300/500V PVC Insulated, Non-sheathed Power Cables (Single Core 90°C)
APPLICATIONThis cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.STANDARDSBasic design to BS EN 50525-2-31(formerly BS 6004:2000)FIRE PERFO…
300_500V PVC Insulated, Non-sheathed Power Cables (Single Core90℃ ).pdf Contact us

APPLICATION

This cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.

STANDARDS

Basic design to BS EN 50525-2-31(formerly BS 6004:2000)

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)EN 60332-1-2

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

ConductorH05V-UClass 1 solid copper conductor to BS EN 60228.
H05V-RClass 2 stranded copper conductor to BS EN 60228.
H05V-KClass 5 stranded copper conductor to BS EN 60228.
InsulationPVC Type TI 3 according to BS EN 50363-3

COLOUR CODE

Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow. Bicolours of any combination of the above mono-colours are permitted.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation (PVC)90°C
Maximum short circuit temperature (5 Seconds)160°C
Minimum bending radiusUp to 8mm²4 x overall diameter

8mm² to 12mm²5 x overall diameter

Above 12mm²6 x overall diameter

CONSTRUCTION PARAMETERS

ConductorFLP300-V2-U/R/K
No. of Cores x Cross SectionClass of ConductorNominal Insulation ThicknessMaximum Overall DiameterApprox. Weight
No.xmm²  mmmmkg/km
1x0.5010.62.38
1x0.7510.62.511
1x1.010.62.714
1x0.5020.62.49
1x0.7520.62.612
1x1.020.62.814
1x0.5050.62.58
1x0.7550.62.711
1x1.050.62.813

ELECTRICAL PROPERTIES

Current-Carrying Capacities (Amp) according to HD516 Table 7 (a)

Conductor cross-sectional areaPVC insulated types (HD 21)
single-phase a.c.three-phase a.c.
mm²AA
0.5033
0.7566
1.01010

Note: These values apply to the majority of cases. Further information should be sought in unusual cases eg.:

(i) When high ambient temperatures are involved, ie. above 30°C

(ii) Where long lengths are used

(iii) Where ventilation is restricted

(iv) Where the cords are used for other purposes, ego internal wiring of apparatus.

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E1B

Nominal Cross Section Area2 cables d.c.2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
Ref. Methods A and B (enclosed in conduit or trunking)Ref. Methods C, F & G (clipped direct, on trays or in free air)Ref. Methods A & B (enclosed in conduit or trunkingRef. Methods C, F & G (clipped direct, on trays or in free air)
Cables touchingCables spaced*Cables touching, TrefoilCables touching, FlatCables spaced*, Flat
123456789
mm²mV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/m
0.509393939380808080
0.756262626254545454
1.04646464640404040