600/1000V single core XLPE insulated PVC sheathed unarmoured cable is designed for fixed low voltage power distribution.
It is suitable for industrial plants, commercial buildings, power distribution systems, electrical cabinets and general low voltage installations.
The XLPE insulation provides reliable electrical performance and thermal stability for low voltage power circuits.
The PVC outer sheath provides general protection for fixed installation environments.
As an unarmoured cable, it is suitable for installations where mechanical protection is provided by cable tray, conduit, trunking, duct or other suitable installation methods.
It is not recommended for direct burial without additional mechanical protection.
The cable should be selected according to voltage rating, conductor size, conductor material, installation method and project specification.
Basic design to to BS 7889:2012
| Flame Retardance (Single Vertical Wire Test) | BS EN 60332-1-2 |
600/1000V
| Conductor | Annealed copper conductor, class 5 according to BS EN 60228. |
| Insulation | XLPE type GP8 according to BS 7655-1.3. |
| Inner Covering Option | The optional inner covering, where used, shall consist of an extruded layer of synthetic polymeric material. It shall surround the single core and the laid-up two, three, four or five cores, giving the assembly a practically circular shape. |
| Outer Sheath | PVC Type 9 according to BS 7655-4.2. |
| Outer Sheath Option | UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request. |
| Insulation Colour | Brown or blue |
| Sheath Colour | Black, other colours can be offered upon request. |
| Maximum temperature range during operation (XLPE) | 90°C |
| Maximum short circuit temperature (5 Seconds) | 250°C |
| Minimum bending radius | |
| Circular copper conductor (OD≤25mm) | 4 x Overall Diameter |
| Circular copper conductor (OD>25mm) | 6 x Overall Diameter |
| Shaped copper conductor | 8 x Overall Diameter |
| Conductor | FLP600-RV-R | ||||
|---|---|---|---|---|---|
| No. of Cores × Cross Section | Class of Conductor | Nominal Insulation Thickness | Nominal Sheath Thickness | Nominal Overall Diameter | Approx.Weight |
| No.xmm² | mm | mm | mm | kg/km | |
| 1x1.5 | 2 | 0.7 | 1.4 | 6.1 | 36 |
| 1x2.5 | 2 | 0.7 | 1.4 | 6.8 | 52 |
| 1x4.0 | 2 | 0.7 | 1.4 | 7.4 | 76 |
| 1x6.0 | 2 | 0.7 | 1.4 | 8.2 | 100 |
| 1x10 | 2 | 0.7 | 1.4 | 9.2 | 160 |
| 1x16 | 2 | 0.7 | 1.4 | 10.7 | 230 |
| 1x25 | 2 | 0.9 | 1.4 | 12.5 | 340 |
| 1x35 | 2 | 0.9 | 1.4 | 13.5 | 440 |
| 1x50 | 2 | 1 | 1.4 | 13.7 | 541 |
| 1x70 | 2 | 1.1 | 1.4 | 15.8 | 749 |
| 1x95 | 2 | 1.1 | 1.5 | 17.5 | 1000 |
| 1x120 | 2 | 1.2 | 1.5 | 19.3 | 1241 |
| 1x150 | 2 | 1.4 | 1.6 | 21.5 | 1523 |
| 1x185 | 2 | 1.6 | 1.6 | 24.7 | 1942 |
| 1x240 | 2 | 1.7 | 1.7 | 27.7 | 2514 |
| 1x300 | 2 | 1.8 | 1.8 | 30.6 | 3125 |
| 1x400 | 2 | 2 | 1.9 | 34.2 | 3967 |
| 1x500 | 2 | 2.2 | 2 | 38 | 5063 |
| 1x630 | 2 | 2.4 | 2.2 | 42.9 | 6491 |
| 1x800 | 2 | 2.6 | 2.3 | 46 | 8075 |
| 1x1000 | 2 | 2.8 | 2.4 | 63 | 9860 |
| Conductor Operating Temperature | 70°C |
| Ambient Temperature | 30°C |
| Conductor cross-sectional area | Reference Method A (enclosed in conduit in thermally insulating wall etc) | Reference Method B (enclosed in conduit on a wall or in trunking etc) | Reference Method C (clipped direct) | Reference Method F (in free air or on a perforated cable tray horizontal or vertical etc) | Reference Method G (in free air) Spaced by one cable diameter | |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2 cables, single-phase a.c. or d.c. | 3 or 4 cables, three-phase a.c. | 2 cables, single-phase a.c. or d.c | 3 or 4 cables, three-phase a.c. | 2 cables, single-phase a.c. or d.c. flat and touching | 3 or 4 cables, three-phase a.c. flat and touching or trefoil | 2 cables, single-phase a.c. or d.c. flat | 3 cables, three-phase a.c. flat | 3 cables, three-phase a.c. trefoil | 2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat | |||
| Horizontal | Vertical | |||||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | |
| mm² | A | A | A | A | A | A | A | A | A | A | A | |
| 1.5 | 19 | 17 | 23 | 20 | 25 | 23 | - | - | - | - | - | |
| 2.5 | 26 | 23 | 31 | 28 | 34 | 31 | - | - | - | - | - | |
| 4 | 35 | 31 | 42 | 37 | 46 | 41 | - | - | - | - | - | |
| 6 | 45 | 40 | 54 | 48 | 59 | 54 | - | - | - | - | - | |
| 10 | 61 | 54 | 75 | 66 | 81 | 74 | - | - | - | - | - | |
| 16 | 81 | 73 | 100 | 88 | 109 | 99 | - | - | - | - | - | |
| 25 | 106 | 95 | 133 | 117 | 143 | 130 | 161 | 141 | 135 | 182 | 161 | |
| 35 | 131 | 117 | 164 | 144 | 176 | 161 | 200 | 176 | 169 | 226 | 201 | |
| 50 | 158 | 141 | 198 | 175 | 228 | 209 | 242 | 216 | 207 | 275 | 246 | |
| 70 | 200 | 179 | 253 | 222 | 293 | 268 | 310 | 279 | 268 | 353 | 318 | |
| 95 | 241 | 216 | 306 | 269 | 355 | 326 | 377 | 342 | 328 | 430 | 389 | |
| 120 | 278 | 249 | 354 | 312 | 413 | 379 | 437 | 400 | 383 | 500 | 454 | |
| 150 | 318 | 285 | 393 | 342 | 476 | 436 | 504 | 464 | 444 | 577 | 527 | |
| 185 | 362 | 324 | 449 | 384 | 545 | 500 | 575 | 533 | 510 | 661 | 605 | |
| 240 | 424 | 380 | 528 | 450 | 644 | 590 | 679 | 634 | 607 | 781 | 719 | |
| 300 | 486 | 435 | 603 | 514 | 743 | 681 | 783 | 736 | 703 | 902 | 833 | |
| 400 | - | - | 683 | 584 | 868 | 793 | 940 | 868 | 823 | 1085 | 1008 | |
| 500 | - | - | 783 | 666 | 990 | 904 | 1083 | 998 | 946 | 1253 | 1169 | |
| 630 | - | - | 900 | 764 | 113 | 1033 | 1254 | 1151 | 1088 | 1454 | 1362 | |
| 800 | - | - | - | - | 1288 | 1179 | 1358 | 1275 | 1214 | 1581 | 1485 | |
| 1000 | - | - | - | - | 1443 | 1323 | 1520 | 1436 | 1349 | 1775 | 1671 | |
| Nomina Cross Section Area | 2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Ref. Methods A and B (enclosed in conduit or trunking) | Ref. Methods C, F & G(clipped direct, on trays or in free air) | Ref. Methods A & B (enclosed in conduit or trunking | Ref. Methods C, F & G (clipped direct, on trays or in free air) | ||||||||||||||||
| 1 | 2 | 3 | Cables touching 4 | Cables spaced* 5 | 6 | 7 | |||||||||||||
| mm² | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | |||||||||||||
| 1.5 | 31 | 31 | 27 | 27 | 27 | 27 | |||||||||||||
| 2.5 | 19 | 19 | 16 | 16 | 16 | 16 | |||||||||||||
| 4 | 33 | 12 | 10 | 10 | 10 | 10 | |||||||||||||
| 6 | 7.8 | 7.9 | 6.8 | 6.8 | 6.8 | 6.8 | |||||||||||||
| 10 | 4.7 | 4.7 | 4.7 | 4 | 4 | 4 | |||||||||||||
| 16 | 2.9 | 2.9 | 2.9 | 2.5 | 2.5 | 2.5 | |||||||||||||
| r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | |||||
| 25 | 1.85 | 1.6 | 0.31 | 1.9 | 1.85 | 0.19 | 1.85 | 1.6 | 0.27 | 1.65 | 1.6 | 0.165 | 1.6 | 1.6 | 0.19 | 1.6 | |||
| 35 | 1.35 | 1.35 | 0.29 | 1.35 | 1.35 | 0.18 | 1.35 | 1.15 | 0.25 | 1.15 | 1.15 | 0.155 | 1.5 | 1.15 | 0.18 | 1.15 | |||
| 50 | 0.99 | 1 | 0.29 | 1.05 | 0.99 | 0.18 | 1 | 0.87 | 0.25 | 0.9 | 0.86 | 0.155 | 0.87 | 0.86 | 0.18 | 0.87 | |||
| 70 | 0.68 | 0.7 | 0.28 | 0.75 | 0.68 | 0.175 | 0.71 | 0.6 | 0.24 | 0.65 | 0.59 | 0.15 | 0.61 | 0.59 | 0.175 | 0.62 | |||
| 95 | 0.49 | 0.51 | 0.27 | 0.58 | 0.49 | 0.17 | 0.52 | 0.44 | 0.23 | 0.5 | 0.43 | 0.145 | 0.45 | 0.43 | 0.17 | 0.46 | |||
| 120 | 0.39 | 0.41 | 0.26 | 0.48 | 0.39 | 0.165 | 0.43 | 0.35 | 0.23 | 0.42 | 0.34 | 0.14 | 0.37 | 0.34 | 0.165 | 0.38 | |||
| 150 | 0.32 | 0.33 | 0.26 | 0.43 | 0.32 | 0.165 | 0.36 | 0.29 | 0.23 | 0.37 | 0.28 | 0.14 | 0.31 | 0.28 | 0.165 | 0.32 | |||
| 185 | 0.25 | 0.27 | 0.26 | 0.37 | 0.26 | 0.165 | 0.3 | 0.23 | 0.23 | 0.32 | 0.22 | 0.14 | 0.26 | 0.22 | 0.165 | 0.28 | |||
| 240 | 0.19 | 0.21 | 0.26 | 0.33 | 0.2 | 0.16 | 0.25 | 0.185 | 0.22 | 0.29 | 0.17 | 0.14 | 0.22 | 0.17 | 0.165 | 0.24 | |||
| 300 | 0.155 | 0.175 | 0.25 | 0.31 | 0.16 | 0.16 | 0.22 | 0.15 | 0.22 | 0.27 | 0.14 | 0.14 | 0.195 | 0.135 | 0.16 | 0.21 | |||
| 400 | 0.12 | 0.14 | 0.25 | 0.29 | 0.13 | 0.155 | 0.2 | 0.125 | 0.22 | 0.25 | 0.11 | 0.135 | 0.175 | 0.11 | 0.16 | 0.195 | |||
| 500 | 0.093 | 0.12 | 0.25 | 0.28 | 0.105 | 0.155 | 0.185 | 0.1 | 0.22 | 0.24 | 0.09 | 0.135 | 0.16 | 0.088 | 0.16 | 0.18 | |||
| 630 | 0.072 | 0.1 | 0.25 | 0.27 | 0.086 | 0.155 | 0.175 | 0.088 | 0.21 | 0.23 | 0.074 | 0.135 | 0.15 | 0.071 | 0.16 | 0.17 | |||
| 800 | 0.056 | - | - | - | 0.072 | 0.15 | 0.17 | - | - | - | 0.062 | 0.13 | 0.145 | 0.059 | 0.155 | 0.165 | |||
| 1000 | 0.045 | - | - | - | 0.063 | 0.15 | 0.165 | - | - | - | 0.055 | 0.13 | 0.14 | 0.05 | 0.155 | 0.165 | |||
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance
KEY FEATURES
- Manufactured according to BS7889 requirements
- 600/1000V voltage rating
- Single core cable construction
- XLPE insulated conductor
- PVC outer sheath
- Unarmoured power cable design
- Suitable for fixed low voltage power distribution
- Suitable for industrial and commercial installations
- Suitable for cable tray, conduit and protected cable routes
- Commonly used where armouring is not required
SELECTION NOTES
Before quotation, please confirm:
- Voltage rating
- Conductor size
- Conductor material
- Cable length
- Sheath colour
- Installation method
- Whether armouring is required
- Required standard or project specification
- Packing requirement
- Destination port or delivery address
600/1000V single core XLPE insulated PVC sheathed unarmoured cable is commonly selected for fixed low voltage power distribution where mechanical armouring is not required.
For direct burial or areas with higher mechanical risk, an armoured cable construction should be considered.
RELATED CABLE TYPES
- BS7889 unarmoured power cable
- Multi-core XLPE PVC unarmoured cable
- BS5467 armoured power cable
- BS6724 LSZH armoured cable
- IEC 60502 low voltage cable
- XLPE PVC power cable
- XLPE SWA PVC cable
- 6181Y cable
- 6381Y cable
- Low voltage power cable
FAQ
What is this single core XLPE PVC unarmoured cable used for?
This cable is used for fixed low voltage power distribution.
It is suitable for industrial plants, commercial buildings, electrical cabinets and protected cable routes.
What standard does this cable follow?
This cable is designed according to BS7889 requirements.
Is this cable armoured?
No. This is an unarmoured cable.
It should be used where mechanical armouring is not required or where protection is provided by the installation method.
Can this cable be directly buried?
Direct burial is not recommended unless suitable mechanical protection is provided.
For direct burial applications, an armoured cable such as XLPE/SWA/PVC is usually more suitable.
Can BURYCABLE supply single core BS7889 XLPE PVC unarmoured cable?
Yes. BURYCABLE can supply single core BS7889 XLPE insulated PVC sheathed unarmoured cables according to project voltage, conductor size, length and packing requirements.