RE-2X(St)HSWAH PiMF 300V XLPE LSZH Armoured Instrumentation Cable
RE-2X(St)HSWAH PiMF 300V XLPE insulated multipair instrumentation cable with individual and overall foil screens, steel wire armour and LSZH sheath. For fixed industrial instrument and control connections.
RE-2X(St)HSWAH PIMF.pdf Contact us

APPLICATION

BURY CABLE RE-2X(St)HSWAH PiMF multipair cable connects instruments and control equipment in industrial process facilities. Copper conductors with XLPE insulation, individual and overall aluminium/polyester screens and galvanised steel wire armour between LSZH inner and outer sheaths support fixed signal wiring. The steel wire armour adds mechanical protection on routes exposed to handling or impact risks. Individually screened pairs keep each signal circuit organised within the common cable assembly. The LSZH sheath suits projects specifying low smoke and halogen free materials.

Standards

Basic design to EN 50288-7

Fire Performance

Flame Retardance (Single Vertical Wire Test)EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation(Vertically-mounted bundled wires & cable test)EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen FreeIEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke EmissionIEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gasesNES 02-713; NF C 20-454
Sunlight ResistanceUL 1581 section 1200
Oil ResistanceICEA S-73-532**

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation, *** denotes optional.

Voltage Rating

300

Cable Construction

Conductor : Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

Insulation : Extruded cross-linked XLPE compound, EN 50290. 2-29.

Pairs : Two insulated conductors uniformly twisted together with a lay not exceeding 100mmIndividual.

Screen : Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm².

Binder tape : PETP transparent tape.

Overall Screen : Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm².

Inner Sheath : LSZH(Low Smoke Zero Halogen) sheath.

Amouring : Galvanized steel wire armour.

Outer Sheath : Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.

Colour Code

Insulation : Black / White, continuously numbered on white core (1, 2..) for multipair.

Outer Sheath : Black or blue for intrinsically safe systems.

Physical and Thermal Properties

Temperature Range During Operation (Fixed State) : -30°C – +90°C

Temperature Range During Installation (Mobile State) : -20°C – +50°C

Minimum Bending Radius : 10 × Overall Diameter

Electrical Roperties

Conductor Area Sizemm²0.50.751.01.31.5
Insulation thickness (nominal)mm0.40.40.40.450.45
Conductor resistance (20°C)Ω/km36.72518.514.212.3
Insulation resistance (20°C)MΩ.km(Min.)5000
Mutual Capacitance (1 kHz)pF/m(Max.)115
InductancemH/km (Max.)1
L / R (ratio) (max.)μH/Ω2525254040
Operating voltage UrmsV300
Test VoltageCore to CoreV1500
Core to ScreenV1500

