This series of cables is specifically designed for critical facilities that require the highest levels of safety and reliability. It is widely used in power plants, subway passenger systems, airports, petrochemical facilities, star-rated hotels, large hospitals, and high-rise buildings, ensuring stable and safe power transmission in various complex environments.
The product design strictly adheres to international standards such as IEC 60502-1, guaranteeing exceptional and reliable fundamental performance.
| Circuit Integrity | IEC 60331-21; EN 6387; BS 8491 |
| Flame Retardance (Single vertical wire or cable test) | IEC 60332-1-2; EN 60332-1-2 |
| Reduced fire Propagation (Vertically-mounted bundled wires & cables test) | IEC 60332-3-24; EN 60332-3-24 |
| Halogen Free | IEC 60754-1; EN 50267-2-1 |
| No Corrosive Gas emission | IEC 60754-2; EN 50267-2-2 |
| Minimum smoke emission | IEC 61034-2; EN 61034-2 |
600/1000V
Conductor : The conductors shall be class 2 plain or metal-coated annealed copper in accordance with IEC 60228. Class 1 and class 5 conductor can be offered as option.
Fire Barrier : Mica glass tape.
Insulation : Thermosetting XLPE material and thickness shall be as per IEC 60502-1.
Inner Covering Option : Thermoplastic halogen free compound ST8 as per IEC 60502-1.
Armouring : Aluminium wire.
Outer Sheath : Thermoplastic halogen free compound ST8 as per IEC 60502-1.
Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.
Insulation Colour : Brown or blue; other colours can be offered upon request.
Sheath Colour : Black; other colours can be offered upon request.
Maximum temperature range during operation : 90°C
Maximum short circuit temperature (5 Seconds) : 250°C
Minimum bending radius : 6 × Overall Diameter
| Conductor | FRP600-mRZ1MAZ1-R | ||||||
|---|---|---|---|---|---|---|---|
| No. of Cores × Cross-sectional Area | Conductor Class | Nominal Insulation Thickness | Nominal Inner Covering Thickness | Nominal AL Wire Diameter | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight |
| no.×mm² | mm | mm | mm | mm | mm | kg/km | |
| 1×4 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 12.2 | 205 |
| 1×6 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 12.7 | 238 |
| 1×10 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 13.7 | 300 |
| 1×16 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 14.7 | 383 |
| 1×25 | 2 | 0.9 | 1.0 | 0.8 | 1.8 | 16.4 | 520 |
| 1×35 | 2 | 0.9 | 1.0 | 1.25 | 1.8 | 18.5 | 695 |
| 1×50 | 2 | 1.0 | 1.0 | 1.25 | 1.8 | 20.0 | 864 |
| 1×70 | 2 | 1.1 | 1.0 | 1.25 | 1.8 | 22.0 | 1132 |
| 1×95 | 2 | 1.1 | 1.0 | 1.6 | 1.8 | 25.0 | 1530 |
| 1×120 | 2 | 1.2 | 1.0 | 1.6 | 1.8 | 26.8 | 1840 |
| 1×150 | 2 | 1.4 | 1.0 | 1.6 | 1.8 | 28.8 | 2186 |
| 1×185 | 2 | 1.6 | 1.0 | 1.6 | 1.8 | 31.4 | 2680 |
| 1×240 | 2 | 1.7 | 1.0 | 1.6 | 1.9 | 34.5 | 3380 |
| 1×300 | 2 | 1.8 | 1.0 | 2.0 | 2.0 | 38.5 | 4255 |
| 1×400 | 2 | 2.0 | 1.2 | 2.0 | 2.2 | 42.3 | 5298 |
| 1×500 | 2 | 2.2 | 1.2 | 2.0 | 2.3 | 46.4 | 6551 |
Conductor operating temperature : 90°C
Ambient temperature : 30°C
