600/1000V LSZH Insulated, Non-sheathed Power Cables to BS EN 50525-3-41 (Single Core)
APPLICATIONThe cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.STANDARDSBasic design adapted to BS EN 50525-3-41FIRE PERFORMANCEFlame Retar…
600_1000V LSZH Insulated, Non-sheathed Power Cables to BS EN 50525-3-41 (Single Core).pdf Contact us

APPLICATION

This cable product is mainly suitable for various critical locations, including but not limited to power stations, underground passenger transport systems of urban rail transit, airports, petrochemical plants, hotels, hospitals, and high-rise buildings. In these places where extremely high requirements are placed on the stability and safety of power supply, our cables can deliver excellent performance and ensure reliable power transmission.

STANDARDS

Basic design adapted to BS EN 50525-3-41

FIRE PERFORMANCE

Flame Retardance (Single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Halogen FreeIEC 60754-1; EN 50267-2-1
No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2
Minimum Smoke EmissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

Conductor : Annealed copper conductor, stranded according to BS EN 60228 class 2.

Insulation : Crosslinked polyolefin material type EI 5 according to EN 50363-5.

Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow. Bi-colours of any combination of the above mono-colours are permitted.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius :

OD<8mm : 4 × Overall Diameter

8mm≤OD≤12mm : 5 × Overall Diameter

OD>12mm : 6 × Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFLP600-Z-R
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessNominal Overall DiameterApprox. Weight
No.×mm² mmmmkg/km
1x1.520.73.123
1x2.520.83.735
1x4.020.84.352
1x6.020.84.873
1x1021.06.2120
1x1621.07.2180
1x2521.29.0285
1x3521.210.2375
1x5021.412.0510
1x7021.414.0720
1x9521.616.0995
1x12021.618.01230
1x15021.820.01520
1x18522.022.01900
1x24022.225.02480
1x30022.428.03100
1x40022.631.53950
1x50022.835.04950
1x63022.839.06360

ELECTRICAL PROPERTIES

Conductor operating temperature : 90°C

Ambient temperature : 30°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4E1A

Conductor cross-sectional areaRef. Method A (enclosed in conduit in thermally insulating wall etc.)Ref. Method B (enclosed in conduit on a wall or in trunking etc.)Ref. Method C (clipped direct)Ref. Method F (in free air or on a perforated cable tray, horizontal or vertical etc.) TouchingRef. Method G (in free air) spaced by one cable diameter
2 cables, single-phase a.c. or d.c.3 or 4 cables, three-phase a.c.2 cables, single-phase a.c. or d.c3 or 4 cables, three-phase a.c.2 cables, single-phase a.c. or d.c. flat and touching3 or 4 cables, three-phase a.c. flat and touching or trefoil2 cables, single-phase a.c. or d.c. flat3 cables, three-phase a.c. flat3 cables, three-phase a.c. trefoil2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat
HorizontalVertical
123456789101112
mm²AAAAAAAAAAA
1.5191723202523-----
2.5262331283431-----
4.0353142374641-----
6.0454054485954-----
10615475668174-----
1681731008810999-----
2510695133117143130161141135182161
35131117164144176161200176169226201
50158141198175228209242216207275246
70200179253222293268310279268353318
95241216306269355326377342328430389
120278249354312413379437400383500454
150318285393342476436504464444577527
185362324449384545500575533510661605
240424380528450644590679634607781719
300486435603514743681783736703902833
400--68358486879394086882310851008
500--783666990904108399894612531169
630--9007641130103312541151108814541362

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E1B

Conductor cross-sectional area2 cables d.c.2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
Ref. Methods A&B (enclosed in conduit or trunking)Ref. Methods C, F&G (clipped direct, on trays or in free air)Ref. Methods A&B (enclosed in conduit or trunking)Ref. Methods C, F&G (clipped direct, on trays or in free air)
cables touchingcables spaced*Cables touching, TrefoilCables touching, FlatCables spaced*, Flat
123456789
mm²mV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/m
1.53131313127272727
2.51919191916161616
4.01212121210101010
6.07.97.97.97.96.86.86.86.8
104.74.74.74.74.04.04.04.0
162.92.92.92.92.52.52.52.5


rxzrxzrxzrxzrxzrxzrxz
251.851.850.311.901.850.1901.851.850.281.851.600.271.651.600.1651.601.600.1901.601.600.271.65
351.351.350.291.351.350.1801.351.350.271.351.150.251.151.150.1551.151.150.1801.151.150.261.20
500.991.000.291.050.990.1801.000.990.271.000.870.250.900.860.1550.870.860.1800.870.860.260.89
700.680.700.280.750.680.1750.710.680.260.730.600.240.650.590.1500.610.590.1750.620.590.250.65
950.490.510.270.580.490.1700.520.490.260.560.440.230.500.430.1450.450.430.1700.460.430.250.49
1200.390.410.260.480.390.1650.430.390.250.470.350.230.420.340.1400.370.340.1650.380.340.240.42
1500.320.330.260.430.320.1650.360.320.250.410.290.230.370.280.1400.310.280.1650.320.280.240.37
1850.250.270.260.370.260.1650.300.250.250.360.230.230.320.220.1400.260.220.1650.280.220.240.33
2400.1900.210.260.330.200.1600.250.1950.250.310.1850.220.290.1700.1400.220.1700.1650.240.1700.240.29
3000.1550.1750.250.310.1600.1600.220.1550.250.290.1500.220.270.1400.1400.1950.1350.1600.210.1350.240.27
4000.1200.1400.250.290.1300.1550.200.1250.240.270.1250.220.250.1100.1350.1750.1100.1600.1950.1100.240.26
5000.0930.1200.250.280.1050.1550.1850.0980.240.260.1000.220.240.0900.1350.1600.0880.1600.1800.0850.240.25
6300.0720.1000.250.270.0860.1550.1750.0780.240.250.0880.210.230.0740.1350.1500.0710.1600.1700.0680.230.24

Note : *Spacings larger than one cable diameter will result in a large voltage drop.

r = conductor resistance at operating temperature

x = reactance

z = impedance