FLP300-V-U/R/K Series Cable is an internationally compliant PVC-insulated copper conductor cable specifically designed for the safe and stable operation of electrical systems. Strictly adhering to the fundamental standard BS EN 50525-2-31 (formerly BS 6004:2000), it boasts excellent flame-retardant performance, flexible conductor configuration, and stable electrical performance. Widely suitable for wiring requirements across multiple scenarios such as industrial, construction, and instrumentation applications, it stands as an ideal choice that balances safety, durability, and compliance.
Basic design to BS EN 50525-2-31(formerly BS 6004:2000)
| Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2 |
300/500V
| Conductor | H05V-U | Class 1 solid copper conductor to BS EN 60228. |
| H05V-R | Class 2 stranded copper conductor to BS EN 60228. | |
| H05V-K | Class 5 stranded copper conductor to BS EN 60228. | |
| Insulation | PVC Type TI 1 according to BS EN 50363-3 | |
Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow. Bicolours of any combination of the above mono-colours are permitted.
| Maximum temperature range during operation (PVC) | 70°C | |
| Maximum short circuit temperature (5 Seconds) | 160°C | |
| Minimum bending radius | Up to 8mm²: | 4 x overall diameter |
| 8mm² to 12mm² | 5 x overall diameter | |
| Above 12mm² | 6 x overall diameter | |
| Conductor | FLP300-V-U/R/K | |||
|---|---|---|---|---|
| No. of Cores x Cross Section | Class of Conductor | Nominal Insulation Thickness | Maximum Overall Diameter | Approx. Weight |
| No.xmm² | mm | mm | kg/km | |
| 1x0.50 | 1 | 0.6 | 2.3 | 8 |
| 1x0.75 | 1 | 0.6 | 2.5 | 11 |
| 1x1.0 | 1 | 0.6 | 2.7 | 14 |
| 1x0.50 | 2 | 0.6 | 2.4 | 9 |
| 1x0.75 | 2 | 0.6 | 2.6 | 12 |
| 1x1.0 | 2 | 0.6 | 2.8 | 14 |
| 1x0.50 | 5 | 0.6 | 2.5 | 8 |
| 1x0.75 | 5 | 0.6 | 2.7 | 11 |
| 1x1.0 | 5 | 0.6 | 2.8 | 13 |
| Conductor cross-sectional area | PVC insulated types (HD 21) | |
|---|---|---|
| single-phase a.c. | three-phase a.c. | |
| mm² | A | A |
| 0.50 | 3 | 3 |
| 0.75 | 6 | 6 |
| 1.0 | 10 | 10 |
Note: These values apply to the majority of cases. Further information should be sought in unusual cases eg.: (i) When high ambient temperatures are involved, ie. above 30°C (ii) Where long lengths are used (iii) Where ventilation is restricted (iv) Where the cords are used for other purposes, ego internal wiring of apparatus. | ||
| Conductor cross-sectional area | d.c. or single-phase a.c. | Three-phase a.c. |
|---|---|---|
| mm² | mV/A/m | mV/A/m |
| 0.50 | 93 | 80 |
| 0.75 | 62 | 54 |
| 1.0 | 46 | 40 |