300/500V Mica+LSZH Insulated, Non-sheathed Power Cables to BS EN 50525-3-41 (Single Core)
APPLICATIONThe cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.STANDARDSBasic design adapted from BS EN 50525-3-41(formerly BS 7211)FIRE PE…
300_500V Mica+LSZH Insulated, Non-sheathed PowerCables to BS EN 50525-3-41 (Single Core).pdf Contact us

APPLICATION

The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.

STANDARDS

Basic design adapted from BS EN 50525-3-41(formerly BS 7211)

FIRE PERFORMANCE

Circuit IntegrityIEC 60331-21; BS 6387
Flame Retardance (Single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Halogen freeIEC 60754-1; EN 50267-2-1
No Corrosive Gas EmissionIEC60754-2; EN 50267-2-2
Minimum Smoke EmissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

Conductor : Copper conductor according to BS EN 60228 class 1/5.

Fire Barrier : Mica glass tape.

Insulation : Crosslinked polyolefin material type EI 5 according to EN 50363-5.

Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow. Bi-colours of any combination of the above mono-colours are permitted.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius : 4 x Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFRP300-05mZ-U/K
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessMin. Overall DiameterMax. Overall DiameterApprox. Weight
No.×mm² mmmmmmkg/km
1×0.510.62.93.413.5
1×0.7510.63.13.616.5
1×1.010.63.23.819.7
1×0.550.63.13.614.2
1×0.7550.63.23.817.7
1×1.050.63.43.920.7

ELECTRICAL PROPERTIES

Conductor operating temperature: 90°C

Ambient temperature: 30°C

CURRENT-CARRYING CAPACITIES (AMP)

Conductor cross-sectional areaSingle-phase a.c.Three-phase a.c.
mm²AA
0.533
0.7566
1.01010

Note: These values apply to the majority of cases. further information should be sought in unusual cases eg.:

When high ambient temperatures are involved, ie. above 30°C

Where long lengths are used

Where ventilation is restricted

Where the cords are used for other purposes, ego internal wiring of apparatus.

VOLTAGE DROP (PER AMP PER METER)

Conductor cross-sectional area2 cables d.c.2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
Ref. Methods A&B (enclosed in conduit or trunking)Ref. Methods C, F&G (clipped direct, on trays or in free air)Ref. Methods A&B (enclosed in conduit or trunking)Ref. Methods C, F&G (clipped direct, on trays or in free air)
Cables touchingCables spaced*Cables touching, TrefoilCables touching, flatCables spaced*, flat
123456789
mm²mV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/m
0.510110110110187878787
0.756868686859595959
1.05050505044444444

Note: *Spacings larger than one cable diameter will result in a large voltage drop.