RE-2X(St)H 300V XLPE LSZH Multipair Instrumentation Cable
RE-2X(St)H 300V XLPE insulated multipair instrumentation cable with an overall foil screen, LSZH sheath. For fixed industrial instrument and control connections.
RE-2X(St)H Multi-Pair.pdf Contact us

APPLICATION

BURY CABLE RE-2X(St)H multipair cable connects instruments and control equipment in industrial process facilities. Copper conductors with XLPE insulation, an overall aluminium/polyester screen and an unarmoured LSZH outer sheath support fixed signal wiring. Use protected indoor routes, including suitable wet or damp locations. Twisted pairs group the signal circuits beneath a common foil screen. The LSZH sheath suits projects specifying low smoke and halogen free materials.

Standards

Basic design to EN 50288-7

Fire Performance

Flame Retardance (Single Vertical Wire Test)EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*
Reduced Fire Propagation(Vertically-mounted bundled wires & cable test)EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4
Halogen FreeIEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1*
No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2*
Minimum Smoke EmissionIEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*
No Toxic gasesNES 02-713; NF C 20-454
Sunlight ResistanceUL 1581 section 1200
Oil ResistanceICEA S-73-532**

Note: Asterisk * denotes superseded standard, ** denotes Test temperature +60°C, duration 4h. Retention: min 60% of tensile strength/min.60% of elongation, *** denotes optional.

Voltage Rating

300V

Cable Construction

Conductor : Annealed copper solid or plain copper stranded to IEC 60228 Class 2.

Insulation : Extruded cross-linked XLPE compound, EN 50290. 2-29.

Pairs : Two insulated conductors uniformly twisted together with a lay not exceeding 100mm

Binder tape : PETP transparent tape

Overall Screen : Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²

Outer Sheath : Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH compound type SW2-SW4 as per BS 7655-2.6 can be offered.). UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option.

Colour Code

Insulation : Black / White, continuously numbered on white core(1, 2..)for multipair.

Outer Sheath : Black or blue for intrinsically safe systems

Physical and Thermal Properties

Temperature Range During Operation (Fixed State) : -30°C – +90°C

Temperature Range During Installation (Mobile State) : -5°C – +50°C

Minimum Bending Radius : 7.5 × Overall Diameter

Electrical Roperties

Conductor Area Sizemm²0.50.751.01.31.5
Insulation thickness (nominal)mm0.350.380.40.450.45
Conductor resistance (20°C)Ω/km36.72518.514.212.3
Insulation resistance (20°C)MΩ.km(Min.)5000
Mutual Capacitance (1 kHz)pF/m(Max.)

≤ 4 pairs909090102102

all other pairs7575758585
Capacitance unbalance(1 kHz)pF/500 m (Max.)500
InductancemH/km (Max.)1
L / R (ratio) (max.)μH/Ω2525254040
Operating voltage UrmsV300
Test VoltageCore to CoreV1500
Core to ScreenV1500

