RE-2X(St)H PiMF XLPE LSZH Instrumentation Cable
RE-2X(St)H PiMF XLPE insulated multipair instrumentation cable with individual and overall foil screens, LSZH sheath. For fixed industrial instrument and control connections.
RE-2X(St)H PIMF.pdf Contact us

APPLICATION

BURY CABLE RE-2X(St)H PiMF multipair cable connects instruments and control equipment in industrial process facilities. Copper conductors with XLPE insulation, individual and overall aluminium/polyester screens and an unarmoured LSZH outer sheath support fixed signal wiring. Use protected indoor routes, including suitable wet or damp locations. Individually screened pairs keep each signal circuit organised within the common cable assembly. The LSZH sheath suits projects specifying low smoke and halogen free materials.

Standards

Basic design to EN 50288-7

Fire Performance

Flame Retardance (Single Vertical Wire Test)EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation(Vertically-mounted bundled wires & cable test)EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen FreeIEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke EmissionIEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gasesNES 02-713; NF C 20-454
Sunlight ResistanceUL 1581 section 1200
Oil ResistanceICEA S-73-532**

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation, *** denotes optional.

Voltage Rating

300/500V

Cable Construction

Conductor : Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

Insulation : Extruded cross-linked XLPE compound, EN 50290. 2-29.

Pairs : Two insulated conductors uniformly twisted together with a lay not exceeding 100mm

Individual Screen : Aluminium/polyester tape is applied over each pair metallic side down in contact with tinned copper drain wire, 0.5mm2

Binder tape : PETP transparent tape

Overall Screen : Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm2

Outer Sheath : Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655 2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.

Colour Code

Insulation : Black / White, continuously numbered on white core(1, 2..)for multipair.

Outer Sheath : Black or blue for intrinsically safe systems

Physical and Thermal Properties

Temperature Range During Operation (Fixed State) : -30°C – +90°C

Temperature Range During Installation (Mobile State) : -5°C – +50°C

Minimum Bending Radius : 7.5 X Overall Diameter

Electrical Roperties

Conductor Area Sizemm²0.50.751.01.31.5
Insulation thickness (nominal)mm0.40.40.40.450.45
Conductor resistance (20°C)Ω/km36.72518.514.212.3
Insulation resistance (20°C)MΩ.km(Min.)5000
Mutual Capacitance (1 kHz)pF/m(Max.)115
InductancemH/km (Max.)1
L / R (ratio) (max.)μH/Ω2525254040
Operating voltage UrmsV300
Test VoltageCore to CoreV1500
Core to ScreenV1500

