600/1000V multi-core XLPE insulated
LSZH sheathed armoured cable is designed
for fixed low voltage power distribution.
It is suitable for industrial plants,
commercial buildings, public buildings,
transport systems and infrastructure projects.
The XLPE insulation provides reliable
electrical performance and thermal stability.
The LSZH sheath helps reduce smoke emission
and corrosive gas release in the event of fire.
The armoured construction provides improved
mechanical protection.
It is suitable for cable trays, cable ducts,
underground cable routes, tunnels
and protected outdoor installation.
It is commonly used where low smoke
zero halogen performance is required.
The cable should be selected according to
voltage rating, number of cores,
conductor size, armour type,
fire performance requirement
and project specification.
The product is designed and manufactured in accordance with the International Electrotechnical Commission (IEC) 60502-1 standard, guaranteeing exceptional quality and universal applicability.
| Flame Retardance (Single vertical wire or cable test) | IEC 60332-1-2; EN 60332-1-2 |
| Reduced Fire Propagation (Vertically-mounted bundled wires & cables test) | IEC 60332-3-24; EN 60332-3-24 |
| Halogen Free | IEC 60754-1; EN 50267-2-1 |
| No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2 |
| Minimum Smoke Emission | IEC 61034-2; EN 61034-2 |
600/1000V
Conductor : The conductors shall be class 2 plain or metal-coated annealed copper in accordance with IEC 60228. Class 1 and class 5 conductor can be offered as option.
Insulation : Thermosetting XLPE material and thickness shall be as per IEC 60502-1.
Inner Covering : Thermoplastic halogen free compound ST8 as per IEC 60502-1.
Armouring : Steel wire armour.
Outer Sheath : Thermoplastic halogen free compound ST8 as per IEC 60502-1.
Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.
| Insulation Colour | 2-core | Brown and blue. |
| 3-core | Brown, black and grey. | |
| 4-core | Blue, brown black and grey. | |
| 5-core | Green and yellow, blue, brown black, grey. | |
| Other colours can be offered upon request. | ||
| Sheath Colour | Black; other colours can be offered upon request. | |
Maximum temperature range during operation : 90°C
Maximum short circuit temperature (5 Seconds) : 250°C
Minimum bending radius :
circular copper conductors : 6 × Overall Diameter
shaped copper conductors : 8 × Overall Diameter
| Conductor | FLP600-RZ1MZ1-R | |||||||
|---|---|---|---|---|---|---|---|---|
| No. of Cores × Cross-sectional Area | Conductor Class | Nominal Insulation Thickness | Nominal Inner Covering Thickness | Nominal Armour Wire Diameter | Nominal Sheath Thickness | Approx. Overall Diameter | Approx. Weight | |
| No.×mm² | mm | mm | mm | mm | mm | kg/km | ||
| 2 cores | ||||||||
| 2×1.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 13.2 | 325 | |
| 2×2.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 14.0 | 372 | |
| 2×4 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 15.1 | 438 | |
| 2×6 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 17.1 | 645 | |
| 2×10 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 19.0 | 806 | |