Construction Parameterst

Caledonian Cable CodeRE-2X(St)H
No. of Pairs × 2 × Cross SectionNominal Insulation ThicknessNominal Outer Sheath ThicknessNominal Overall DiameterApprox. Weight
No. × 2 × mm²mmmmmmkg/km
0.5mm², Multipair
RE-2X(St)H 2P0.52x2x0.50.350.97.666
RE-2X(St)H 4P0.54x2x0.50.350.98.898
RE-2X(St)H 5P0.55x2x0.50.351.09.8112
RE-2X(St)H 6P0.56x2x0.50.351.010.6133
RE-2X(St)H 8P0.58x2x0.50.351.011.3161
RE-2X(St)H 10P0.510x2x0.50.351.112.9200
RE-2X(St)H 12P0.512x2x0.50.351.113.5242
RE-2X(St)H 16P0.516x2x0.50.351.115.2288
RE-2X(St)H 20P0.520x2x0.50.351.216.9376
RE-2X(St)H 24P0.524x2x0.50.351.218.3426
0.75mm², Multipair
RE-2X(St)H 2P0.752x2x0.750.380.98.587
RE-2X(St)H 4P0.753x2x0.750.381.010.0122
RE-2X(St)H 5P0.754x2x0.750.381.010.9154
RE-2X(St)H 6P0.755x2x0.750.381.011.8174
RE-2X(St)H 8P0.758x2x0.750.381.112.8213
RE-2X(St)H 10P0.7510x2x0.750.381.114.5266
RE-2X(St)H 12P0.7512x2x0.750.381.115.1304
RE-2X(St)H 16P0.7516x2x0.750.381.217.3398
RE-2X(St)H 20P0.7520x2x0.750.381.319.2478
RE-2X(St)H 24P0.7524x2x0.750.381.320.8559
1.0mm², Multipair
RE-2X(St)H 2P1.02x2x1.00.40.99.2101
RE-2X(St)H 4P1.03x2x1.00.41.010.9157
RE-2X(St)H 5P1.04x2x1.00.41.011.9194
RE-2X(St)H 6P1.05x2x1.00.41.013.0223
RE-2X(St)H 8P1.08x2x1.00.41.114.0272
RE-2X(St)H 10P1.010x2x1.00.41.115.9334
RE-2X(St)H 12P1.012x2x1.00.41.216.8390
RE-2X(St)H 16P1.016x2x1.00.41.219.0511
RE-2X(St)H 20P1.020x2x1.00.41.321.1617
RE-2X(St)H 24P1.024x2x1.00.41.423.1749
1.3mm², Multipair
RE-2X(St)H 2P1.32x2x1.30.451.010.4124
RE-2X(St)H 4P1.33x2x1.30.451.012.0184
RE-2X(St)H 5P1.34x2x1.30.451.113.4226
RE-2X(St)H 6P1.35x2x1.30.451.114.6289
RE-2X(St)H 8P1.38x2x1.30.451.215.7337
RE-2X(St)H 10P1.310x2x1.30.451.217.9411
RE-2X(St)H 12P1.312x2x1.30.451.318.9495
RE-2X(St)H 16P1.316x2x1.30.451.321.4651
RE-2X(St)H 20P1.320x2x1.30.451.423.8772
RE-2X(St)H 24P1.324x2x1.30.451.525.9933
1.5mm², Multipair
RE-2X(St)H 2P1.52x2x1.50.451.010.8139*
RE-2X(St)H 4P1.53x2x1.50.451.112.7214
RE-2X(St)H 5P1.54x2x1.50.451.114.0259
RE-2X(St)H 6P1.55x2x1.50.451.215.2305
RE-2X(St)H 8P1.58x2x1.50.451.216.4385
RE-2X(St)H 10P1.510x2x1.50.451.318.8460
RE-2X(St)H 12P1.512x2x1.50.451.319.7558
RE-2X(St)H 16P1.516x2x1.50.451.422.5725
RE-2X(St)H 20P1.520x2x1.50.451.525.0881
RE-2X(St)H 24P1.524x2x1.50.451.527.1147



KEY FEATURES

  • XLPE insulation with twisted pairs and an overall foil screen.

  • Unarmoured construction with an LTS3 LSZH outer sheath; thermosetting sheath options are listed in the technical description.

  • Electrical and construction tables cover 0.5-1.5 mm² conductor sections, with original dimensions and weights retained.

SELECTION NOTES

  • Specify pair count, conductor size and construction, circuit voltage, cable length and termination arrangement.

  • Coordinate screen bonding and mechanical route protection with the installation design. Use a minimum bending radius of 7.5 times overall diameter.

  • Choose black or blue sheath identification for the specified system. Blue identification is coordinated with the complete intrinsically safe circuit design; environmental sheath options form part of the order specification.

RELATED CABLE TYPES

FAQ

What is RE-2X(St)H cable used for?

It connects instruments and control equipment on fixed industrial signal routes using a multipair copper cable with XLPE insulation and an LSZH sheath.

How are the conductors arranged?

Two insulated conductors form each twisted pair, with numbered white cores supporting pair identification.

Which screening construction is used?

An aluminium/polyester foil screen surrounds the complete core assembly, with a tinned copper drain wire for screen connection.

What does the LSZH sheath provide?

The low smoke zero halogen sheath is selected where reduced smoke and corrosive combustion gases are part of the installation specification.

How is the cable selected for installation?

Match the pair count, conductor cross-section, circuit voltage and route conditions. Include cable length, screen termination, sheath colour and packing in the order.