450/750V Mica+LSZH Insulated, Non-sheathed Power Cables to BS EN 50525-3-41 (Single Core)
APPLICATIONThe cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.STANDARDSBasic design adapted from BS EN 50525-3-41(formerly BS 7211)FIRE PE…
Contact us

APPLICATION

The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.

STANDARDS

Basic design adapted from BS EN 50525-3-41(formerly BS 7211)

FIRE PERFORMANCE

Circuit IntegrityIEC 60331-21; BS 6387; BS 8491
Flame Retardance (Single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Halogen freeIEC 60754-1; EN 50267-2-1
No Corrosive Gas EmissionIEC60754-2; EN 50267-2-2
Minimum Smoke EmissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

450/750V

CABLE CONSTRUCTION

Conductor : Copper conductor according to BS EN 60228 class 1/2/5.

FRP450 mZ-U : 1.5-10mm² Class 1 solid copper conductor to BS EN 60228.

FRP450 mZ-R : 1.5-630mm² Class 2 stranded copper conductor to BS EN 60228.

FRP450 mZ-K : 1.5-240mm² Class 5 stranded copper conductor to BS EN 60228.

Fire Barrier : Mica glass tape.

Insulation : Crosslinked polyolefin material type EI 5 according to EN 50363-5.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius :

OD<8mm : 4 × Overall Diameter

8mm≤OD≤12mm : 5 × Overall Diameter

OD>12mm : 6 × Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFRP450 mZ-U/R/K
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessMin. Overall DiameterMax. Overall DiameterApprox. Weight
No.×mm² mmmmmmkg/km
1×1.510.73.64.322
1×2.510.84.25.035
1×410.84.65.652
1×610.85.16.273
1×1011.06.37.6122
1×1.520.73.74.424
1×2.520.84.35.137
1×420.84.85.754
1×620.85.36.476
1×1021.06.68.0127
1×1621.07.49.0191
1×2521.29.111.1301
1×3521.210.012.3405
1×5021.411.614.2550
1×7021.413.116.1774
1×9521.615.118.61069
1×12021.616.620.41333
1×15021.818.322.61640
1×18522.020.325.12055
1×24022.223.028.52690
1×30022.425.531.63364
1×40022.628.535.34252
1×50022.831.539.25343
1×63022.835.043.56868
1×1.550.73.84.523
1×2.550.84.45.337
1×450.84.95.954
1×650.85.46.576
1×1051.06.78.1128
1×1651.07.79.4191
1×2551.29.411.6297
1×3551.210.713.1403
1×5051.412.515.4577
1×7051.414.217.6803
1×9551.616.119.81066
1×12051.617.721.91332
1×15051.819.624.31660
1×18552.021.626.82030
1×24052.224.530.42659

ELECTRICAL PROPERTIES

Conductor operating temperature : 90°C

Ambient temperature : 30°C

CURRENT-CARRYING CAPACITIES (AMP) ACCORDING TO BS 7671:2008 TABLE 4E1A

Conductor cross-sectional areaRef. Method A (enclosed in conduit in thermally insulating wall etc.)Ref. Method B (enclosed in conduit on a wall or in trunking etc.)Ref. Method C (clipped direct)Ref. Method F (in free air or on a perforated cable tray, horizontal or vertical etc)Ref. Method G (in free air)
TouchingSpaced by one cable diameter
2 cables, single-phase a.c. or d.c.3 or 4 cables, three-phase a.c.2 cables, single-phase a.c. or d.c3 or 4 cables, three-phase a.c.2 cables, single-phase a.c. or d.c. flat and touching3 or 4 cables, three-phase a.c. flat and touching or trefoil2 cables, single-phase a.c. or d.c. flat3 cables, three-phase a.c. flat3 cables, three-phase a.c. trefoil2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat
HorizontalVertical
123456789101112
mm²AAAAAAAAAAA
1.5191723202523-----
2.5262331283431-----
4353142374641-----
6454054485954-----
10615475668174-----
1681731008810999-----
2510695133117143130161141135182161
35131117164144176161200176169226201
50158141198175228209242216207275246
70200179253222293268310279268353318
95241216306269355326377342328430389
120278249354312413379437400383500454
150318285393342476436504464444577527
185362324449384545500575533510661605
240424380528450644590679634607781719
300486435603514743681783736703902833
400--68358486879394086882310851008
500--783666990904108399894612531169
630--9007641130103312541151108814541362

VOLTAGE DROP (PER AMP PER METER) ACCORDING TO BS 7671:2008 TABLE 4E1B

Conductor cross-sectional area2 cables d.c.2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
Ref. Methods A&B (enclosed in conduit or trunking)Ref. Methods C & F(clipped direct, on trays or in free air)Ref. Methods A & B (enclosed in conduit or trunking)Ref. Methods C & F (clipped direct, on trays or in free air)
Cables touchingCables spaced*Cables touching, TrefoilCables touching, FlatCables spaced*, Flat
123456789
mm²mV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/m
1.53131313127272727
2.51919191916161616
41212121210101010
67.97.97.97.96.86.86.86.8
104.74.74.74.74.04.04.04.0
162.92.92.92.92.52.52.52.5


rxzrxzrxzrxzrxzrxzrxz
251.851.850.311.901.850.1901.851.850.281.851.600.271.651.600.1651.601.600.1901.601.600.271.65
351.351.350.291.351.350.1801.351.350.271.351.150.251.151.150.1551.151.150.1801.151.150.261.20
500.991.000.291.050.990.1801.000.990.271.000.870.250.900.860.1550.870.860.1800.870.860.260.89
700.680.700.280.750.680.1750.710.680.260.730.600.240.650.590.1500.610.590.1750.620.590.250.65
950.490.510.270.580.490.1700.520.490.260.560.440.230.500.430.1450.450.430.1700.460.430.250.49
1200.390.410.260.480.390.1650.430.390.250.470.350.230.420.340.1400.370.340.1650.380.340.240.42
1500.320.330.260.430.320.1650.360.320.250.410.290.230.370.280.1400.310.280.1650.320.280.240.37
1850.250.270.260.370.260.1650.300.250.250.360.230.230.320.220.1400.260.220.1650.280.220.240.33
2400.1900.210.260.330.200.1600.250.1950.250.310.1850.220.290.1700.1400.220.1700.1650.240.1700.240.29
3000.1550.1750.250.310.1600.1600.220.1550.250.290.1500.220.270.1400.1400.1950.1350.1600.210.1350.240.27
4000.1200.1400.250.290.1300.1550.200.1250.240.270.1250.220.250.1100.1350.1750.1100.1600.1950.1100.240.26
5000.0930.1200.250.280.1050.1550.1850.0980.240.260.1000.220.240.0900.1350.1600.0880.1600.1800.0850.240.25
6300.0720.1000.250.270.0860.1550.1750.0780.240.250.0880.210.230.0740.1350.1500.0710.1600.1700.0680.230.24

Note: *Spacings larger than one cable diameter will result in a large voltage drop.

r = conductor resistance at operating temperature

x = reactance

z = impedance