |
KEY FEATURES
- Manufactured according to BS EN 50525-2-11 requirements
- 300/500V voltage rating
- PVC insulated conductors
- PVC outer sheath
- Multi-core cable construction
- Suitable for fixed wiring installation
- Suitable for lighting and power circuits
- Suitable for conduit, trunking and protected wiring systems
- Copper conductor construction
- Commonly used in building electrical installations
SELECTION NOTES
Before quotation, please confirm:
- Voltage rating
- Number of cores
- Conductor size
- Conductor material
- Cable length
- Sheath colour
- Installation environment
- Required standard or project specification
- Packing requirement
- Destination port or delivery address
300/500V PVC insulated and PVC sheathed multi-core cable is commonly selected for fixed wiring and general building electrical installations.
It is suitable where PVC sheathed cable construction and protected installation are required.
RELATED CABLE TYPES
- 300/500V PVC insulated PVC sheathed single core cable
- 300/500V PVC insulated non-sheathed cable
- 6181Y cable
- 6181X cable
- 6192Y cable
- 6193Y cable
- 6242Y cable
- BS6004 PVC cable
- BS7211 LSZH cable
FAQ
What is this 300/500V PVC sheathed cable used for?
This cable is used for fixed wiring installations.
It is suitable for building wiring, lighting circuits, power circuits and protected low voltage electrical systems.
Is this cable sheathed?
Yes. This cable has PVC insulation and a PVC outer sheath.
What standard does this cable follow?
This cable is designed according to BS EN 50525-2-11 requirements.
Can this cable be used in conduit or trunking?
Yes. It can be used in conduit, trunking, panels and protected wiring systems.
Can BURYCABLE supply 300/500V PVC sheathed multi-core cable?
Yes. BURYCABLE can supply 300/500V PVC insulated and PVC sheathed multi-core cables according to project size, core number, colour, length and packing requirements.