Construction Parameterst

Caledonian Cable CodeRE-2X(St)HSWAH PiMF
No. of Pairs ×2×Cross SectionNominal Insulation ThicknessNominal Inner Sheath ThicknessNominal Overall Diameter Over Inner SheathNominal Armour Wire DiameterNominal Outer Sheath ThicknessNominal Overall DiameterApprox. Weight
 No.×2×mm²mmmmmmmmmmmmkg/km
0.5mm2, Multipair
RE-2X(St)HSWAH PiMF 2P0.52x2x0.50.350.98.70.91.413.3311
RE-2X(St)HSWAH PiMF 4P0.54x2x0.50.351.010.20.91.414.8373
RE-2X(St)HSWAH PiMF 5P0.55x2x0.50.351.011.20.91.415.8451
RE-2X(St)HSWAH PiMF 6P0.56x2x0.50.351.012.10.91.616.9483
RE-2X(St)HSWAH PiMF 8P0.58x2x0.50.351.113.10.91.617.9537
RE-2X(St)HSWAH PiMF 10P0.510x2x0.50.351.215.10.91.519.9781
RE-2X(St)HSWAH PiMF 12P0.512x2x0.50.351.215.70.91.520.5804
RE-2X(St)HSWAH PiMF 16P0.516x2x0.50.351.217.81.251.623.5968
RE-2X(St)HSWAH PiMF 20P0.520x2x0.50.351.319.71.251.725.61143
RE-2X(St)HSWAH PiMF 24P0.524x2x0.50.351.421.51.251.727.41264
0.75mm2, Multipair
RE-2X(St)HSWAH PiMF 2P0.752x2x0.750.381.09.70.91.414.3342
RE-2X(St)HSWAH PiMF 4P0.753x2x0.750.381.011.20.91.415.8439
RE-2X(St)HSWAH PiMF 5P0.754x2x0.750.381.112.50.91.517.3496
RE-2X(St)HSWAH PiMF 6P0.755x2x0.750.381.113.60.91.518.4578
RE-2X(St)HSWAH PiMF 8P0.758x2x0.750.381.114.40.91.519.2664
RE-2X(St)HSWAH PiMF 10P0.7510x2x0.750.381.216.61.251.622.3876
RE-2X(St)HSWAH PiMF 12P0.7512x2x0.750.381.217.41.251.623.1942
RE-2X(St)HSWAH PiMF 16P0.7516x2x0.750.381.319.81.251.725.71130
RE-2X(St)HSWAH PiMF 20P0.7520x2x0.750.381.422.01.251.727.91325
RE-2X(St)HSWAH PiMF 24P0.7524x2x0.750.381.524.01.251.830.11490
1.0mm2, Multipair
RE-2X(St)HSWAH PiMF 2P1.02x2x1.00.41.010.40.91.415.0382
RE-2X(St)HSWAH PiMF 4P1.03x2x1.00.41.012.10.91.416.7487
RE-2X(St)HSWAH PiMF 5P1.04x2x1.00.41.113.50.91.518.3566
RE-2X(St)HSWAH PiMF 6P1.05x2x1.00.41.114.70.91.519.5641
RE-2X(St)HSWAH PiMF 8P1.08x2x1.00.41.215.80.91.520.6718
RE-2X(St)HSWAH PiMF 10P1.010x2x1.00.41.218.01.251.623.7994
RE-2X(St)HSWAH PiMF 12P1.012x2x1.00.41.319.01.251.724.71083
RE-2X(St)HSWAH PiMF 16P1.016x2x1.00.41.321.51.251.727.41361
RE-2X(St)HSWAH PiMF 20P1.020x2x1.00.41.423.91.251.729.81510
RE-2X(St)HSWAH PiMF 24P1.024x2x1.00.41.526.11.251.832.21902
1.3mm2, Multipair
RE-2X(St)HSWAH PiMF 2P1.32x2x1.30.451.011.40.91.416.0452
RE-2X(St)HSWAH PiMF 4P1.33x2x1.30.451.113.40.91.518.2576
RE-2X(St)HSWAH PiMF 5P1.34x2x1.30.451.114.80.91.519.6647
RE-2X(St)HSWAH PiMF 6P1.35x2x1.30.451.216.30.91.621.3857
RE-2X(St)HSWAH PiMF 8P1.38x2x1.30.451.317.61.251.623.3980
RE-2X(St)HSWAH PiMF 10P1.310x2x1.30.451.320.01.251.725.91195
RE-2X(St)HSWAH PiMF 12P1.312x2x1.30.451.421.11.251.727.01256
RE-2X(St)HSWAH PiMF 16P1.316x2x1.30.451.524.11.251.830.21562
RE-2X(St)HSWAH PiMF 20P1.320x2x1.30.451.626.81.251.933.11958
RE-2X(St)HSWAH PiMF 24P1.324x2x1.30.451.729.21.252.036.42251
1.5mm2, Multipair
RE-2X(St)HSWAH PiMF 2P1.52x2x1.50.451.011.80.91.516.6475
RE-2X(St)HSWAH PiMF 4P1.53x2x1.50.451.113.90.91.518.7599
RE-2X(St)HSWAH PiMF 5P1.54x2x1.50.451.215.50.91.520.3818
RE-2X(St)HSWAH PiMF 6P1.55x2x1.50.451.216.91.251.622.6940
RE-2X(St)HSWAH PiMF 8P1.58x2x1.50.451.318.21.251.724.11037
RE-2X(St)HSWAH PiMF 10P1.510x2x1.50.451.421.01.251.726.91273
RE-2X(St)HSWAH PiMF 12P1.512x2x1.50.451.421.91.251.727.81353
RE-2X(St)HSWAH PiMF 16P1.516x2x1.50.451.525.11.251.831.21932
RE-2X(St)HSWAH PiMF 20P1.520x2x1.50.451.627.81.251.934.82224
RE-2X(St)HSWAH PiMF 24P1.524x2x1.50.451.730.41.252.037.62541



KEY FEATURES

  • XLPE insulation with individually screened twisted pairs and an overall foil screen.

  • LSZH inner sheath, galvanised steel wire armour and LSZH outer sheath.

  • Electrical and construction tables cover 0.5-1.5 mm² conductor sections, with original dimensions and weights retained.

SELECTION NOTES

  • Specify pair count, conductor size and construction, circuit voltage, cable length and termination arrangement.

  • Coordinate screen bonding and armour termination with the installation design. Use a minimum bending radius of 10 times overall diameter.

  • Choose black or blue sheath identification for the specified system. Blue identification is coordinated with the complete intrinsically safe circuit design; environmental sheath options form part of the order specification.

RELATED CABLE TYPES

FAQ

What is RE-2X(St)HSWAH PiMF cable used for?

It connects instruments and control equipment on fixed industrial signal routes using a multipair copper cable with XLPE insulation and an LSZH sheath.

How are the conductors arranged?

Two insulated conductors form each twisted pair, with numbered white cores supporting pair identification.

Which screening construction is used?

PiMF construction uses individual pair screens together with an overall aluminium/polyester screen and tinned copper drain wires.

What does the steel wire armour provide?

Galvanised steel wire adds mechanical protection around the screened assembly, with LSZH inner and outer sheath layers.

How is the cable selected for installation?

Match the pair count, conductor cross-section, circuit voltage and route conditions. Include cable length, screen termination, sheath colour and packing in the order.