| 2×16 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 21.1 | 1015 | |
| 2×25 | 2 | 0.9 | 1.0 | 1.6 | 1.8 | 25.2 | 1517 | |
| 2×35 | 2 | 0.9 | 1.0 | 1.6 | 1.8 | 27.5 | 1830 | |
| 2×50 | 2 | 1.0 | 1.0 | 1.6 | 1.9 | 30.8 | 2259 | |
| 2×70 | 2 | 1.1 | 1.0 | 2.0 | 2.0 | 35.8 | 3182 | |
| 2×95 | 2 | 1.1 | 1.2 | 2.0 | 2.1 | 40.2 | 4022 | |
| 2×120 | 2 | 1.2 | 1.2 | 2.0 | 2.3 | 44.2 | 4810 | |
| 2×150 | 2 | 1.4 | 1.2 | 2.5 | 2.4 | 49.3 | 6120 | |
| 2×185 | 2 | 1.6 | 1.4 | 2.5 | 2.6 | 54.7 | 7375 | |
| 2×240 | 2 | 1.7 | 1.4 | 2.5 | 2.7 | 60.5 | 9037 | |
| 2×300 | 2 | 1.8 | 1.6 | 2.5 | 2.9 | 66.6 | 10871 | |
| 2×400 | 2 | 2.0 | 1.6 | 2.5 | 3.1 | 73.7 | 13256 | |
| 3 cores | ||||||||
| 3×1.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 13.6 | 368 | |
| 3×2.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 14.5 | 427 | |
| 3×4 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 15.7 | 514 | |
| 3×6 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 17.8 | 752 | |
| 3×10 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 19.8 | 965 | |
| 3×16 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 22.1 | 1244 | |
| 3×25 | 2 | 0.9 | 1.0 | 1.6 | 1.8 | 26.5 | 1872 | |
| 3×35 | 2 | 0.9 | 1.0 | 1.6 | 1.8 | 29.0 | 2298 | |
| 3×50 | 2 | 1.0 | 1.0 | 1.6 | 1.9 | 32.5 | 2876 | |
| 3×70 | 2 | 1.1 | 1.0 | 2.0 | 2.1 | 38.0 | 4081 | |
| 3×95 | 2 | 1.1 | 1.2 | 2.0 | 2.2 | 42.7 | 5227 | |
| 3×120 | 2 | 1.2 | 1.2 | 2.0 | 2.3 | 46.8 | 6283 | |
| 3×150 | 2 | 1.4 | 1.4 | 2.5 | 2.5 | 52.8 | 8045 | |
| 3×185 | 2 | 1.6 | 1.4 | 2.5 | 2.7 | 58.1 | 9678 | |
| 3×240 | 2 | 1.7 | 1.4 | 2.5 | 2.8 | 64.3 | 11998 | |
| 3×300 | 2 | 1.8 | 1.6 | 2.5 | 3.0 | 70.8 | 14540 | |
| 3×400 | 2 | 2 | 1.6 | 3.15 | 3.3 | 80.0 | 18919 | |
| 3 cores + 1 core earth conductor | ||||||||
| 3 cores | 1 core | |||||||
| 3×16/10 | 2 | 0.7 | 0.7 | 1.0 | 1.6 | 1.8 | 23.5 | 1363 |
| 3×25/16 | 2 | 0.9 | 0.7 | 1.0 | 1.6 | 1.8 | 27.3 | 2054 |
| 3×35/16 | 2 | 0.9 | 0.7 | 1.0 | 1.6 | 1.9 | 30.1 | 2480 |
| 3×50/25 | 2 | 1.0 | 0.9 | 1.0 | 1.6 | 2.1 | 34.0 | 3167 |
| 3×70/35 | 2 | 1.1 | 0.9 | 1.2 | 2 | 2.2 | 39.9 | 4476 |
| 3×95/50 | 2 | 1.1 | 1.0 | 1.2 | 2 | 2.3 | 44.3 | 5757 |
| 3×120/70 | 2 | 1.2 | 1.1 | 1.2 | 2 | 2.5 | 48.8 | 7047 |
| 3×150/70 | 2 | 1.4 | 1.1 | 1.4 | 2.5 | 2.7 | 55.0 | 8812 |
| 3×185/95 | 2 | 1.6 | 1.1 | 1.4 | 2.5 | 2.8 | 60.4 | 10723 |
| 3×240/120 | 2 | 1.7 | 1.2 | 1.6 | 2.5 | 3.1 | 67.8 | 13326 |
| 3×300/150 | 2 | 1.8 | 1.4 | 1.6 | 2.5 | 3.2 | 73.8 | 16169 |
| 3×400/185 | 2 | 2.0 | 1.6 | 1.6 | 3.15 | 3.6 | 83.5 | 20955 |
| 4 cores | ||||||||
| 4×1.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 14.4 | 414 | |
| 4×2.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 15.4 | 487 | |
| 4×4 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 16.7 | 617 | |
| 4×6 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 19.0 | 870 | |
| 4×10 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 21.3 | 1136 | |
| 4×16 | 2 | 0.7 | 1.0 | 1.6 | 1.8 | 24.5 | 1642 | |
| 4×25 | 2 | 0.9 | 1.0 | 1.6 | 1.8 | 28.6 | 2254 | |
| 4×35 | 2 | 0.9 | 1.0 | 1.6 | 1.9 | 31.6 | 2814 | |
| 4×50 | 2 | 1.0 | 1.0 | 2.0 | 2.1 | 36.5 | 3837 | |
| 4×70 | 2 | 1.1 | 1.2 | 2.0 | 2.2 | 41.9 | 5096 | |
| 4×95 | 2 | 1.1 | 1.2 | 2.0 | 2.3 | 46.7 | 6499 | |
| 4×120 | 2 | 1.2 | 1.4 | 2.5 | 2.5 | 52.9 | 8446 | |
| 4×150 | 2 | 1.4 | 1.4 | 2.5 | 2.7 | 58.0 | 10039 | |
| 4×185 | 2 | 1.6 | 1.4 | 2.5 | 2.8 | 63.7 | 12099 | |
| 4×240 | 2 | 1.7 | 1.6 | 2.5 | 3.1 | 71.5 | 15261 | |
| 4×300 | 2 | 1.8 | 1.6 | 2.5 | 3.2 | 78.0 | 18400 | |
| 4×400 | 2 | 2.0 | 1.8 | 3.15 | 3.6 | 88.7 | 24037 | |
| 5 cores | ||||||||
| 5x1.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 14.8 | 481 | |
| 5×2.5 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 15.8 | 571 | |
| 5×4 | 2 | 0.7 | 1.0 | 0.8 | 1.8 | 17.2 | 702 | |
| 5×6 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 19.4 | 1020 | |
| 5×10 | 2 | 0.7 | 1.0 | 1.25 | 1.8 | 21.6 | 1345 | |
| 5×16 | 2 | 0.7 | 1.0 | 1.6 | 1.8 | 24.7 | 1944 | |
| 5×25 | 2 | 0.9 | 1.0 | 1.6 | 1.9 | 29.0 | 2810 | |
| 5×35 | 2 | 0.9 | 1.0 | 1.6 | 2.0 | 32.2 | 3398 | |
Conductor operating temperature : 90°C
Air ambient temperature : 30°C
Ground ambient temperature : 20°C
| Conductor cross-ectional area | Ref. Method C (clipped direct) | Ref. Method E (in free air or on a perforated cable tray etc. horizontal or vertical) | Ref. Method D (direct in in groud or in ducting in groud. in or around buildings) | |||
|---|---|---|---|---|---|---|
| 1 two-core cable, single-phase a.c. or d.c. | 1 three- or four-core cable, three-phase a.c. | 1 two-core cable, single-phase a.c. or d.c. | 1 three- or four-core cable, three-phase a.c. | 1 two-core cable, single-phase a.c. or d.c. | 1 three- or four-core cable, three-phase a.c. | |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 |
| mm² | A | A | A | A | A | A |
| 1.5 | 27 | 23 | 29 | 25 | 25 | 21 |
| 2.5 | 36 | 31 | 39 | 33 | 33 | 28 |
| 4 | 49 | 42 | 52 | 44 | 43 | 36 |
| 6 | 62 | 53 | 66 | 56 | 53 | 44 |
| 10 | 85 | 73 | 90 | 78 | 71 | 58 |
| 16 | 110 | 94 | 115 | 99 | 91 | 75 |
| 25 | 146 | 124 | 152 | 131 | 116 | 96 |
| 35 | 180 | 154 | 188 | 162 | 139 | 115 |
| 50 | 219 | 187 | 228 | 197 | 164 | 135 |
| 70 | 279 | 238 | 291 | 251 | 203 | 167 |
| 95 | 338 | 289 | 354 | 304 | 239 | 197 |
| 120 | 392 | 335 | 410 | 353 | 271 | 223 |
| 150 | 451 | 386 | 472 | 406 | 306 | 251 |
| 185 | 515 | 441 | 539 | 463 | 343 | 281 |
| 240 | 607 | 520 | 636 | 546 | 395 | 324 |
| 300 | 698 | 599 | 732 | 628 | 446 | 365 |
| 400 | 787 | 673 | 847 | 728 | - | - |
| Conductor cross-sectional area | Two-core cable, d.c. | Two-core cable, single-phase a.c. | Three- or four-core cable, three-phase a.c. | ||||
|---|---|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | ||||
| mm² | mV/A/m | mV/A/m | mV/A/m | ||||
| 1.5 | 31 | 31 | 27 | ||||
| 2.5 | 19 | 19 | 16 | ||||
| 4 | 12 | 12 | 10 | ||||
| 6 | 7.9 | 7.9 | 6.8 | ||||
| 10 | 4.7 | 4.7 | 4.0 | ||||
| 16 | 2.9 | 2.9 | 2.5 | ||||
| r | x | z | r | x | z | ||
| 25 | 1.85 | 1.85 | 0.160 | 1.90 | 1.60 | 0.140 | 1.65 |
| 35 | 1.35 | 1.35 | 0.155 | 1.35 | 1.15 | 0.135 | 1.15 |
| 50 | 0.98 | 0.99 | 0.155 | 1.00 | 0.86 | 0.135 | 0.87 |
| 70 | 0.67 | 0.67 | 0.150 | 0.69 | 0.59 | 0.130 | 0.60 |
| 95 | 0.49 | 0.50 | 0.150 | 0.52 | 0.43 | 0.130 | 0.45 |
