600/1000V single core XLPE insulated
PVC sheathed armoured cable is designed
for fixed low voltage power distribution.
It is suitable for industrial plants,
commercial buildings, power stations,
substations and infrastructure projects.
The XLPE insulation provides reliable
electrical performance and thermal stability.
The PVC outer sheath provides general
protection against moisture, abrasion
and normal installation conditions.
The armoured construction provides improved
mechanical protection.
It is suitable for underground cable routes,
cable trenches, cable ducts
and outdoor installation.
For single core armoured cable,
the armour type should be selected
according to project requirements.
The cable should be selected according to
voltage rating, conductor size,
conductor material, armour type,
installation method and project specification.
The product strictly adheres to the IEC 60502-1 international standard for fundamental design and manufacturing.
| Flame Retardance (Single Vertical Wire Test) | IEC 60332-1 |
600/1000V
| Conductor | Annealed copper wire, stranded according to IEC 60228 class 2. |
| Insulation | XLPE according to IEC 60502-1. |
| Inner Covering | Extruded PVC or polymeric compound. |
| Armouring | Aluminium wire |
| Outer Sheath | Extruded PVC Type ST1/ST2 according to IEC 60502-1. |
| Outer Sheath Option | UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request. |
| Insulation Colour | Brown or blue, other colours can be offered upon request. |
| Sheath Colour | Black, other colours can be offered upon request. |
| Maximum temperature range during operation | 80°C (For ST1 Sheath); 90°C (For ST2 Sheath) |
| Maximum short circuit temperature (5 Seconds) | 250°C |
| Minimum bending radius | |
| Circular copper conductors | 6 x Overall Diameter |
| Shaped copper conductors | 8 x Overall Diameter |
| Conductor | FLP600-RVMAV-R | ||||||
|---|---|---|---|---|---|---|---|
| No. of Cores × Cross Section | Class of Conductor | Nominal Insulation Thickness | Nominal Inner Covering Thickness | Nominal Armour Wire Diameter | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight |
| No.xmm² | mm | mm | mm | mm | mm | kg/km | |
| 1x1.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 10.2 | 150 |
| 1x2.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 10.6 | 169 |
| 1x4.0 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 11.2 | 196 |
| 1x6.0 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 11.7 | 228 |
| 1x10 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 12.7 | 290 |
| 1x16 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 13.7 | 372 |
| 1x25 | 2 | 0.9 | 1.0 | 0.8 | 1.8 | 15.4 | 507 |
| 1x35 | 2 | 0.9 | 1.0 | 1.25 | 1.8 | 17.5 | 681 |
| 1x50 | 2 | 1.0 | 1.0 | 1.25 | 1.8 | 19.0 | 848 |
| 1x70 | 2 | 1.1 | 1.0 | 1.25 | 1.8 | 21.0 | 1116 |
| 1x95 | 2 | 1.1 | 1.0 | 1.6 | 1.8 | 24.0 | 1511 |
| 1x120 | 2 | 1.2 | 1.0 | 1.6 | 1.8 | 25.8 | 1821 |
| 1x150 | 2 | 1.4 | 1.0 | 1.6 | 1.8 | 27.8 | 2165 |
| 1x185 | 2 | 1.6 | 1.0 | 1.6 | 1.8 | 30.4 | 2655 |
| 1x240 | 2 | 1.7 | 1.0 | 1.6 | 1.9 | 33.5 | 3352 |
| 1x300 | 2 | 1.8 | 1.0 | 2.0 | 2.0 | 37.5 | 4224 |
| 1x400 | 2 | 2.0 | 1.2 | 2.0 | 2.2 | 41.3 | 5263 |
| 1x500 | 2 | 2.2 | 1.2 | 2.0 | 2.3 | 44.2 | 7379 |
| 1x630 | 2 | 2.4 | 1.2 | 2.5 | 2.4 | 49.8 | 9611 |
| 1x800 | 2 | 2.6 | 1.4 | 2.5 | 2.6 | 55.3 | 11896 |
| 1x1000 | 2 | 2.8 | 1.4 | 2.5 | 2.7 | 60.4 | 14467 |
| Conductor Operating Temperature | 90°C |
| Ambient Temperature | 30°C |
| Conductor cross-sectional area | Reference Method C (clipped direct) | Reference Method F (in free air or on a perforated cable tray, horizontal or vertical) | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Touching | Touching | Spaced by on cable diameter | |||||||||
| 2 cables, single-phase a.c. or d.c. flat | 3 or 4 cables, threep-hase a.c. flat | 2 cables, single-phase a.c. or d.c. flat | 3 or 4 cables, three-phase a.c. flat | 3 cables threep-hase a.c. trefoil | 2 cables, d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | ||||
| Horizontal | Vertical | Horizontal | Vertical | Horizontal | Vertical | ||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
| mm2 | A | A | A | A | A | A | A | A | A | A | A |
| 50 | 237 | 220 | 253 | 232 | 222 | 284 | 270 | 282 | 266 | 288 | 266 |
| 70 | 303 | 277 | 322 | 293 | 285 | 356 | 349 | 357 | 337 | 358 | 331 |
| 95 | 367 | 333 | 389 | 352 | 346 | 446 | 426 | 436 | 412 | 425 | 393 |
| 120 | 425 | 383 | 449 | 405 | 402 | 519 | 497 | 504 | 477 | 485 | 449 |
| 150 | 488 | 437 | 516 | 462 | 463 | 600 | 575 | 566 | 539 | 549 | 510 |
| 185 | 557 | 496 | 587 | 524 | 529 | 688 | 660 | 643 | 614 | 618 | 574 |
| 240 | 656 | 579 | 689 | 612 | 625 | 815 | 782 | 749 | 714 | 715 | 666 |
| 300 | 755 | 662 | 792 | 700 | 720 | 943 | 906 | 842 | 805 | 810 | 755 |
| 400 | 853 | 717 | 899 | 767 | 815 | 1137 | 1094 | 929 | 889 | 848 | 797 |
| 500 | 962 | 791 | 1016 | 851 | 918 | 1314 | 1266 | 1032 | 989 | 923 | 871 |
| 630 | 1082 | 861 | 1146 | 935 | 1027 | 1528 | 1474 | 1139 | 1092 | 992 | 940 |
| 800 | 1170 | 904 | 1246 | 987 | 1119 | 1809 | 1744 | 1204 | 1155 | 1042 | 978 |
| 1000 | 1261 | 961 | 1345 | 1055 | 1214 | 2100 | 2026 | 1289 | 1238 | 1110 | 1041 |
| Nominal Cross Section Area | 2 cables d.c. | Ref. Methods C&F(clipped direct, on trays or in free air) | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||||||||||||
| Touching | Spaced* | Trefoil and touching | Flat and touching | Flat and spaced* | ||||||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | ||||||||||
| mm2 | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | ||||||||||
| r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | ||
| 50 | 0.98 | 0.99 | 0.21 | 1.0 | 0.98 | 0.29 | 1.0 | 0.86 | 0.18 | 0.87 | 0.64 | 0.25 | 0.88 | 0.84 | 0.33 | 0.9 |
| 70 | 0.67 | 0.68 | 0.20 | 0.71 | 0.69 | 0.29 | 0.75 | 0.59 | 0.170 | 0.62 | 0.60 | 0.25 | 0.65 | 0.62 | 0.32 | 0.70 |
| 95 | 0.49 | 0.51 | 0.195 | 0.55 | 0.53 | 0.28 | 0.60 | 0.44 | 0.170 | 0.47 | 0.46 | 0.24 | 0.52 | 0.49 | 0.31 | 0.58 |
| 120 | 0.39 | 0.41 | 0.190 | 0.45 | 0.43 | 0.27 | 0.51 | 0.35 | 0.165 | 0.39 | 0.38 | 0.24 | 0.44 | 0.41 | 0.30 | 0.51 |
| 150 | 0.31 | 0.33 | 0.185 | 0.38 | 0.36 | 0.27 | 0.45 | 0.29 | 0.160 | 0.33 | 0.31 | 0.23 | 0.39 | 0.34 | 0.29 | 0.45 |
| 185 | 0.25 | 0.27 | 0.185 | 0.33 | 0.30 | 0.26 | 0.40 | 0.23 | 0.160 | 0.28 | 0.26 | 0.23 | 0.34 | 0.29 | 0.29 | 0.41 |
| 240 | 0.195 | 0.21 | 0.180 | 0.28 | 0.24 | 0.26 | 0.35 | 0.180 | 0.155 | 0.24 | 0.21 | 0.22 | 0.30 | 0.24 | 0.28 | 0.37 |
