This series of cables is specifically designed for critical facilities that demand extremely high levels of safety and reliability. It is widely used in power plants, rail transit systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings . With exceptional fire resistance and durability, it provides robust protection for life and property safety, as well as continuous power supply for critical equipment.
The fundamental design of the product strictly adheres to the BS 6724 standard.
| Circuit Integrity | IEC 60331-21; EN 6387; BS 8491 |
| Flame Retardance (Single vertical wire or cable test) | IEC 60332-1-2; EN 60332-1-2 |
| Reduced fire Propagation (Vertically-mounted bundled wires & cables test) | IEC 60332-3-24; EN 60332-3-24 |
| Halogen Free | IEC 60754-1; EN 50267-2-1 |
| No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2 |
| Minimum Smoke Emission | IEC 61034-2; EN 61034-2 |
600/1000V
Conductor : Annealed copper wire, stranded according to BS EN 60228 class 2.
Fire Barrier : Mica glass tape.
Insulation : XLPE type GP 8 according to BS 7655-1.3. HEPR type GP 6 according to BS 7655-1.2 or crosslinked polyolefin material type EI 5 according to BS EN 50363-5 can be offered as option.
Bedding : Extruded layer of polymeric material.
Armouring : Aluminium wire.
Outer Sheath : Extruded layer of polymeric material LTS 1 according to BS 7655-6.1.
Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.
Insulation Colour : Brown or blue; other colours can be offered upon request.
Sheath Colour : Black; other colours can be offered upon request.
Maximum temperature range during operation : 90°C
Maximum short circuit temperature (5 Seconds) : 250°C
Minimum bending radius : 6 × Overall Diameter
| Conductor | FRP600-mRZ1MAZ1-R | ||||||
|---|---|---|---|---|---|---|---|
| No. of Cores × Cross-sectional Area | Conductor Class | Nominal Insulation Thickness | Nominal Bedding Thickness | Nominal AL Wire Armour Diameter | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight |
| no.×mm² | mm | mm | mm | mm | kg/km | ||
| 1×50 | 2 | 1.0 | 0.8 | 0.9 | 1.5 | 18.5 | 696 |
| 1×70 | 2 | 1.1 | 0.8 | 1.25 | 1.5 | 21.2 | 949 |
| 1×95 | 2 | 1.1 | 0.8 | 1.25 | 1.6 | 23.3 | 1253 |
| 1×120 | 2 | 1.2 | 0.8 | 1.25 | 1.6 | 25.2 | 1533 |
| 1×150 | 2 | 1.4 | 1.0 | 1.6 | 1.7 | 28.4 | 1863 |
| 1×185 | 2 | 1.6 | 1.0 | 1.6 | 1.8 | 31.0 | 2304 |
| 1×240 | 2 | 1.7 | 1.0 | 1.6 | 1.8 | 33.8 | 2938 |
| 1×300 | 2 | 1.8 | 1.0 | 1.6 | 1.9 | 36.6 | 3626 |
| 1×400 | 2 | 2.0 | 1.2 | 2.0 | 2.0 | 41.5 | 4668 |
| 1×500 | 2 | 2.2 | 1.2 | 2.0 | 2.1 | 45.2 | 5795 |
| 1×630 | 2 | 2.4 | 1.2 | 2.0 | 2.2 | 49.8 | 7357 |
| 1×800 | 2 | 2.6 | 1.4 | 2.5 | 2.4 | 56.4 | 9380 |
| 1×1000 | 2 | 2.8 | 1.4 | 2.5 | 2.5 | 61.6 | 11660 |
Conductor operating temperature : 90°C
Ambient temperature : 30°C
| Conductor cross-sectional area | Ref. Method C (clipped direct) | Ref. Method F (in free air or on a perforated cable tray, horizontal or vertical) | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Touching | Touching | Spaced by on cable diameter | |||||||||
| 2 cables, single-phase a.c. or d.c. flat | 3 or 4 cables, three-phase a.c. flat | 2 cables, single-phase a.c. or d.c. flat | 3 or 4 cables, three-phase a.c. flat | 3 cables three-phase a.c. trefoil | 2 cables, d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | ||||
