The Profibus SK range is intended for fixed fieldbus connections using compatible quick-connection plugs and cable preparation tools. PVC and PE sheath options cover indoor and outdoor routes. Solid copper conductors, foam-skin PE insulation, foil screening and a tinned copper braid form the signal cable construction.
| Type/Area of Application | Fixed Installation, Indoor /Outdoor |
| Cable Construction | 1x2x0.64 mm |
| Inner Conductor Diameter | Copper, bare (AWG 22/1) |
| Conductor Insulation | Foam-skin-PE |
| Conductor Colors | red, green |
| Stranding Element | 2 conductors + filler |
| Wrapping | Polyester foil over stranded bundle |
| Shielding | Polyester foil, aluminum-lined |
| Total Shielding | Copper braid, tinned |
| Outer Jacket Material | PVC/PE |
| Outer Diameter | 8.0 mm ± 0.4 mm |
| Outer Jacket Color | Violet /Black |
| CharacteristicImpedance@3-20MHz | 150 Ω ± 10 Ω | ||||
| Conductor Resistance | 57.1 Ohm/km max. | ||||
| Insulation Resistance | 1.00 GOhm x km min. | ||||
| Mutual Capacitance@1KHz | 35.0 nF/km nom. | ||||
| Working Voltage | 300V | ||||
| Test Voltage | 1.5 KV | ||||
| Attenuation | 9.6 | kHz | < | 2.5 | dB/km |
| 38.4 | kHz | < | 4.0 | dB/km | |
| 4.0 | MHz | < | 22.0 | dB/km | |
| 16.0 | MHz | < | 42.0 | dB/km | |
| Weight: | approximately 75.0 kg/km | approximately 65.0 kg/km |
| Min. Bending Radius (Laying) | 15 x OD mm | 15 x OD mm |
| Operating Temp.Range, min. | - 40 °C | - 40 °C |
| Operating Temp.Range, max. | +70 °C | +70 °C |
AWG 22/1 solid copper pair with red and green insulation.
PVC and PE sheath options for fixed indoor and outdoor installation.
150 ± 10 ohms impedance at 3–20 MHz and 300V working voltage.
Specify the sheath version and match the plug and stripping tool to the SK cable construction. Allow for an 8.0 ± 0.4 mm outer diameter and a laying radius of 15 times the overall diameter. Use the selected version’s data when planning cable weight and supports.
Profibus L2 Indoor Cable, 150 Ohm, Foil and Braid Screened, PVC
Profibus L2 Outdoor and Industry Cable, 150 Ohm, PE or PUR Sheath
Profibus SK FRNC and Industry Cable, 150 Ohm, FRNC or PUR Sheath
The construction is intended for quick connection with compatible plugs and cable preparation tools.
PVC and PE sheath versions are listed for fixed indoor and outdoor installation.
Bare copper AWG 22/1 solid conductors with foam-skin PE insulation.
Aluminium-lined polyester foil and a tinned copper braid surround the pair assembly.
The outer diameter is 8.0 ± 0.4 mm and the minimum laying bend radius is 15 times the overall diameter.