600/1000V multi-core PVC insulated PVC sheathed armoured cable is designed for fixed low voltage power distribution.
It is suitable for industrial plants, commercial buildings, power stations, substations and infrastructure projects.
The PVC insulation provides reliable electrical insulation for low voltage power circuits.
The PVC outer sheath provides general protection against moisture, abrasion and normal installation conditions.
The armoured construction provides improved mechanical protection.
It is suitable for underground cable routes, cable trenches, cable ducts and outdoor installation.
Typical applications include power distribution systems, plant rooms, industrial facilities and protected low voltage installations.
The cable should be selected according to voltage rating, number of cores, conductor size, armour type, installation method and project specification.
Basic design adapted to IEC 60502-1
| Flame Retardance (Single Vertical Wire Test) | IEC 60332-1-2 |
600/1000V
| Conductor | Annealed copper wire, stranded according to IEC 60228 class 2. |
| Insulation | PVC/A according to IEC 60502-1. |
| Inner Covering | Extruded PVC or polymeric compound. |
| Armouring | Galvanized steel wire |
| Outer Sheath | Extruded PVC Type ST1/ST2 according to IEC 60502-1. |
| Outer Sheath Option | UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request. |
| Insulation Colour | Two-core: Brown, blue Three-core: Brown, black, grey Four-core: Blue, brown, black, grey Five-core: Green-and-yellow, blue, brown, black, grey Other colours can be offered upon request. |
| Sheath Colour | Black, other colours can be offered upon request. |
| Maximum temperature range during operation (PVC) | 70°C |
| Maximum short circuit temperature (5 Seconds) | 160°C(≤300 mm²); 140°C(>300 mm²) |
| Minimum bending radius | |
| Circular copper conductors | 6 x Overall Diameter |
| Shaped copper conductors | 8 x Overall Diameter |
| Conductor | FLP600-VVMV-R | |||||||
|---|---|---|---|---|---|---|---|---|
| No. of Cores x Cross Section | Class of Conductor | Nominal Insulation Thickness | Nominal Inner Covering Thickness | Armour Wire Diameter | Nominal Sheath Thickness | Nominal Overall Diameter | Approx. Weight | |
| No.xmm2 | mm | mm | mm | mm | mm | kg/km | ||
| 2 Cores | ||||||||
| 2x2.5 | 2 | 0.8 | 1.0 | 0.8 | 1.8 | 14.0 | 380 | |
| 2x4.0 | 2 | 1.0 | 1.0 | 1.25 | 1.8 | 16.7 | 604 | |
| 2x6.0 | 2 | 1.0 | 1.0 | 1.25 | 1.8 | 17.7 | 689 | |
| 2x10 | 2 | 1.0 | 1.0 | 1.25 | 1.8 | 19.3 | 841 | |
| 2x16 | 2 | 1.0 | 1.0 | 1.25 | 1.8 | 21.1 | 1037 | |
| 2x25 | 2 | 1.2 | 1.0 | 1.6 | 1.8 | 24.8 | 1513 | |
| 2x35 | 2 | 1.2 | 1.0 | 1.6 | 1.8 | 27.0 | 1843 | |
| 2x50 | 2 | 1.4 | 1.0 | 1.6 | 1.9 | 30.7 | 2356 | |
| 2x70 | 2 | 1.4 | 1.0 | 2.0 | 2.1 | 34.5 | 3179 | |
| 2x95 | 2 | 1.6 | 1.2 | 2.0 | 2.2 | 39.2 | 4042 | |
| 2x120 | 2 | 1.6 | 1.2 | 2.0 | 2.3 | 42.2 | 4764 | |
| 2x150 | 2 | 1.8 | 1.2 | 2.5 | 2.5 | 47.2 | 6095 | |
| 2x185 | 2 | 2.0 | 1.4 | 2.5 | 2.6 | 51.6 | 7207 | |
| 2x240 | 2 | 2.2 | 1.4 | 2.5 | 2.8 | 57.2 | 8861 | |
| 2x300 | 2 | 2.4 | 1.6 | 2.5 | 3.0 | 62.8 | 10608 | |
| 2x400 | 2 | 2.6 | 1.6 | 2.5 | 3.2 | 70.3 | 13385 | |
| 3 Cores | ||||||||
| 3x2.5 | 2 | 0.8 | 1.0 | 0.8 | 1.8 | 14.5 | 432 | |
| 3x4.0 | 2 | 1.0 | 1.0 | 1.25 | 1.8 | 17.4 | 689 | |
| 3x6.0 | 2 | 1.0 | 1.0 | 1.25 | 1.8 | 18.4 | 800 | |
| 3x10 | 2 | 1.0 | 1.0 | 1.25 | 1.8 | 20.2 | 1001 | |
| 3x16 | 2 | 1.0 | 1.0 | 1.6 | 1.8 | 22.8 | 1405 | |
| 3x25 | 2 | 1.2 | 1.0 | 1.6 | 1.8 | 26.0 | 1860 | |
| 3x35 | 2 | 1.2 | 1.0 | 1.6 | 1.9 | 28.5 | 2325 | |
| 3x50 | 2 | 1.4 | 1.0 | 2.0 | 2.0 | 33.3 | 3266 | |
| 3x70 | 2 | 1.4 | 1.2 | 2.0 | 2.1 | 37.0 | 4108 | |
| 3x95 | 2 | 1.6 | 1.2 | 2.0 | 2.3 | 41.6 | 5245 | |
| 3x120 | 2 | 1.6 | 1.2 | 2.5 | 2.4 | 45.9 | 6677 | |
| 3x150 | 2 | 1.8 | 1.4 | 2.5 | 2.6 | 50.4 | 8016 | |
| 3x185 | 2 | 2.0 | 1.4 | 2.5 | 2.7 | 54.8 | 9466 | |
| 3x240 | 2 | 2.2 | 1.5 | 2.5 | 2.9 | 61.2 | 11805 | |
| 3x300 | 2 | 2.4 | 1.6 | 2.5 | 3.1 | 66.8 | 14181 | |
| 3x400 | 2 | 2.8 | 1.6 | 3.15 | 3.4 | 76.7 | 19235 | |
| 3x500 | 2 | 2.8 | 1.8 | 3.15 | 3.7 | 83.6 | 23011 | |
| 3 Cores+1 Earth Conductor | ||||||||
| 3x10/6 | 2 | 1.0 | 1.0 | 1.0 | 1.25 | 1.8 | 21.9 | 1140 |
| 3x16/10 | 2 | 1.0 | 1.0 | 1.0 | 1.6 | 1.8 | 24.2 | 1633 |
| 3x25/16 | 2 | 1.2 | 1.0 | 1.0 | 1.6 | 1.8 | 27.9 | 2145 |
| 3x35/16 | 2 | 1.2 | 1.0 | 1.0 | 1.6 | 1.9 | 30.8 | 2659 |
| 3x50/25 | 2 | 1.4 | 1.2 | 1.0 | 2.0 | 2.0 | 36.4 | 3739 |
| 3x70/35 | 2 | 1.4 | 1.2 | 1.2 | 2.0 | 2.1 | 40.1 | 4720 |
| 3x95/50 | 2 | 1.6 | 1.4 | 1.2 | 2.5 | 2.3 | 46.3 | 6398 |
| 3x120/70 | 2 | 1.6 | 1.4 | 1.4 | 2.5 | 2.4 | 50.3 | 7746 |
| 3x150/70 | 2 | 1.8 | 1.4 | 1.4 | 2.5 | 2.6 | 55.0 | 9128 |
| 3x185/95 | 2 | 2.0 | 1.6 | 1.4 | 2.5 | 2.7 | 60.3 | 10916 |
| 3x240/120 | 2 | 2.2 | 1.6 | 1.6 | 2.5 | 2.9 | 67.0 | 13713 |
| 3x300/150 | 2 | 2.4 | 1.8 | 1.6 | 3.15 | 3.1 | 74.6 | 17403 |
| 3x400/185 | 2 | 2.6 | 2.0 | 1.8 | 3.15 | 3.4 | 84.1 | 20704 |
| 3x500/240 | 2 | 2.8 | 2.2 | 2.0 | 3.15 | 3.7 | 91.8 | 25817 |
| 4 Cores | ||||||||
| 4x4.0 | 2 | 1.0 | 1.0 | 1.25 | 1.8 | 18.5 | 792 | |
| 4x6.0 | 2 | 1.0 | 1.0 | 1.25 | 1.8 | 19.7 | 931 | |
| 4x10 | 2 | 1.0 | 1.0 | 1.25 | 1.8 | 22.3 | 1185 | |
| 4x16 | 2 | 1.0 | 1.0 | 1.6 | 1.8 | 24.5 | 1672 | |
| 4x25 | 2 | 1.2 | 1.0 | 1.6 | 1.9 | 28.2 | 2260 | |
| 4x35 | 2 | 1.2 | 1.0 | 1.6 | 2.0 | 31.1 | 2854 | |
| 4x50 | 2 | 1.4 | 1.0 | 2.0 | 2.1 | 36.7 | 4013 | |
| 4x70 | 2 | 1.4 | 1.2 | 2.0 | 2.3 | 40.4 | 5104 | |
| 4x95 | 2 | 1.6 | 1.2 | 2.5 | 2.5 | 46.6 | 6996 | |
| 4x120 | 2 | 1.6 | 1.4 | 2.5 | 2.6 | 50.6 | 8400 | |
| 4x150 | 2 | 1.8 | 1.4 | 2.5 | 2.7 | 55.3 | 10008 | |
| 4x185 | 2 | 2.0 | 1.4 | 2.5 | 2.9 | 60.6 | 11906 | |
| 4x240 | 2 | 2.2 | 1.6 | 2.5 | 3.1 | 67.3 | 14963 | |
| 4x300 | 2 | 2.4 | 1.6 | 3.15 | 3.4 | 74.9 | 18944 | |
| 4x400 | 2 | 2.6 | 1.8 | 3.15 | 3.7 | 84.4 | 24304 | |
| 4x500 | 2 | 2.8 | 2.0 | 3.15 | 3.9 | 92.1 | 29351 | |
Note: Other conductor sizes & core confi gurations are available upon request.
| Conductor Operating Temperature | 70°C |
| Ambient Temperature | 30°C |
| Conductor crosssectional area | Reference Method C (clipped direct) | Reference Method E (in free air or on a perforated cable tray, horizontal or vertical) | Reference Method D (direct in in groud or in ducting in groud. in or around buildings) | |||
|---|---|---|---|---|---|---|
| 1 two-core cable, single-phase a.c. or d.c. | 1 three-or four core cable, three-phase a.c. | 1 two-core cable, singlephase a.c. or d.c. | 1 three-or four core cable, three-phase a.c. | 1 two-core cable, single-phase a.c. or d.c. | 1 three-or four core cable, threephase a.c. | |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 |
| mm2 | A | A | A | A | A | A |
| 1.5 | 21 | 18 | 22 | 19 | 22 | 18 |
| 2.5 | 28 | 25 | 31 | 26 | 29 | 24 |
| 4.0 | 38 | 33 | 41 | 35 | 37 | 30 |
| 6.0 | 49 | 42 | 53 | 45 | 46 | 38 |
| 10 | 67 | 58 | 72 | 62 | 60 | 50 |
| 16 | 89 | 77 | 97 | 83 | 78 | 64 |
| 25 | 118 | 102 | 128 | 110 | 99 | 82 |
| 35 | 145 | 125 | 157 | 135 | 119 | 98 |
| 50 | 175 | 151 | 190 | 163 | 140 | 116 |
| 70 | 222 | 192 | 241 | 207 | 173 | 143 |
| 95 | 269 | 231 | 291 | 251 | 204 | 169 |
| 120 | 310 | 267 | 336 | 290 | 231 | 192 |
| 150 | 356 | 306 | 386 | 332 | 261 | 217 |
| 185 | 405 | 348 | 439 | 378 | 292 | 243 |
| 240 | 476 | 409 | 516 | 445 | 336 | 280 |
| 300 | 547 | 469 | 592 | 510 | 379 | 316 |
| 400 | 621 | 540 | 683 | 590 | - | - |
| Nominal Cross Section Area | Two-core cables d.c. | Two-core cable, single-phase a.c. | Three- or four-core cable, three-phase a.c. | ||||
|---|---|---|---|---|---|---|---|
| 1 | 2 | 3 | 4 | ||||
| mm2 | mV/A/m | mV/A/m | mV/A/m | ||||
| 1.5 | 29 | 29 | 25 | ||||
| 2.5 | 18 | 18 | 15 | ||||
| 4.0 | 11 | 11 | 9.5 | ||||
| 6.0 | 7.3 | 7.3 | 6.4 | ||||
| 10 | 4.4 | 4.4 | 3.8 | ||||
| 16 | 2.8 | 2.8 | 2.4 | ||||
| r | x | z | r | x | z | ||
| 25 | 1.75 | 1.75 | 0.170 | 1.75 | 1.50 | 0.145 | 1.50 |
| 35 | 1.25 | 1.25 | 0.165 | 1.25 | 1.10 | 0.145 | 1.10 |
| 50 | 0.93 | 0.93 | 0.165 | 0.94 | 0.80 | 0.140 | 0.81 |
| 70 | 0.63 | 0.63 | 0.160 | 0.65 | 0.55 | 0.140 | 0.57 |
| 95 | 0.46 | 0.47 | 0.155 | 0.50 | 0.41 | 0.135 | 0.43 |
| 120 | 0.36 | 0.38 | 0.155 | 0.41 | 0.33 | 0.135 | 0.35 |
| 150 | 0.29 | 0.30 | 0.155 | 0.34 | 0.26 | 0.130 | 0.29 |
| 185 | 0.23 | 0.25 | 0.150 | 0.29 | 0.21 | 0.130 | 0.25 |
| 240 | 0.180 | 0.190 | 0.150 | 0.24 | 0.165 | 0.130 | 0.21 |
| 300 | 0.145 | 0.155 | 0.145 | 0.21 | 0.135 | 0.130 | 0.185 |
| 400 | 0.105 | 0.115 | 0.145 | 0.185 | 0.100 | 0.125 | 0.160 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance
KEY FEATURES
- Manufactured according to IEC 60502-1 requirements
- 600/1000V voltage rating
- Multi-core power cable construction
- PVC insulated conductors
- PVC outer sheath
- Armoured cable design
- Suitable for fixed low voltage power distribution
- Suitable for underground and outdoor installation
- Suitable for industrial and infrastructure projects
- Provides improved mechanical protection
SELECTION NOTES
Before quotation, please confirm:
- Voltage rating
- Number of cores
- Conductor size
- Conductor material
- Armour type
- Cable length
- Sheath colour
- Installation method
- Installation environment
- Required standard or project specification
- Packing requirement
- Destination port or delivery address
600/1000V PVC insulated PVC sheathed armoured cable is commonly selected for low voltage power distribution where mechanical protection is required.
It is suitable for underground cable routes, industrial plants, outdoor installation and infrastructure power systems.
RELATED CABLE TYPES
- IEC 60502 low voltage cable
- PVC insulated PVC sheathed armoured cable
- XLPE insulated PVC sheathed armoured cable
- XLPE PVC armoured cable
- XLPE PVC unarmoured cable
- BS5467 armoured power cable
- BS6724 LSZH armoured cable
- 600/1000V power cable
- Low voltage power cable
- Underground power cable
FAQ
What is this 600/1000V PVC armoured cable used for?
It is used for fixed low voltage power distribution.
It is suitable for industrial plants, commercial buildings, infrastructure projects, underground cable routes and outdoor installations.
What standard does this cable follow?
This cable is designed according to IEC 60502-1 requirements.
Is this cable armoured?
Yes. This cable has an armoured construction.
The armour provides improved mechanical protection.
Can this cable be used underground?
Yes. It can be used for underground cable routes and cable trenches.
The final installation should follow project specifications and local installation requirements.
What is the difference between PVC insulated cable and XLPE insulated cable?
This cable uses PVC insulation.
XLPE insulated cable normally offers higher thermal performance.
The final choice depends on the project requirement.
What information is required for quotation?
Please confirm voltage rating, number of cores, conductor size, armour type and cable length.