For underground L2-BUS routes between automation equipment, this cable combines a PVC inner jacket with a PE outer jacket. The screened signal pair uses solid bare copper conductors and foam-skin PE insulation. Its two-jacket construction distinguishes it from the indoor and single-jacket outdoor versions.
Type/Area of Application: Underground Laying
Cable Construction: 1x2x0.64 mm
Inner Conductor Diameter: Copper, bare (AWG 22/1)
Conductor Insulation: Foam-skin-PE
Conductor Colors: Red, green
Stranding Element: 2 conductors + 2 fillers stranded together
Shielding: Polyester foil, aluminum lined
Total Shielding: Copper braid, tinned
Inner Jacket Material: PVC
Outer Jacket Material: PE
Outer Diameter: 10.0 mm ± 0.2 mm
Outer Jacket Color: Black
| Characteristic Impedance@3-20MHz | 150 Ω ± 10 Ω | ||||
| Conductor Resistance | 57.1 Ohm/km max. | ||||
| Insulation Resistance | 1.00 GOhm x km min. | ||||
| Mutual Capacitance@1 KHz | 30.0 nF/km nom. | ||||
| Working Voltage | Max: 250V | ||||
| Test Voltage | 1.5 KV | ||||
| Attenuation | 9.6 | kHz | < | 2.1 | dB/km |
| 38.4 | kHz | < | 3.1 | dB/km | |
| 3.0 | MHz | < | 18.2 | dB/km | |
| 20.0 | MHz | < | 47.0 | dB/km | |
| Weight | approximately 92.0 kg/km |
| Min. Bending Radius for Laying | 18 x OD mm |
| Operating Temperature Range, min. | -40°C |
| Operating Temperature Range, max. | +70°C |
PVC inner jacket beneath a black PE outer jacket.
Aluminium-lined foil and overall tinned copper braid screens.
150 ± 10 ohms impedance at 3–20 MHz; 10.0 ± 0.2 mm outer diameter.
Plan the underground route, entry points and mechanical protection with the installation design. Size ducts, glands and supports for the 10.0 mm nominal diameter, and maintain the listed laying bend radius of 18 times the overall diameter.
Profibus L2 Outdoor and Industry Cable, 150 Ohm, PE or PUR Sheath
Profibus L2 Indoor Cable, 150 Ohm, Foil and Braid Screened, PVC
Profibus SK Indoor and Outdoor Cable, 150 Ohm, PVC or PE Sheath
The cable is specified for underground laying and has separate PVC inner and PE outer jackets.
Bare copper AWG 22/1 conductors with red and green foam-skin PE insulation.
An aluminium-lined polyester foil and a tinned copper braid provide the two screening layers.
The technical data specify 18 times the overall cable diameter.
The listed outer diameter is 10.0 ± 0.2 mm and the approximate cable weight is 92.0 kg/km.