| Conductor cross- sectional area | Ref. Method c (clipped direct) | Ref. Method f (in free air or on a perforated cable tray, horizontal or vertical) | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Touching | Touching | Spaced by on cable diameter | |||||||||
| 2 cables, single-phase a.c. or d.c. flat | 3 or 4 cables, three-phase a.c. flat | 2 cables, single- phase a.c. or d.c. flat | 3 or 4 cables, three-phase a.c. flat | 3 cables three-phase a.c. trefoil | 2 cables, d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | ||||
| Horizontal | Vertical | Horizontal | Vertical | Horizontal | Vertical | ||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
| mm² | A | A | A | A | A | A | A | A | A | A | A |
| 50 | 237 | 220 | 253 | 232 | 222 | 284 | 270 | 282 | 266 | 288 | 266 |
| 70 | 303 | 277 | 322 | 293 | 285 | 356 | 349 | 357 | 337 | 358 | 331 |
| 95 | 367 | 333 | 389 | 352 | 346 | 446 | 426 | 436 | 412 | 425 | 393 |
| 120 | 425 | 383 | 449 | 405 | 402 | 519 | 497 | 504 | 477 | 485 | 449 |
| 150 | 488 | 437 | 516 | 462 | 463 | 600 | 575 | 566 | 539 | 549 | 510 |
| 185 | 557 | 496 | 587 | 524 | 529 | 688 | 660 | 643 | 614 | 618 | 574 |
| 240 | 656 | 579 | 689 | 612 | 625 | 815 | 782 | 749 | 714 | 715 | 666 |
| 300 | 755 | 662 | 792 | 700 | 720 | 943 | 906 | 842 | 805 | 810 | 755 |
| 400 | 853 | 717 | 899 | 767 | 815 | 1137 | 1094 | 929 | 889 | 848 | 797 |
| 500 | 962 | 791 | 1016 | 851 | 918 | 1314 | 1266 | 1032 | 989 | 923 | 871 |
| Conductor cross-sectional area | 2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Touching | Spaced* | Trefoil and touching | Flat and touching | Flat and spaced* | ||||||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | ||||||||||
| mm² | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | ||||||||||
| r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | ||
| 50 | 0.98 | 0.99 | 0.21 | 1.00 | 0.98 | 0.29 | 1.00 | 0.86 | 0.180 | 0.87 | 0.84 | 0.25 | 0.88 | 0.84 | 0.33 | 0.90 |
| 70 | 0.67 | 0.68 | 0.20 | 0.71 | 0.69 | 0.29 | 0.75 | 0.59 | 0.170 | 0.62 | 0.60 | 0.25 | 0.65 | 0.62 | 0.32 | 0.70 |
| 95 | 0.49 | 0.51 | 0.195 | 0.55 | 0.53 | 0.28 | 0.60 | 0.44 | 0.170 | 0.47 | 0.46 | 0.24 | 0.52 | 0.49 | 0.31 | 0.58 |
| 120 | 0.39 | 0.41 | 0.190 | 0.45 | 0.43 | 0.27 | 0.51 | 0.35 | 0.165 | 0.39 | 0.38 | 0.34 | 0.44 | 0.41 | 0.30 | 0.51 |
| 150 | 0.31 | 0.33 | 0.185 | 0.38 | 0.36 | 0.27 | 0.45 | 0.29 | 0.160 | 0.33 | 0.31 | 0.23 | 0.39 | 0.34 | 0.39 | 0.45 |
| 185 | 0.25 | 0.27 | 0.185 | 0.33 | 0.30 | 0.26 | 0.40 | 0.23 | 0.160 | 0.28 | 0.26 | 0.23 | 0.34 | 0.29 | 0.29 | 0.41 |
| 240 | 0.195 | 0.21 | 0.180 | 0.28 | 0.24 | 0.26 | 0.35 | 0.180 | 0.155 | 0.24 | 0.21 | 0.22 | 0.30 | 0.24 | 0.28 | 0.37 |
| 300 | 0.155 | 0.17 | 0.175 | 0.25 | 0.195 | 0.25 | 0.32 | 0.145 | 0.150 | 0.21 | 0.170 | 0.22 | 0.28 | 0.20 | 0.27 | 0.34 |
| 400 | 0.115 | 0.145 | 0.170 | 0.22 | 0.180 | 0.24 | 0.30 | 0.125 | 0.150 | 0.195 | 0.160 | 0.21 | 0.27 | 0.20 | 0.27 | 0.33 |
| 500 | 0.093 | 0.125 | 0.170 | 0.21 | 0.165 | 0.24 | 0.29 | 0.105 | 0.145 | 0.180 | 0.145 | 0.20 | 0.25 | 0.190 | 0.24 | 0.31 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance