whatsapp
backtop
Profibus PA Cable, 100 Ohm, AWG 18 Solid Copper, Screened PVC
Profibus PA process-automation cable with solid AWG 18 copper conductors, PE insulation and a PVC sheath. Foil and tinned copper braid screens enclose the pair. Impedance: 100 ohms at 31.25 kHz; working voltage: 300V.
Profibus PA.pdf Contact us

APPLICATION

For Profibus PA connections in process-automation systems, this cable uses a screened pair of solid bare copper conductors with PE insulation. A PVC outer sheath is offered in blue or black. Its electrical data are specified for the PA cable construction, including 100 ± 20 ohms impedance at 31.25 kHz.

CONSTRUCTION

Type/Area of ApplicationHazardous Areas /Non-Hazardous Areas
Cable Construction1x2x1.0/2.55 mm
Inner Conductor DiameterCopper, bare (AWG 18/1)
Conductor InsulationPE
Conductor Colorsred, green
Stranding Element2 conductors + 2 fillers stranded together
ShieldingPolyester foil, aluminum-lined
Total ShieldingCopper braid, tinned
Outer Jacket MaterialPVC
Outer Diameter7.6 mm ± 0.2 mm
Outer Jacket ColorBlue/Black

ELECTRICAL DATA

Characteristic Impedance @ 31.25 KHz100 Ω ± 20 Ω
Conductor Resistance22.0 Ohm/km max.
Insulation Resistance1.00 GOhm x km min.
Mutual Capacitance@1KHz55.0 nF/km nom.
Working Voltage300 V
Test Voltage2.5 kV
Attenuation39kHz≤3dB/km

TECHNICAL DATA

Weightapproximately 76.0 kg/km
Min. Bending Radius (Laying)18 x OD mm
Operating Temp.Range, min.- 20 °C
Operating Temp.Range, max.+70 °C


KEY FEATURES

  • AWG 18/1 solid bare copper conductors with red and green PE insulation.

  • Aluminium-lined foil and overall tinned copper braid screening.

  • 300V working voltage and 7.6 ± 0.2 mm outer diameter.

SELECTION NOTES

Choose the sheath colour and termination arrangement to match the project. Include cable length, device loading and power-supply arrangement in the PA segment design. For hazardous-area circuits, select the cable as part of the complete protection concept and the equipment installation requirements.

RELATED CABLE TYPES

FREQUENTLY ASKED QUESTIONS

What impedance is specified for this PA cable?

The characteristic impedance is 100 ± 20 ohms at 31.25 kHz.

What conductor construction is used?

The cable uses bare copper AWG 18/1 solid conductors.

Which insulation and sheath materials are used?

PE insulation surrounds the conductors, with PVC as the outer sheath material.

What screening layers are included?

Aluminium-lined polyester foil and an overall tinned copper braid surround the pair.

What are the diameter and minimum laying radius?

The outer diameter is 7.6 ± 0.2 mm. The listed minimum laying radius is 18 times the overall diameter.