| Horizontal | Vertical | Horizontal | Vertical | Horizontal | Vertical | ||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
| mm² | A | A | A | A | A | A | A | A | A | A | A |
| 50 | 237 | 220 | 253 | 232 | 222 | 284 | 270 | 282 | 266 | 288 | 266 |
| 70 | 303 | 277 | 322 | 293 | 285 | 356 | 349 | 357 | 337 | 358 | 331 |
| 95 | 367 | 333 | 389 | 352 | 346 | 446 | 426 | 436 | 412 | 425 | 393 |
| 120 | 425 | 383 | 449 | 405 | 402 | 519 | 497 | 504 | 477 | 485 | 449 |
| 150 | 488 | 437 | 516 | 462 | 463 | 600 | 575 | 566 | 539 | 549 | 510 |
| 185 | 557 | 496 | 587 | 524 | 529 | 688 | 660 | 643 | 614 | 618 | 574 |
| 240 | 656 | 579 | 689 | 612 | 625 | 815 | 782 | 749 | 714 | 715 | 666 |
| 300 | 755 | 662 | 792 | 700 | 720 | 943 | 906 | 842 | 805 | 810 | 755 |
| 400 | 853 | 717 | 899 | 767 | 815 | 1137 | 1094 | 929 | 889 | 848 | 797 |
| 500 | 962 | 791 | 1016 | 851 | 918 | 1314 | 1266 | 1032 | 989 | 923 | 871 |
| 630 | 1082 | 861 | 1146 | 935 | 1027 | 1528 | 1474 | 1139 | 1092 | 992 | 940 |
| 800 | 1170 | 904 | 1246 | 987 | 1119 | 1809 | 1744 | 1204 | 1155 | 1042 | 978 |
| 1000 | 1261 | 961 | 1345 | 1055 | 1214 | 2100 | 2026 | 1289 | 1238 | 1110 | 1041 |
| Conductor cross-sectional area | 2 cables d.c. | Ref. Methods C&F (clipped direct, on trays or in free air) | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||||||||||||
| Touching | Spaced* | Trefoil and touching | Flat and touching | Flat and spaced* | ||||||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | ||||||||||
| mm² | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | |||||||||||
| r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | ||
| 50 | 0.98 | 0.99 | 0.21 | 1.00 | 0.98 | 0.29 | 1.00 | 0.86 | 0.180 | 0.87 | 0.84 | 0.25 | 0.88 | 0.84 | 0.33 | 0.90 |
| 70 | 0.67 | 0.68 | 0.20 | 0.71 | 0.69 | 0.29 | 0.75 | 0.59 | 0.170 | 0.62 | 0.60 | 0.25 | 0.65 | 0.62 | 0.32 | 0.70 |
| 95 | 0.49 | 0.51 | 0.195 | 0.55 | 0.53 | 0.28 | 0.60 | 0.44 | 0.170 | 0.47 | 0.46 | 0.24 | 0.52 | 0.49 | 0.31 | 0.58 |
| 120 | 0.39 | 0.41 | 0.190 | 0.45 | 0.43 | 0.27 | 0.51 | 0.35 | 0.165 | 0.39 | 0.38 | 0.34 | 0.44 | 0.41 | 0.30 | 0.51 |
| 150 | 0.31 | 0.33 | 0.185 | 0.38 | 0.36 | 0.27 | 0.45 | 0.29 | 0.160 | 0.33 | 0.31 | 0.23 | 0.39 | 0.34 | 0.39 | 0.45 |
| 185 | 0.25 | 0.27 | 0.185 | 0.33 | 0.30 | 0.26 | 0.40 | 0.23 | 0.160 | 0.28 | 0.26 | 0.23 | 0.34 | 0.29 | 0.29 | 0.41 |
| 240 | 0.195 | 0.21 | 0.180 | 0.28 | 0.24 | 0.26 | 0.35 | 0.180 | 0.155 | 0.24 | 0.21 | 0.22 | 0.30 | 0.24 | 0.28 | 0.37 |
| 300 | 0.155 | 0.17 | 0.175 | 0.25 | 0.195 | 0.25 | 0.32 | 0.145 | 0.150 | 0.21 | 0.170 | 0.22 | 0.28 | 0.20 | 0.27 | 0.34 |
| 400 | 0.115 | 0.145 | 0.170 | 0.22 | 0.180 | 0.24 | 0.30 | 0.125 | 0.150 | 0.195 | 0.160 | 0.21 | 0.27 | 0.20 | 0.27 | 0.33 |
| 500 | 0.093 | 0.125 | 0.170 | 0.21 | 0.165 | 0.24 | 0.29 | 0.105 | 0.145 | 0.180 | 0.145 | 0.20 | 0.25 | 0.190 | 0.24 | 0.31 |
| 630 | 0.073 | 0.105 | 0.165 | 0.195 | 0.150 | 0.23 | 0.27 | 0.092 | 0.145 | 0.170 | 0.135 | 0.195 | 0.24 | 0.175 | 0.23 | 0.29 |
| 800 | 0.056 | 0.090 | 0.160 | 0.190 | 0.145 | 0.23 | 0.27 | 0.086 | 0.140 | 0.165 | 0.130 | 0.180 | 0.23 | 0.175 | 0.195 | 0.26 |
| 1000 | 0.045 | 0.092 | 0.155 | 0.180 | 0.140 | 0.21 | 0.25 | 0.080 | 0.135 | 0.155 | 0.125 | 0.170 | 0.21 | 0.165 | 0.180 | 0.24 |
Note : *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance