300/500V SR Insulated, LSZH Sheathed, Screened Power Cables to BS 7629-1 (2-4 Cores & Multcore)
APPLICATIONThe cables are primarily intended for use in the following applications:BS 5266-1 for emergency lighting of premises.BS 5839-1 for fire detection and fire alarm systems in and around building.BS 5839-8 for voice alarm systems.BS 5839-9 for …
300_500V SR Insulated, LSZH Sheathed,Screened Power Cables to BS 7629-1 (2-4 Cores & Multcore).pdf Contact us

APPLICATION

The FRP300-SOZ1-U/R Series Fire-Resistant Cable is a safety-type cable that complies with high international standards, specifically designed for scenarios with stringent requirements for circuit reliability, fire resistance performance, and environmental adaptability. From building emergency systems to industrial critical equipment, and from metro tunnels to petrochemical facilities, this cable, with its excellent fire integrity, low-smoke and halogen-free characteristics, and ability to withstand complex environments, provides full-cycle protection for circuit safety.

STANDARDS

Basic design to BS 7629-1:2015

FIRE PERFORMANCE

Circuit IntegrityBS 6387; BS EN50200
Flame Retardance (single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen freeIEC 60754-1; EN 50267-2-1
No corrosive Gas emissionIEC 60754-2; EN 50267-2-2
Minimum smoke emissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

Conductor : Copper conductor according to BS EN 60228 class 1/2.

Insulation : Fire resistant special ceramized silicone rubber compound type EI 2 as per BS EN 50363-1.

Screened : One or more metallic or laminated metallic tape(s) shall be applied, either longitudinally or helically or a combination of both, with the metallic element in contact with the uninsulated circuit protective conductor or drain wire.

Circuit Protective Conductor : Uninsulated tinned copper conductor of the same section and class as the insulated conductors in the two,three and four cores cables.

Sheath : Extruded LSZH type LTS 3 according to BS 7655-6.1.

Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Insulation Colour :

Number of coresCore colours or numbering
2 cores+uninsulated circuit protective conductorBrown, Blue or Brown, Brown
3 cores+uninsulated circuit protective conductorBrown, Black, Grey
4 cores+uninsulated circuit protective conductorBrown, Blue, Black, Grey
7, 12 and19 cores+uninsulated drain wireNumbers 1, 2, 3, 4, 5, 6, 7 and upwards or, for identification by colour, an identical colour(excluding brown and black),except for two adjacent cores in each layer distinctively coloured brown and black.

Sheath Colour : Colours upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 60°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius : 6 x Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFRP300-SOZ1-U/R PH30/PH60
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessCPC Nominal Cross-sectional AreaNominal Sheath ThicknessApprox. Overall DiameterApprox. Weight
no.×mm² mmmm²mmmmkg/km
2 cores
2x1.01/20.61.00.98.078
2x1.51/20.71.50.98.5103
2x2.51/20.82.51.010.5150
2x4.01/20.84.01.112.5212
3 cores
3x1.51/20.71.50.99.5130
3x2.51/20.82.51.011.5191
3x4.01/20.84.01.113.5273
4 cores
4x1.51/20.71.51.010.5165
4x2.51/20.82.51.112.0242
4x4.01/20.84.01.215.0344
7 cores
7x1.51/20.70.51.112.5257
7x2.51/20.80.51.215.0568
12 cores
12x1.51/20.70.51.216.0414
12x2.51/20.80.51.420.0886
19 cores
19x1.51/20.70.51.319.0617

ELECTRICAL PROPERTIES

Conductor operating temperature : 70°C

Ambient temperature : 30°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4D2A

Conductor cross-sectional areaRef. Method A (enclosed in conduit in thermally insulating wall etc)Ref. Method B (enclosed in conduit on a wall or in trunking etc)Ref. Method C (clipped direct)Ref. Method E (in free air or on a perforated cable tray etc. horizontal or vertical)
1 two-core cable*, single-phase a.c. or d.c.1 three-core or 1 four-core cable*, three-phase a.c.1 two-core cable*, singlephase a.c. or d.c.1 three-core or 1 four-core cable*, three-phase a.c.1 two-core cable*, single-phase a.c. or d.c.1 three-core or 1 four-core cable*, three-phase a.c.1 two-core cable*, single-phase a.c. or d.c.1 three-core or 1 four-core cable*, three-phase a.c.
123456789
mm²AAAAAAAA
1.011101311.51513.51714.5
1.5141316.51519.517.52218.5
2.518.517.5232027243025
42523302736324034

Note: *With or without a protective conductor.

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4D2B

Conductor cross-sectional areaTwo-core cable d.c.Two-core cable single-phase a.c.Three- or four-core cable, three-phase a.c.
1234
mm²mV/A/mmV/A/mmV/A/m
1.0444438
1.5292925
2.5181815
411119.5