Construction Parameterst

Caledonian Cable CodeRE-2X(St)H PiMF
No. of Pairs ×2×Cross SectionNominal Insulation ThicknessNominal Outer Sheath ThicknessNominal Overall DiameterApprox. Weight
No.×2×mm²mmmmmmkg/km
0.5mm2, Multipair
RE-2X(St)H PiMF 2P0.52x2x0.50.350.98.785
RE-2X(St)H PiMF 4P0.54x2x0.50.351.010.2120
RE-2X(St)H PiMF 5P0.55x2x0.50.351.011.2145
RE-2X(St)H PiMF 6P0.56x2x0.50.351.012.1170
RE-2X(St)H PiMF 8P0.58x2x0.50.351.113.1214
RE-2X(St)H PiMF 10P0.510x2x0.50.351.215.1265
RE-2X(St)H PiMF 12P0.512x2x0.50.351.215.7286
RE-2X(St)H PiMF 16P0.516x2x0.50.351.217.8380
RE-2X(St)H PiMF 20P0.520x2x0.50.351.319.7475
RE-2X(St)H PiMF 24P0.524x2x0.50.351.421.5561
0.75mm2, Multipair
RE-2X(St)H PiMF 2P0.752x2x0.750.381.09.7101
RE-2X(St)H PiMF 4P0.753x2x0.750.381.011.2159
RE-2X(St)H PiMF 5P0.754x2x0.750.381.112.5183
RE-2X(St)H PiMF 6P0.755x2x0.750.381.113.6215
RE-2X(St)H PiMF 8P0.758x2x0.750.381.114.4272
RE-2X(St)H PiMF 10P0.7510x2x0.750.381.216.6333
RE-2X(St)H PiMF 12P0.7512x2x0.750.381.217.4383
RE-2X(St)H PiMF 16P0.7516x2x0.750.381.319.8492
RE-2X(St)H PiMF 20P0.7520x2x0.750.381.422.0603
RE-2X(St)H PiMF 24P0.7524x2x0.750.381.524.0704
1.0mm2, Multipair
RE-2X(St)H PiMF 2P1.02x2x1.00.41.010.4112
RE-2X(St)H PiMF 4P1.03x2x1.00.41.012.1179
RE-2X(St)H PiMF 5P1.04x2x1.00.41.113.5220
RE-2X(St)H PiMF 6P1.05x2x1.00.41.114.7256
RE-2X(St)H PiMF 8P1.08x2x1.00.41.215.8323
RE-2X(St)H PiMF 10P1.010x2x1.00.41.218.0401
RE-2X(St)H PiMF 12P1.012x2x1.00.41.319.0454
RE-2X(St)H PiMF 16P1.016x2x1.00.41.321.5601
RE-2X(St)H PiMF 20P1.020x2x1.00.41.423.9719
RE-2X(St)H PiMF 24P1.024x2x1.00.41.526.1884
1.3mm2, Multipair
RE-2X(St)H PiMF 2P1.32x2x1.30.451.011.4153
RE-2X(St)H PiMF 4P1.33x2x1.30.451.113.4208
RE-2X(St)H PiMF 5P1.34x2x1.30.451.114.8263
RE-2X(St)H PiMF 6P1.35x2x1.30.451.216.3318
RE-2X(St)H PiMF 8P1.38x2x1.30.451.317.6406
RE-2X(St)H PiMF 10P1.310x2x1.30.451.320.0501
RE-2X(St)H PiMF 12P1.312x2x1.30.451.421.1552
RE-2X(St)H PiMF 16P1.316x2x1.30.451.524.1728
RE-2X(St)H PiMF 20P1.320x2x1.30.451.626.8892
RE-2X(St)H PiMF 24P1.324x2x1.30.451.729.21067
1.5mm2, Multipair
RE-2X(St)H PiMF 2P1.52x2x1.50.451.011.8164
RE-2X(St)H PiMF 4P1.53x2x1.50.451.113.9235
RE-2X(St)H PiMF 5P1.54x2x1.50.451.215.5289
RE-2X(St)H PiMF 6P1.55x2x1.50.451.216.9366
RE-2X(St)H PiMF 8P1.58x2x1.50.451.318.2446
RE-2X(St)H PiMF 10P1.510x2x1.50.451.421.0565
RE-2X(St)H PiMF 12P1.512x2x1.50.451.421.9637
RE-2X(St)H PiMF 16P1.516x2x1.50.451.525.1828
RE-2X(St)H PiMF 20P1.520x2x1.50.451.627.81024
RE-2X(St)H PiMF 24P1.524x2x1.50.451.730.41219



KEY FEATURES

  • XLPE insulation with individually screened twisted pairs and an overall foil screen.

  • Unarmoured construction with an LTS3 LSZH outer sheath; thermosetting sheath options are listed in the technical description.

  • Electrical and construction tables cover 0.5-1.5 mm² conductor sections, with original dimensions and weights retained.

SELECTION NOTES

  • Specify pair count, conductor size and construction, circuit voltage, cable length and termination arrangement.

  • Coordinate screen bonding and mechanical route protection with the installation design. Use a minimum bending radius of 7.5 times overall diameter.

  • Choose black or blue sheath identification for the specified system. Blue identification is coordinated with the complete intrinsically safe circuit design; environmental sheath options form part of the order specification.

RELATED CABLE TYPES

FAQ

What is RE-2X(St)H PiMF cable used for?

It connects instruments and control equipment on fixed industrial signal routes using a multipair copper cable with XLPE insulation and an LSZH sheath.

How are the conductors arranged?

Two insulated conductors form each twisted pair, with numbered white cores supporting pair identification.

Which screening construction is used?

PiMF construction uses individual pair screens together with an overall aluminium/polyester screen and tinned copper drain wires.

What does the LSZH sheath provide?

The low smoke zero halogen sheath is selected where reduced smoke and corrosive combustion gases are part of the installation specification.

How is the cable selected for installation?

Match the pair count, conductor cross-section, circuit voltage and route conditions. Include cable length, screen termination, sheath colour and packing in the order.