| 300 | 0.155 | 0.17 | 0.175 | 0.25 | 0.195 | 0.25 | 0.32 | 0.145 | 0.150 | 0.21 | 0.170 | 0.22 | 0.28 | 0.20 | 0.27 | 0.34 |
| 400 | 0.115 | 0.145 | 0.170 | 0.22 | 0.180 | 0.24 | 0.30 | 0.125 | 0.150 | 0.195 | 0.160 | 0.21 | 0.27 | 0.20 | 0.27 | 0.33 |
| 500 | 0.093 | 0.125 | 0.170 | 0.21 | 0.165 | 0.24 | 0.29 | 0.105 | 0.145 | 0.180 | 0.145 | 0.20 | 0.25 | 0.190 | 0.24 | 0.31 |
| 630 | 0.073 | 0.105 | 0.165 | 0.195 | 0.150 | 0.23 | 0.27 | 0.092 | 0.145 | 0.170 | 0.135 | 0.195 | 0.24 | 0.175 | 0.23 | 0.29 |
| 800 | 0.056 | 0.090 | 0.160 | 0.190 | 0.145 | 0.23 | 0.27 | 0.086 | 0.140 | 0.165 | 0.130 | 0.180 | 0.23 | 0.175 | 0.195 | 0.26 |
| 1000 | 0.045 | 0.092 | 0.155 | 0.180 | 0.140 | 0.21 | 0.25 | 0.080 | 0.135 | 0.155 | 0.125 | 0.170 | 0.21 | 0.165 | 0.180 | 0.24 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance
KEY FEATURES
- Manufactured according to IEC 60502-1 requirements
- 600/1000V voltage rating
- Single core power cable construction
- XLPE insulated conductor
- PVC outer sheath
- Armoured cable design
- Suitable for fixed low voltage power distribution
- Suitable for underground and outdoor installation
- Suitable for industrial and infrastructure projects
- Provides improved mechanical protection
SELECTION NOTES
Before quotation, please confirm:
- Voltage rating
- Conductor size
- Conductor material
- Armour type
- Cable length
- Sheath colour
- Installation method
- Installation environment
- Required standard or project specification
- Packing requirement
- Destination port or delivery address
600/1000V single core XLPE armoured cable
is commonly selected for low voltage
power distribution where mechanical
protection is required.
It is suitable for underground cable routes,
outdoor installation and infrastructure
power systems.
RELATED CABLE TYPES
- IEC 60502 low voltage cable
- XLPE insulated PVC sheathed cable
- Single core XLPE armoured cable
- Multi-core XLPE armoured cable
- XLPE unarmoured power cable
- PVC armoured power cable
- BS5467 armoured power cable
- BS6724 LSZH armoured cable
- 600/1000V power cable
- Low voltage power cable
FAQ
What is this cable used for?
It is used for fixed low voltage
power distribution.
It is suitable for industrial plants,
commercial buildings, underground routes
and infrastructure projects.
What standard does this cable follow?
This cable is designed according to
IEC 60502-1 requirements.
Is this cable armoured?
Yes. This is an armoured cable.
The armour provides improved
mechanical protection.
Can this cable be used underground?
Yes. It can be used for underground
cable routes and cable trenches.
The final installation should follow
project specifications and local
installation requirements.
What is the difference between XLPE
and PVC insulation?
XLPE insulation provides higher
thermal performance.
PVC insulation is commonly used for
general low voltage applications.
What information is required for quotation?
Please confirm voltage rating,
conductor size, conductor material,
armour type and cable length.
Installation method and destination port
are also required.
Can BURYCABLE supply IEC 60502
single core XLPE armoured cable?
Yes. BURYCABLE can supply IEC 60502-1
single core XLPE insulated PVC sheathed
armoured cables.
We can support different conductor sizes,
armour types, sheath colours, lengths
and packing requirements.