The basic design of the product refers to the BS EN 50525 - 3 - 31 standard, ensuring the standardization and high quality of the product in design and manufacturing. This cable is mainly used in scenarios such as power stations, underground passenger transport systems of urban rail transit, airports, petrochemical plants, hotels, hospitals, and high - rise buildings. In these places, the cable can transmit power stably and reliably, meeting the power consumption needs of different environments and equipment.
Basic design adapted from BS EN 50525-3-31
| Circuit Integrity | IEC 60331-21; BS 6387; BS 8491 |
| Flame Retardance (single vertical wire or cable test) | IEC 60332-1-2; EN 60332-1-2 |
| Reduced Fire Propagation (Vertically-mounted bundled wires & cables test) | IEC 60332-3-24; EN 60332-3-24 |
| Halogen free | IEC 60754-1; EN 50267-2-1 |
| No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2 |
| Minimum Smoke Emission | IEC 61034-2; EN 61034-2 |
450/750V
Conductor : Copper conductor according to BS EN 60228 class 1/2/5.
FRP450-mZ1-U : 1.5-10mm2 Class 1 solid copper conductor to BS EN 60228.
FRP450-mZ1-R : 1.5-630mm2 Class 2 stranded copper conductor to BS EN 60228.
FRP450-mZ1-K : 1.5-240mm2 Class 5 stranded copper conductor to BS EN 60228.
Fire Barrier : Mica glass tape.
Insulation : Thermoplastic compound of type TI 7 to EN 50363-7.
Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.
Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow.
Maximum temperature range during operation : 70°C
Maximum short circuit temperature (5 Seconds) : 160°C
OD<8mm : 4 × Overall Diameter;
8mm≤OD≤12mm: 5 × Overall Diameter;
OD>12mm : 6 × Overall Diameter
| Conductor | FRP450-mZ1-U/R/K | ||||
|---|---|---|---|---|---|
| No. of Cores × Cross-sectional Area | Conductor Class | Nominal Insulation Thickness | Min. Overall Diameter | Max. Overall Diameter | Approx. Weight |
| No.×mm² | mm | mm | mm | kg/km | |
| 1×1.5 | 1 | 0.7 | 3.6 | 4.2 | 26 |
| 1×2.5 | 1 | 0.8 | 4.2 | 4.9 | 40 |
| 1×4 | 1 | 0.8 | 4.6 | 5.4 | 57 |
| 1×6 | 1 | 0.8 | 5.1 | 6.0 | 78 |
| 1×10 | 1 | 1.0 | 6.3 | 7.4 | 128 |
| 1×1.5 | 2 | 0.7 | 3.7 | 4.3 | 28 |
| 1×2.5 | 2 | 0.8 | 4.3 | 5.0 | 42 |
| 1×4 | 2 | 0.8 | 4.8 | 5.6 | 59 |
| 1×6 | 2 | 0.8 | 5.3 | 6.2 | 81 |
| 1×10 | 2 | 1.0 | 6.6 | 7.7 | 133 |
| 1×16 | 2 | 1.0 | 7.4 | 8.8 | 197 |
| 1×25 | 2 | 1.2 | 9.1 | 10.7 | 308 |
| 1×35 | 2 | 1.2 | 10.0 | 11.9 | 412 |
| 1×50 | 2 | 1.4 | 11.6 | 13.8 | 558 |
| 1×70 | 2 | 1.4 | 13.1 | 15.6 | 782 |
| 1×95 | 2 | 1.6 | 15.1 | 18.1 | 1078 |
| 1×120 | 2 | 1.6 | 16.6 | 19.8 | 1342 |
| 1×150 | 2 | 1.8 | 18.3 | 21.9 | 1650 |
| 1×185 | 2 | 2.0 | 20.3 | 24.3 | 2067 |
| 1×240 | 2 | 2.2 | 23 | 27.6 | 2703 |
| 1×300 | 2 | 2.4 | 25.5 | 30.6 | 3378 |
| 1×400 | 2 | 2.6 | 28.5 | 34.2 | 4267 |
| 1×500 | 2 | 2.8 | 31.5 | 37.9 | 5359 |
| 1×630 | 2 | 2.8 | 35 | 42.1 | 6884 |
| 1×1.5 | 5 | 0.7 | 3.8 | 4.4 | 27 |
| 1×2.5 | 5 | 0.8 | 4.4 | 5.1 | 42 |
| 1×4 | 5 | 0.8 | 4.9 | 5.8 | 59 |
| 1×6 | 5 | 0.8 | 5.4 | 6.3 | 81 |
