300-500V Mica+XLPE Insulated & lSZH Sheathed Fire Alarm Cables
APPLICATIONThe cables are primarily intended for use in the following applications:BS 5266-1 for emergency lighting of premises.BS 5839-1 for fire detection and fire alarm systems in and around building.BS 5839-8 for voice alarm systems.BS 5839-9 for …
300-500V Mica+xlPe Insulated & lSZH Sheathed Fire Alarm Cables.pdf Contact us

APPLICATION

This cable is strictly designed in accordance with BS 7629-1:2015 standard, integrating excellent fire resistance performance, safety and environmental protection characteristics, and durable structure into one professional cable. Its core advantages lie in the protection of circuit integrity in fire environments, low smoke and halogen-free safety design, and multi-scenario adaptability. It is widely applicable to high-rise buildings, subways, hospitals, industrial plants, data centers and other places with strict requirements for fire safety, providing reliable protection for power supply of critical equipment and operation of fire protection systems.

STANDARDS

Basic design to BS 7629-1:2015

FIRE PERFORMANCE

Circuit IntegrityBS 6387; BS EN50200
Flame Retardance (single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen freeIEC 60754-1; EN 50267-2-1
No corrosive Gas emissionIEC 60754-2; EN 50267-2-2
Minimum smoke emissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

Conductor : Copper conductor according to BS EN 60228 class 1/2.

Insulation : Fire resistant special ceramized silicone rubber compound type EI 2 as per BS EN 50363-1.

Screened : One or more metallic or laminated metallic tape(s) shall be applied, either longitudinally or helically or a combination of both, with the metallic element in contact with the uninsulated circuit protective conductor or drain wire.

Circuit Protective Conductor : Uninsulated tinned copper conductor of the same section and class as the insulated conductors in the two,three and four cores cables.

Sheath : Extruded LSZH type LTS 3 according to BS 7655-6.1.

Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Insulation Colour :

Number of coresCore colours or numbering
2 cores+uninsulated circuit protective conductorBrown, Blue or Brown, Brown
3 cores+uninsulated circuit protective conductorBrown, Black, Grey
4 cores+uninsulated circuit protective conductorBrown, Blue, Black, Grey
7, 12 and19 cores+uninsulated drain wireNumbers 1, 2, 3, 4, 5, 6, 7 and upwards or, for identification by colour, an identical colour(excluding brown and black),except for two adjacent cores in each layer distinctively coloured brown and black.

Sheath Colour : Colours upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 60°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius : 6 x Overall Diameter