300/500V PVC Insulated, PVC Sheathed, Twin & Earth Cables (2-3 Cores)
APPLICATIONThe cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings. This product type is TUV approved.STANDARDSBasic design to BS 6004:2012FIR…
300_500V PVC Insulated, PVC Sheathed, Twin & Earth Cables (2-3Cores).pdf Contact us

APPLICATION

FLP300-VV-U/R Series Cable is a PVC-insulated and sheathed power cable that complies with international standards and offers comprehensive performance, specifically designed for stable and safe power transmission.

The product strictly adheres to the basic design standard of BS 6004:2012, with flame retardant performance passing the EN 60332-1-2 single vertical burning test. Boasting a voltage rating of 300/500V, it is widely applicable to various fixed installation scenarios such as building electrical systems, industrial wiring, and civil facilities, providing efficient and reliable power connection for your electrical system. 

STANDARDS

Basic design to BS 6004:2012

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)EN 60332-1-2

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

ConductorAnnealed copper conductor,class 1 (1.0mm² to 2.5mm²) or class 2 (4mm² to 35mm²) according to BS EN 60228.
InsulationPVC Type TI 1 according to BS EN 50363-3.
Circuit Protective Conductor (CPC)

Annealed plain copper (class 1 or 2)

Position of CPCCentrally placed between cores in same plane (twin); centrally placed between black and grey cores in same plane(3-core).
Outer SheathPVC Type 6 according to BS 7655-4.2.
Outer Sheath OptionUV resistance,hydrocarbon resistance,oil resistance,anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1,IEC 60332-3,UL 1581,UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE

Insulation Colour :

Twin : brown and blue, alternatively, for 2 x 1.0 and 2 x 1.5 cables, brown and brown;

3-core : brown, black (centre core), and grey

Sheath Colour : Grey, other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation (PVC)70°C
Maximum short circuit temperature (5 Seconds)160°C
Minimum bending radius6 x Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFLP300-VV-U/R
No. of Cores x Cross SectionClass of ConductorNominal Insulation ThicknessCross-Section Area of CPCClass of CPCNominal Sheath ThicknessMaximum Overall DiameterApprox. Weight
No.xmm² mmmm² mmmmkg/km
2x1.010.61.010.94.8x8.768
2x1.510.71.010.95.3x9.785
2x2.510.81.511.06.2x11.7120
2x4.020.81.511.06.9x13.1175
2x6.020.82.511.17.8x15.0240
2x1021.04.021.29.5x18.9390
2x1621.06.021.310.8x21.9560
3x1.010.61.010.94.8x11.491
3x1.510.71.010.95.3x12.9115
3x2.510.81.511.06.2x15.3170
3x4.020.81.511.17.1x17.9250
3x6.020.82.511.17.8x20.2340
3x1021.04.021.29.5x25.7540
3x1621.06.021.310.8x29.7790

ELECTRICAL PROPERTIES

Conductor Operating Temperature70°C
Ambient Temperature30°C

Current-Carrying Capacities (Amp) and Voltage Drop (Per Amp Per Meter) according to BS7671:2008 table 4D5

Conductor cross-sectional areaReference Method 100# (above a plasterboard ceiling covered by thermal insulation not exceeding 100 mm in thickness)Reference Method 101# (above a plasterboard ceiling covered by thermal insulation exceeding 100 mm in thickness)Reference Method 102# (in a stud wall with thermal insulation with cable touching the inner wall surface)Reference Method 103# (in a stud wall with thermal insulation with cable not touching the inner wall surface)Reference Method C* (clipped direct)Reference Method A* (enclosed in conduit in an insulated wall)Voltage Drop (per ampere per meter)
12345678
mm²AAAAAAmV/A/m
1.01310.5138.01611.544
1.5161316102014.529
2.521172113.5272018
4.027222717.5372611
6.034273523.547327.3
104536473264444.4
1657466342.585572.8

A* For full installation method refer to Table 4A2 (BS 7671-2008) Installation Method 2 but for flat twin and earth cable

C* For full installation method refer to Table 4A2 (BS 7671-2008) Installation Method 20 but for flat twin and earth cable

100# For full installation method refer to Table 4A2 (BS 7671-2008) Installation Method 100

102# For full installation method refer to Table 4A2 (BS 7671-2008) Installation Method 102

103# For full installation method refer to Table 4A2 (BS 7671-2008) Installation Method 103

Wherever practicable, a cable is to be fixed in a position such that it will not be covered with thermal insulation.

Regulation 523.7, BS 5803-5 Appendix C: Avoidance of overheating of electric cables, Building Regulations Approved document B and Thermal insulation: avoiding risks, BR 262, BRE, 2001 refer.