| 1×10 | 5 | 1.0 | 6.7 | 7.8 | 134 |
| 1×16 | 5 | 1.0 | 7.7 | 9.1 | 197 |
| 1×25 | 5 | 1.2 | 9.4 | 11.2 | 304 |
| 1×35 | 5 | 1.2 | 10.7 | 12.7 | 410 |
| 1×50 | 5 | 1.4 | 12.5 | 14.9 | 585 |
| 1×70 | 5 | 1.4 | 14.2 | 17.0 | 811 |
| 1×95 | 5 | 1.6 | 16.1 | 19.2 | 1075 |
| 1×120 | 5 | 1.6 | 17.7 | 21.2 | 1341 |
| 1×150 | 5 | 1.8 | 19.6 | 23.5 | 1670 |
| 1×185 | 5 | 2.0 | 21.6 | 25.9 | 2042 |
| 1×240 | 5 | 2.2 | 24.5 | 29.4 | 2672 |
Conductor operating temperature : 70°C
Ambient temperatur : 30°C
| Conductor cross-sectional area | Ref. Method A (enclosed in conduit in thermally insulating wall etc.) | Ref. Method B (enclosed in conduit on a wall or in trunking etc.) | Ref. Method C (clipped direct) | Ref. Method F (in free air or on a perforated cable tray horizontal or vertical) | |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Touching | Spaced by one diameter | ||||||||||
| 2 cables, single-phase a.c. or d.c. | 3 or 4 cables, three-phase a.c. | 2 cables, single-phase a.c. or d.c | 3 or 4 cables, three-phase a.c. | 2 cables, single-phase a.c. or d.c. flat and touching | 3 or 4 cables, three-phase a.c. flat and touching or trefoil | 2 cables, single-phase a.c. or d.c. flat | 3 cables, three-phase a.c. flat | 3 cables, three-phase a.c. trefoil | 2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat | ||
| Horizontal | Vertical | ||||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
| mm² | A | A | A | A | A | A | A | A | A | A | A |
| 1.5 | 14.5 | 13.5 | 17.5 | 15.5 | 20 | 18 | - | - | - | - | - |
| 2.5 | 20 | 18 | 24 | 21 | 27 | 25 | - | - | - | - | - |
| 4 | 26 | 24 | 32 | 28 | 37 | 33 | - | - | - | - | - |
| 6 | 34 | 31 | 41 | 36 | 47 | 43 | - | - | - | - | - |
| 10 | 46 | 42 | 57 | 50 | 65 | 59 | - | - | - | - | - |
| 16 | 61 | 56 | 76 | 68 | 87 | 79 | - | - | - | - | - |
| 25 | 80 | 73 | 101 | 89 | 114 | 104 | 131 | 114 | 110 | 146 | 130 |
| 35 | 99 | 89 | 125 | 110 | 141 | 129 | 162 | 143 | 137 | 181 | 162 |
| 50 | 119 | 108 | 151 | 134 | 182 | 167 | 196 | 174 | 167 | 219 | 197 |
| 70 | 151 | 136 | 192 | 171 | 234 | 214 | 251 | 225 | 216 | 281 | 254 |
| 95 | 182 | 164 | 232 | 207 | 284 | 261 | 304 | 275 | 264 | 341 | 311 |
| 120 | 210 | 188 | 269 | 239 | 330 | 303 | 352 | 321 | 308 | 396 | 362 |
| 150 | 240 | 216 | 300 | 262 | 381 | 349 | 406 | 372 | 356 | 456 | 419 |
| 185 | 273 | 245 | 341 | 296 | 436 | 400 | 463 | 427 | 409 | 521 | 480 |
| 240 | 321 | 286 | 400 | 346 | 515 | 472 | 546 | 507 | 485 | 615 | 569 |
| 300 | 367 | 328 | 458 | 394 | 594 | 545 | 629 | 587 | 561 | 709 | 659 |
| 400 | - | - | 546 | 467 | 694 | 634 | 754 | 689 | 656 | 852 | 795 |
| 500 | - | - | 626 | 533 | 792 | 723 | 868 | 789 | 749 | 982 | 920 |
| 630 | - | - | 720 | 611 | 904 | 826 | 1005 | 905 | 855 | 1138 | 1070 |
| Conductor cross-sectional area | 2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Ref. Methods A&B (enclosed in conduit or trunking) | Ref. Methods C & F(clipped direct, on trays or in free air) | Ref. Methods A & B (enclosed in conduit or trunking) | Ref. Methods C & F (clipped direct, on trays or in free air) | |||||||||||||||||||
