whatsapp
backtop
600/1000V Multi-Core PVC Insulated PVC Sheathed Armoured Cable to IEC 60502-1
600/1000V multi-core PVC insulated and PVC sheathed armoured cable to IEC 60502-1 is designed for low voltage power distribution, underground installation, industrial plants and infrastructure projects.
600_1000V PVC Insulated, PVC Sheathed, Armoured PowerCables to IEC 60502 (2-4 Cores).pdf Contact us

APPLICATION

600/1000V multi-core PVC insulated PVC sheathed armoured cable is designed for fixed low voltage power distribution.


It is suitable for industrial plants, commercial buildings, power stations, substations and infrastructure projects.


The PVC insulation provides reliable electrical insulation for low voltage power circuits.


The PVC outer sheath provides general protection against moisture, abrasion and normal installation conditions.


The armoured construction provides improved mechanical protection.


It is suitable for underground cable routes, cable trenches, cable ducts and outdoor installation.


Typical applications include power distribution systems, plant rooms, industrial facilities and protected low voltage installations.


The cable should be selected according to voltage rating, number of cores, conductor size, armour type, installation method and project specification.




STANDARDS

Basic design adapted to IEC 60502-1

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)IEC 60332-1-2

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

ConductorAnnealed copper wire, stranded according to IEC 60228 class 2.
InsulationPVC/A according to IEC 60502-1.
Inner CoveringExtruded PVC or polymeric compound.
ArmouringGalvanized steel wire
Outer SheathExtruded PVC Type ST1/ST2 according to IEC 60502-1.
Outer Sheath OptionUV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE

Insulation ColourTwo-core: Brown, blue
Three-core: Brown, black, grey
Four-core: Blue, brown, black, grey
Five-core: Green-and-yellow, blue, brown, black, grey
Other colours can be offered upon request.
Sheath ColourBlack, other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation (PVC)70°C
Maximum short circuit temperature (5 Seconds)160°C(≤300 mm²); 140°C(>300 mm²)
Minimum bending radius
Circular copper conductors6 x Overall Diameter
Shaped copper conductors8 x Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFLP600-VVMV-R
No. of Cores x Cross SectionClass of ConductorNominal Insulation
Thickness
Nominal Inner Covering
Thickness
Armour Wire DiameterNominal Sheath ThicknessNominal Overall
Diameter
Approx. Weight
No.xmm2 mmmmmmmmmmkg/km
2 Cores
2x2.520.81.00.81.814.0380
2x4.021.01.01.251.816.7604
2x6.021.01.01.251.817.7689
2x1021.01.01.251.819.3841
2x1621.01.01.251.821.11037
2x2521.21.01.61.824.81513
2x3521.21.01.61.827.01843
2x5021.41.01.61.930.72356
2x7021.41.02.02.134.53179
2x9521.61.22.02.239.24042
2x12021.61.22.02.342.24764
2x15021.81.22.52.547.26095
2x18522.01.42.52.651.67207
2x24022.21.42.52.857.28861
2x30022.41.62.53.062.810608
2x40022.61.62.53.270.313385
3 Cores
3x2.520.81.00.81.814.5432
3x4.021.01.01.251.817.4689
3x6.021.01.01.251.818.4800
3x1021.01.01.251.820.21001
3x1621.01.01.61.822.81405
3x2521.21.01.61.826.01860
3x3521.21.01.61.928.52325
3x5021.41.02.02.033.33266
3x7021.41.22.02.137.04108
3x9521.61.22.02.341.65245
3x12021.61.22.52.445.96677
3x15021.81.42.52.650.48016
3x18522.01.42.52.754.89466
3x24022.21.52.52.961.211805
3x30022.41.62.53.166.814181
3x40022.81.63.153.476.719235
3x50022.81.83.153.783.623011
3 Cores+1 Earth Conductor
3x10/621.01.01.01.251.821.91140
3x16/1021.01.01.01.61.824.21633
3x25/1621.21.01.01.61.827.92145
3x35/1621.21.01.01.61.930.82659
3x50/2521.41.21.02.02.036.43739
3x70/3521.41.21.22.02.140.14720
3x95/5021.61.41.22.52.346.36398
3x120/7021.61.41.42.52.450.37746
3x150/7021.81.41.42.52.655.09128
3x185/9522.01.61.42.52.760.310916
3x240/12022.21.61.62.52.967.013713
3x300/15022.41.81.63.153.174.617403
3x400/18522.62.01.83.153.484.120704
3x500/24022.82.22.03.153.791.825817
4 Cores
4x4.021.01.01.251.818.5792
4x6.021.01.01.251.819.7931
4x1021.01.01.251.822.31185
4x1621.01.01.61.824.51672
4x2521.21.01.61.928.22260
4x3521.21.01.62.031.12854
4x5021.41.02.02.136.74013
4x7021.41.22.02.340.45104
4x9521.61.22.52.546.66996
4x12021.61.42.52.650.68400
4x15021.81.42.52.755.310008
4x18522.01.42.52.960.611906
4x24022.21.62.53.167.314963
4x30022.41.63.153.474.918944
4x40022.61.83.153.784.424304
4x50022.82.03.153.992.129351

Note: Other conductor sizes & core confi gurations are available upon request.

ELECTRICAL PROPERTIES

Conductor Operating Temperature70°C
Ambient Temperature30°C

Current-Carrying Capacities (Amp) according to BS 7671: 2008 table 4D4A

Conductor crosssectional
area
Reference Method C (clipped direct)Reference Method E (in free air or
on a perforated cable tray, horizontal
or vertical)
Reference Method D (direct in in
groud or in ducting in groud. in or
around buildings)
1 two-core cable,
single-phase a.c.
or d.c.
1 three-or four
core cable,
three-phase a.c.
1 two-core
cable, singlephase
a.c. or
d.c.
1 three-or four
core cable,
three-phase a.c.
1 two-core cable,
single-phase a.c.
or d.c.
1 three-or four
core cable, threephase
a.c.
1234567
mm2AAAAAA
1.5211822192218
2.5282531262924
4.0383341353730
6.0494253454638
10675872626050
16897797837864
251181021281109982
3514512515713511998
50175151190163140116
70222192241207173143
95269231291251204169
120310267336290231192
150356306386332261217
185405348439378292243
240476409516445336280
300547469592510379316
400621540683590--

Voltage Drop (Per Amp Per Meter) according to BS 7671: 2008 table 4D4B

Nominal Cross Section  AreaTwo-core cables d.c.Two-core cable, single-phase a.c.Three- or four-core cable, three-phase a.c.
1234
mm2mV/A/mmV/A/mmV/A/m
1.5292925
2.5181815
4.011119.5
6.07.37.36.4
104.44.43.8
162.82.82.4


rxzrxz
251.751.750.1701.751.500.1451.50
351.251.250.1651.251.100.1451.10
500.930.930.1650.940.800.1400.81
700.630.630.1600.650.550.1400.57
950.460.470.1550.500.410.1350.43
1200.360.380.1550.410.330.1350.35
1500.290.300.1550.340.260.1300.29
1850.230.250.1500.290.210.1300.25
2400.1800.1900.1500.240.1650.1300.21
3000.1450.1550.1450.210.1350.1300.185
4000.1050.1150.1450.1850.1000.1250.160

Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance

KEY FEATURES


- Manufactured according to IEC 60502-1 requirements

- 600/1000V voltage rating

- Multi-core power cable construction

- PVC insulated conductors

- PVC outer sheath

- Armoured cable design

- Suitable for fixed low voltage power distribution

- Suitable for underground and outdoor installation

- Suitable for industrial and infrastructure projects

- Provides improved mechanical protection



SELECTION NOTES


Before quotation, please confirm:


- Voltage rating

- Number of cores

- Conductor size

- Conductor material

- Armour type

- Cable length

- Sheath colour

- Installation method

- Installation environment

- Required standard or project specification

- Packing requirement

- Destination port or delivery address


600/1000V PVC insulated PVC sheathed armoured cable is commonly selected for low voltage power distribution where mechanical protection is required.


It is suitable for underground cable routes, industrial plants, outdoor installation and infrastructure power systems.



RELATED CABLE TYPES


- IEC 60502 low voltage cable

- PVC insulated PVC sheathed armoured cable

- XLPE insulated PVC sheathed armoured cable

- XLPE PVC armoured cable

- XLPE PVC unarmoured cable

- BS5467 armoured power cable

- BS6724 LSZH armoured cable

- 600/1000V power cable

- Low voltage power cable

- Underground power cable



FAQ


What is this 600/1000V PVC armoured cable used for?


It is used for fixed low voltage power distribution.


It is suitable for industrial plants, commercial buildings, infrastructure projects, underground cable routes and outdoor installations.



What standard does this cable follow?


This cable is designed according to IEC 60502-1 requirements.



Is this cable armoured?


Yes. This cable has an armoured construction.


The armour provides improved mechanical protection.



Can this cable be used underground?


Yes. It can be used for underground cable routes and cable trenches.


The final installation should follow project specifications and local installation requirements.



What is the difference between PVC insulated cable and XLPE insulated cable?


This cable uses PVC insulation.


XLPE insulated cable normally offers higher thermal performance.


The final choice depends on the project requirement.



What information is required for quotation?


Please confirm voltage rating, number of cores, conductor size, armour type and cable length.


Destination port or delivery address is also required.



Can BURYCABLE supply IEC 60502 PVC armoured power cable?


Yes. BURYCABLE can supply IEC 60502-1 PVC insulated PVC sheathed armoured cables.


We can support different core numbers, conductor sizes, armour types, lengths and packing requirements.