| 120 | 0.39 | 0.40 | 0.145 | 0.42 | 0.34 | 0.130 | 0.37 |
| 150 | 0.31 | 0.32 | 0.145 | 0.35 | 0.38 | 0.125 | 0.30 |
| 185 | 0.25 | 0.26 | 0.145 | 0.29 | 0.22 | 0.125 | 0.26 |
| 240 | 0.195 | 0.200 | 0.140 | 0.24 | 0.175 | 0.125 | 0.21 |
| 300 | 0.155 | 0.160 | 0.140 | 0.21 | 0.140 | 0.120 | 0.185 |
| 400 | 0.120 | 0.130 | 0.140 | 0.190 | 0.115 | 0.120 | 0.165 |
Note :
r = conductor resistance at operating temperature
x = reactance
z = impedance
KEY FEATURES
- Manufactured according to IEC 60502-1 requirements
- 600/1000V voltage rating
- Multi-core power cable construction
- XLPE insulated conductors
- LSZH / LSOH outer sheath
- Armoured cable design
- Low smoke zero halogen sheath performance
- Suitable for fixed low voltage power distribution
- Suitable for public buildings and transport systems
- Provides improved mechanical protection
SELECTION NOTES
Before quotation, please confirm:
- Voltage rating
- Number of cores
- Conductor size
- Conductor material
- Armour type
- Cable length
- Sheath colour
- Fire performance requirement
- Installation method
- Installation environment
- Required standard or project specification
- Packing requirement
- Destination port or delivery address
600/1000V multi-core XLPE LSZH armoured cable
is commonly selected for projects requiring
mechanical protection and LSZH performance.
It is suitable for infrastructure projects,
public buildings, transport systems,
industrial plants and protected cable routes.
RELATED CABLE TYPES
- IEC 60502 low voltage cable
- XLPE insulated LSZH sheathed cable
- XLPE LSZH armoured cable
- XLPE LSZH unarmoured cable
- XLPE PVC armoured cable
- PVC armoured power cable
- BS6724 LSZH armoured cable
- BS5467 armoured power cable
- 600/1000V power cable
- Low voltage power cable
FAQ
What is this cable used for?
It is used for fixed low voltage
power distribution.
It is suitable for public buildings,
transport systems, industrial plants
and infrastructure projects.
What standard does this cable follow?
This cable is designed according to
IEC 60502-1 requirements.
Is this cable armoured?
Yes. This is an armoured cable.
The armour provides improved
mechanical protection.
What does LSZH mean?
LSZH means Low Smoke Zero Halogen.
The sheath helps reduce smoke emission
and corrosive gas release during fire.
Can this cable be used underground?
Yes. It can be used for underground
cable routes and cable trenches.
The final installation should follow
project specifications and local
installation requirements.
What is the difference between LSZH
and PVC sheath?
LSZH sheath provides better low smoke
and halogen-free performance.
PVC sheath is commonly used for
general low voltage applications.
What information is required for quotation?
Please confirm voltage rating,
number of cores, conductor size,
armour type and cable length.
Fire performance requirement and
destination port are also required.
Can BURYCABLE supply IEC 60502
XLPE LSZH armoured cable?
Yes. BURYCABLE can supply IEC 60502-1
multi-core XLPE insulated LSZH sheathed
armoured cables.
We can support different core numbers,
conductor sizes, armour types,
sheath colours and packing requirements.