300/500V PVC Insulated, PVC Sheathed Power Cables to BS 6004 (Single Core)
APPLICATIONThe cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings. This product type is TUV approved.STANDARDSBasic design to BS 6004: 2012FI…
300_500V PVC Insulated, PVC Sheathed Power Cables to BS6004 (Single Core).pdf Contact us

APPLICATION

The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings. 

STANDARDS

Basic design to BS 6004: 2012

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)EN 60332-1-2

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

ConductorAnnealed copper conductor, class 1 (1.0mm² to 2.5mm²) or class 2 (4mm² to 35mm²) according to BS EN 60228.
InsulationPVC Type TI 1 according to BS EN 50363-3.
Outer SheathPVC Type 6 according to BS 7655-4.2.
Outer Sheath OptionUV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE

Insulation ColourBrown or blue.
Sheath ColourGrey, other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation (PVC)70°C
Maximum short circuit temperature (5 Seconds)160°C
Minimum bending radiusUp to 10mm² - Fixed: 3 x overall diameter

10mm² to 25mm² - Fixed: 4 x overall diameter

CONSTRUCTION PARAMETERS

ConductorFLP300 VV-U/R
No. of Cores x Cross SectionClass of ConductorNominal Insulation ThicknessNominal Sheath ThicknessMaximum Overall DiameterApprox. Weight
No.xmm²  mm mmkg/km
1x1.010.60.84.527
1x1.510.70.85.036
1x2.510.80.85.752
1x4.020.80.96.776
1x6.020.80.97.3100
1x1021.00.98.8160
1x1621.01.010.1230
1x2521.21.112.1340
1x3521.21.113.5440

ELECTRICAL PROPERTIES

Conductor Operating Temperature70°C
Ambient Temperature30°

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4D1A

Conductor cross- sectional areaReference Method A (enclosed in conduit in thermally insulating wall etc)Reference Method B (enclosed in conduit on a wall or in trunking etc)Reference Method C (clipped direct)Reference Method F (in free air or on a perforated cable tray horizontal or vertical etc)
TouchingSpaced by one cable diameter
2 cables, single-phase a.c. or d.c.3 or 4 cables, three-phase a.c.2 cables, single-phase a.c. or d.c3 or 4 cables, three-phase a.c.2 cables, single-phase a.c. or d.c. flat and touching3 or 4 cables, three-phase a.c. flat and touching or trefoil2 cables, single-phase a.c. or d.c. flat3 cables, three-phase a.c. flat3 cables, three-phase a.c. trefoil2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat
HorizontalVertical
123456789101112
mm²AAAAAAAAAAA
1.011.010.513.512.015.514-----
1.514.513.517.515.52018-----
2.5201824212725-----
4.0262432283733-----
6.0343141364743-----
10464257506559-----
16615676688779-----
25807310189114104131114110146130
359989125110141129162143137181162

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4D1B

Nominal Cross Section Area2 cables d.c.2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
Ref. Methods A and B (enclosed in conduit or trunking)Ref. Methods C & F(clipped direct, on trays or in free air)Ref. Methods A & B (enclosed in conduit or trunkingRef. Methods C & F (clipped direct, on trays or in free air)
Cables touchingCables spaced*Cables touching, TrefoilCables touching, FlatCables spaced*, Flat
123456789
mm²mV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/m
1.04444444438383838
1.52929292925252525
2.51818181815151515
4.0111111119.59.59,59.5
6.07.37.37.37.36.46.46.46.4
104.44.44.44.43.83.83.83.8
162.82.82.82.82.42.42.42.4


rxzrxzrxzrxzrxzrxzrxz
251.751.80.331.81.750.201.751.750.291.81.50.291.551.50.1751.51.50.251.551.50.321.55
351.251.30.311.31.250.1951.251.250.281.31.10.271.101.10.1701.11.10.241.101.10.321.15

Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance