whatsapp
backtop
AS/NZS 5000/Zero Halogen Flame Retardant 110°C Double Insulated Cable, 0.6/1kV
APPLICATIONComplies with the AS/NZS 3000 Electrical Standard and the GB/T 12706.1-2020 Cable Standard, and has passed the inspection by the National Wire and Cable Quality Supervision and Inspection Center.”Complies with the AS/NZS 3000 Electrical St…
21 Zero Halogen Flame Retardant 110degC DoubleInsulated Cable, 0.6_1kV.pdf Contact us

APPLICATION

High-quality cables that comply with the AS/NZS 3000 electrical standard and the GB/T 12706.1-2020 cable standard, and have passed testing by the National Wire and Cable Quality Supervision and Inspection Center. The products are manufactured in strict accordance with international standards such as AS/NZS 5000.1, AS1125, and AS3808. They feature conductors made of 0.2mm stranded soft copper wire compliant with AS 1125, insulation that meets the R-E-110 specification in AS3808 (standard color: white), and an outer sheath made of HFS-110-TP material (standard colors: orange and black, other colors customizable). This series offers a comprehensive range of specifications, from 10mm² to 120mm², with excellent electrical performance, low resistance, strong current-carrying capacity, and minimal voltage drop. Suitable for various single-phase and three-phase power configurations, the cables provide detailed structural parameters, including the number of cores, conductor structure, insulation and sheath thickness, outer diameter, and reference weight, meeting the demanding requirements of industrial and commercial power applications. Choosing us means selecting a safe, reliable, and compliant cable solution for your project.

STANDARD

  • AS/NZS 5000.1

  • AS1125

  • AS3808

CONSTRUCTION

ConductorNominal 0.2mm stranded flexible plain copper wire to AS 1125
InsulationR -E-110 to AS3808
Insulation Colour:White
Sheath:HFS-110-TP to comply with AS3808
Sheath Colours:Orange , Black - other colours available by request

TECHNICAL CHARACTERISTICS

Conductor SizeElectrical Resistance @20.CCurrent Ratìng' AMPS 2 single coresVoltage Drop mV 1Am at Max operating Temperature
mm^2Ohm/kmSingle PhaseThree Phase
101.9101054.974.30
161.2101353.132.70
250.7801851.991.72
350.5542251.441.24
500.3862751.070.92
700.2723500.7690.65
950.2064350.5670.48
1200.1615100.4650.39

CABLE PARAMETER

Conductor SizeNo.of coresConductor No./ ODNominal Insulation ThicknessNominal Sheath ThicknessNominal O.D.Approx. Cable Weight
mm^2 mmmmmmmmkg/100m
101322/0.21.01.49.116.30
161511/0.21.01.410.123.40
251784/0.21.21.411.833.60
35111201021.21.413.144.60
5011568/0.21.41.414.962.50
7012240/0.21.41.417.081 .80
9513040/0.21.61.519.3113.00
12013800/0.21.61.520.8137.40