| Cables touching | Cables spaced* | Cables touching, Trefoil | Cables touching, Flat | Cables spaced*, Flat | ||||||||||||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | ||||||||||||||
| mm² | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | |||||||||||||||
| 1.5 | 29 | 29 | 29 | 29 | 25 | 25 | 25 | 25 | ||||||||||||||
| 2.5 | 18 | 18 | 18 | 18 | 15 | 15 | 15 | 15 | ||||||||||||||
| 4 | 11 | 11 | 11 | 11 | 9.5 | 9.5 | 9,5 | 9.5 | ||||||||||||||
| 6 | 7.3 | 7.3 | 7.3 | 7.3 | 6.4 | 6.4 | 6.4 | 6.4 | ||||||||||||||
| 10 | 4.4 | 4.4 | 4.4 | 4.4 | 3.8 | 3.8 | 3.8 | 3.8 | ||||||||||||||
| 16 | 2.8 | 2.8 | 2.8 | 2.8 | 2.4 | 2.4 | 2.4 | 2.4 | ||||||||||||||
| r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | ||
| 25 | 1.75 | 1.80 | 0.33 | 1.80 | 1.75 | 0.20 | 1.75 | 1.75 | 0.29 | 1.80 | 1.50 | 0.29 | 1.55 | 1.50 | 0.175 | 1.50 | 1.50 | 0.25 | 1.55 | 1.50 | 0.32 | 1.55 |
| 35 | 1.25 | 1.30 | 0.31 | 1.30 | 1.25 | 0.195 | 1.25 | 1.25 | 0.28 | 1.30 | 1.10 | 0.27 | 1.10 | 1.10 | 0.170 | 1.10 | 1.10 | 0.24 | 1.10 | 1.10 | 0.32 | 1.15 |
| 50 | 0.93 | 0.95 | 0.3 | 1.0 | 0.93 | 0.19 | 0.95 | 0.93 | 0.28 | 0.97 | 0.81 | 0.26 | 0.85 | 0.8 | 0.165 | 0.82 | 0.8 | 0.24 | 0.84 | 0.8 | 0.32 | 0.86 |
| 70 | 0.63 | 0.65 | 0.29 | 0.72 | 0.63 | 0.185 | 0.66 | 0.63 | 0.27 | 0.69 | 0.56 | 0.25 | 0.61 | 0.55 | 0.16 | 0.57 | 0.55 | 0.24 | 0.6 | 0.55 | 0.31 | 0.63 |
| 95 | 0.46 | 0.49 | 0.28 | 0.56 | 0.47 | 0.18 | 0.50 | 0.47 | 0.27 | 0.54 | 0.42 | 0.24 | 0.48 | 0.41 | 0.155 | 0.43 | 0.41 | 0.23 | 0.47 | 0.4 | 0.31 | 0.51 |
| 120 | 0.36 | 0.39 | 0.27 | 0.47 | 0.37 | 0.175 | 0.41 | 0.37 | 0.26 | 0.45 | 0.33 | 0.23 | 0.41 | 0.32 | 0.15 | 0.36 | 0.32 | 0.23 | 0.4 | 0.32 | 0.3 | 0.44 |
| 150 | 0.29 | 0.31 | 0.27 | 0.41 | 0.3 | 0.175 | 0.34 | 0.29 | 0.26 | 0.39 | 0.27 | 0.23 | 0.36 | 0.26 | 0.15 | 0.3 | 0.26 | 0.23 | 0.34 | 0.26 | 0.3 | 0.40 |
| 185 | 0.23 | 0.25 | 0.27 | 0.37 | 0.24 | 0.17 | 0.29 | 0.24 | 0.26 | 0.35 | 0.22 | 0.23 | 0.32 | 0.21 | 0.145 | 0.26 | 0.21 | 0.22 | 0.31 | 0.21 | 0.3 | 0.36 |
| 240 | 0.18 | 0.195 | 0.26 | 0.33 | 0.185 | 0.165 | 0.25 | 0.185 | 0.25 | 0.31 | 0.17 | 0.23 | 0.29 | 0.16 | 0.145 | 0.22 | 0.16 | 0.22 | 0.27 | 0.16 | 0.29 | 0.34 |
| 300 | 0.145 | 0.16 | 0.26 | 0.31 | 0.15 | 0.165 | 0.22 | 0.15 | 0.25 | 0.29 | 0.14 | 0.23 | 0.27 | 0.13 | 0.14 | 0.19 | 0.13 | 0.22 | 0.25 | 0.13 | 0.29 | 0.32 |
| 400 | 0.105 | 0.13 | 0.26 | 0.29 | 0.12 | 0.16 | 0.20 | 0.115 | 0.25 | 0.27 | 0.12 | 0.22 | 0.25 | 0.105 | 0.14 | 0.175 | 0.105 | 0.21 | 0.24 | 0.1 | 0.29 | 0.31 |
| 500 | 0.086 | 0.11 | 0.26 | 0.28 | 0.098 | 0.155 | 0.185 | 0.093 | 0.24 | 0.26 | 0.1 | 0.22 | 0.25 | 0.086 | 0.135 | 0.16 | 0.086 | 0.21 | 0.23 | 0.081 | 0.29 | 0.30 |
| 630 | 0.068 | 0.094 | 0.25 | 0.27 | 0.081 | 0.155 | 0.175 | 0.076 | 0.24 | 0.25 | 0.08 | 0.22 | 0.24 | 0.072 | 0.135 | 0.15 | 0.072 | 0.21 | 0.22 | 0.066 | 0.28 | 0.29 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance