For RS485 data circuits specifying a fire resistant cable construction. Mica glass tape forms an overall fire barrier around the cabled assembly, while an LSZH sheath encloses the selected screening arrangement. Four construction families support different pair counts and signal termination layouts.
Basic design adapted to EIA/TIA 485
| Circuit Integrity | IEC 60331-23; BS 6387 CWZ (Optional) |
|---|---|
| Flame Retardance (Single Vertical Wire or cable test) | IEC 60332-1-2; EN 60332-1-2 |
| Reduced Fire Propagation (Vertically-mounted bundled wires & cables test) | IEC 60332-3-24; EN 60332-3-24 |
| Halogen Free | IEC 60754-1; EN 50267-2-1 |
| No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2 |
| Minimum Smoke Emission | IEC 61034-2; EN 61034-2 |
| Conductor | Tinned copper wire, stranded according to IEC 60228 class 2 or class5. |
| Insulation | Foam PE or foam skin PE+SR. |
| Cabling Elements | Insulated cores are twisted to form pairs with varying lay length to minimize crosstalk. Two pair cable had four cores laid in quad formation. |
| Cabling | Pairs are cabled together in concentric layers. |
| Overall Fire Barrier | Mica glass tape. |
| Overall Screen | Aluminum/polyester tape with tinned copper drain wire. |
| Outer Sheath | Halogen-free flame retardant thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered). |
| Outer Sheath Option | UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option. |
| Conductor | Tinned copper wire, stranded according to IEC 60228 class 2 or class5. |
| Insulation | Foam PE or foam skin PE. |
| Cabling Elements | Insulated cores are twisted to form pairs with varying lay length to minimize crosstalk. Two pair cable had four cores laid in quad formation. |
| Cabling | Pairs are cabled together in concentric layers. |
| Overall Fire Barrier | Mica glass tape. |
| Overall Screen | Aluminium/polyester tape+copper wire braid. |
| Outer Sheath | Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered). |
| Outer Sheath Option | UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option. |
| Conductor | Tinned copper wire, stranded according to IEC 60228 class 2 or class5. |
| Insulation | Foam PE or foam skin PE. |
| Cabling Elements | Insulated cores are twisted to form pairs with varying lay length to minimize crosstalk. Two pair cable had four cores laid in quad formation. |
| Cabling | Pairs are cabled together in concentric layers. |
| Individual Screen | Individual aluminium/polyester tape. |
| Overall Fire Barrier | Mica glass tape. |
| Overall Screen | Copper wire braid. |
| Outer Sheath | Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered). |
| Outer Sheath Option | UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option. |
| Conductor | Tinned copper wire, stranded according to IEC 60228 class 2 or class5. |
| Insulation | Foam PE or foam skin PE. |
| Cabling Elements | Insulated cores are twisted to form pairs with varying lay length to minimize crosstalk. Two pair cable had four cores laid in quad formation. |
| Cabling | Pairs are cabled together in concentric layers. |
| Overall Fire Barrier | Mica glass tape. |
| Overall Screen | Copper wire braid. |
| Outer Sheath | Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered). |
| Outer Sheath Option | UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option. |
| Temperature range during operation (fixed state) | -20°C - +90°C |
| Temperature range during installation (mobile state) | -5°C - +60°C |
| Minimum bending radius | 8 x Overall Diameter |
| Dielectric test | 1000 V r.m.s. for 5’ (core-core) |
|---|---|
| 1000 V r.m.s. for 5’ (core-screen) | |
| Impedance | 120Ω |
| Capacitance | 45 nF/km conductor to conductor |
| 90 nF/km conductor to shield |
| No.of Pair | Nominal Cross Sectional Area | No./Nominal Diameter of Strands | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx.Weight |
|---|---|---|---|---|---|---|
| No. | mm² | no/mm | mm | mm | mm | kg/km |
| 1 | 0.22 | 7/0.2 | 1.2 | 1.1 | 6.6 | 73 |
| 2 | 0.22 | 7/0.2 | 1.2 | 1.1 | 10.9 | 136 |
| 4 | 0.22 | 7/0.2 | 1.2 | 1.1 | 12.6 | 214 |
| 1 | 0.50 | 16/0.2 | 1.2 | 1.1 | 7.2 | 88 |
| 2 | 0.50 | 16/0.2 | 1.2 | 1.1 | 12.0 | 165 |
| 4 | 0.50 | 16/0.2 | 1.2 | 1.1 | 14.0 | 266 |
| 1 | 0.75 | 24/0.2 | 1.2 | 1.1 | 7.6 | 100 |
| 2 | 0.75 | 24/0.2 | 1.2 | 1.1 | 12.8 | 189 |
| 4 | 0.75 | 24/0.2 | 1.2 | 1.1 | 15.0 | 309 |
| 1 | 1.00 | 32/0.2 | 1.2 | 1.1 | 7.8 | 106 |
| 2 | 1.00 | 32/0.2 | 1.2 | 1.1 | 13.1 | 199 |
| 4 | 1.00 | 32/0.2 | 1.2 | 1.1 | 15.3 | 328 |
| No.of Pair | Nominal Cross Sectional Area | No./Nominal Diameter of Strands | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx.Weight |
|---|---|---|---|---|---|---|
| No. | mm² | no/mm | mm | mm | mm | kg/km |
| 1 | 0.22 | 7/0.2 | 1.2 | 1.1 | 7.1 | 91 |
| 2 | 0.22 | 7/0.2 | 1.2 | 1.1 | 11.4 | 168 |
| 4 | 0.22 | 7/0.2 | 1.2 | 1.1 | 13.1 | 252 |
| 1 | 0.50 | 16/0.2 | 1.2 | 1.1 | 7.7 | 108 |
| 2 | 0.50 | 16/0.2 | 1.2 | 1.1 | 12.5 | 201 |
| 4 | 0.50 | 16/0.2 | 1.2 | 1.1 | 14.5 | 308 |
| 1 | 0.75 | 24/0.2 | 1.2 | 1.1 | 8.1 | 121 |
| 2 | 0.75 | 24/0.2 | 1.2 | 1.1 | 13.3 | 228 |
| 4 | 0.75 | 24/0.2 | 1.2 | 1.1 | 15.5 | 355 |
| 1 | 1.00 | 32/0.2 | 1.2 | 1.1 | 8.8 | 128 |
| 2 | 1.00 | 32/0.2 | 1.2 | 1.1 | 13.6 | 238 |
| 4 | 1.00 | 32/0.2 | 1.2 | 1.1 | 15.8 | 375 |
| No.of Pair | Nominal Cross Sectional Area | No./Nominal Diameter of Strands | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx.Weight |
|---|---|---|---|---|---|---|
| No. | mm² | no/mm | mm | mm | mm | kg/km |
| 1 | 0.22 | 7/0.2 | 1.2 | 1.1 | 7.4 | 94 |
| 2 | 0.22 | 7/0.2 | 1.2 | 1.1 | 12.1 | 176 |
| 4 | 0.22 | 7/0.2 | 1.2 | 1.1 | 14.0 | 266 |
| 1 | 0.50 | 16/0.2 | 1.2 | 1.1 | 8.0 | 111 |
| 2 | 0.50 | 16/0.2 | 1.2 | 1.1 | 13.3 | 210 |
| 4 | 0.50 | 16/0.2 | 1.2 | 1.1 | 15.5 | 325 |
| 1 | 0.75 | 24/0.2 | 1.2 | 1.1 | 8.4 | 125 |
| 2 | 0.75 | 24/0.2 | 1.2 | 1.1 | 14.2 | 237 |
| 4 | 0.75 | 24/0.2 | 1.2 | 1.1 | 16.6 | 372 |
| 1 | 1.00 | 32/0.2 | 1.2 | 1.1 | 8.6 | 131 |
| 2 | 1.00 | 32/0.2 | 1.2 | 1.1 | 14.5 | 248 |
| 4 | 1.00 | 32/0.2 | 1.2 | 1.1 | 17.0 | 393 |
| No.of Pair | Nominal Cross Sectional Area | No./Nominal Diameter of Strands | Nominal Insulation Thickness | Nominal Sheath Thickness | Approx. Overall Diameter | Approx.Weight |
|---|---|---|---|---|---|---|
| No. | mm² | no/mm | mm | mm | mm | kg/km |
| 1 | 0.22 | 7/0.2 | 1.2 | 1.1 | 6.9 | 86 |
| 2 | 0.22 | 7/0.2 | 1.2 | 1.1 | 11.2 | 160 |
| 4 | 0.22 | 7/0.2 | 1.2 | 1.1 | 13.0 | 243 |
| 1 | 0.50 | 16/0.2 | 1.2 | 1.1 | 7.5 | 123 |
| 2 | 0.50 | 16/0.2 | 1.2 | 1.1 | 12.3 | 193 |
| 4 | 0.50 | 16/0.2 | 1.2 | 1.1 | 14.3 | 299 |
| 1 | 0.75 | 24/0.2 | 1.2 | 1.1 | 7.9 | 116 |
| 2 | 0.75 | 24/0.2 | 1.2 | 1.1 | 13.1 | 219 |
| 4 | 0.75 | 24/0.2 | 1.2 | 1.1 | 15.3 | 344 |
| 1 | 1.00 | 32/0.2 | 1.2 | 1.1 | 8.0 | 122 |
| 2 | 1.00 | 32/0.2 | 1.2 | 1.1 | 13.4 | 229 |
| 4 | 1.00 | 32/0.2 | 1.2 | 1.1 | 15.6 | 364 |
Overall mica glass tape fire barrier.
120 ohm impedance and four foil or braid screening constructions.
Choose screening construction, pair count and conductor area. Specify the required fire performance option with the cable design; BS 6387 CWZ is listed as optional.
BRAIL MVB RS485 Databus Cable, 300/500V, 120 Ohm, EVA Sheathed
FRL MVB RS485 Databus Cable, 300/500V, 120 Ohm, EVA Sheathed
An overall mica glass tape barrier surrounds the cabled pair assembly.
The listed cable impedance is 120 ohms.
Overall foil; overall foil plus braid; individual pair foil with overall braid; and overall copper braid.
The tables list 1, 2 and 4 pairs in 0.22, 0.50, 0.75 and 1.00 mm² sizes.
The standard sheath is thermoplastic LSZH; thermosetting LSZH is offered as an option.